7.8 Measurement modules
This is measurement data that can be read in Hydro MPC,
Control MPC and Hydro Multi-E.
PROFIBUS/PROFINET direction: Inputs.
Module Name
Data
type
Unit
Description
MP
C
M
u
lti-E
model G
Multi-E/TPED model
H and l
a
ter
M
A
GNA3-D
3
WarningCode
5
-
The Grundfos-specific warning code.
For a list of warning codes. See section
●
-
●
●
4
FaultCode
5
-
The Grundfos-specific alarm code.
For a list of alarm codes. See section
●
●
●
●
5
VolumeFlow
8
m
3
/h
Provides the flow through the system as estimated or
measured.
S
S
S
●
6
Head
8
bar
Provides the differential pressure between inlet and outlet
as estimated, or measured, by the booster system.
S
S
S
●
7
RemotePressure
8
bar
Provides the measured pressure at an external pressure
sensor. This pressure sensor must be installed for this
value to be valid.
S
-
S
S
8
InletPressure
8
bar
Provides the inlet pressure if a pressure sensor is
configured and installed at the inlet.
It has an offset of -1.000 bar.
S
-
S
-
9
OutletPressure
8
bar
Provides the outlet pressure measured by a pressure
sensor.
S
-
S
-
10
Level
8
m
Provides the tank level.
Requires that a level sensor is installed.
It has an offset of -100 metres.
S
S
S
-
11
FeedTankLevel
8
m
Provides the feed tank level.
Requires that a level sensor is installed.
It has an offset of -100 metres.
S
-
S
-
12
Power
8
W
Provides the actual power consumed by the booster
system.
●
**
●
●
●
13
Energy
8
Wh
Provides the accumulated electric energy consumption of
the system.
●
**
●
●
●
14
RemoteTemperature
8
°C
Provides the temperature measured by a remote
temperature sensor.
S
S
S
-
15
AmbientTemperature
8
°C
Provides the ambient temperature measured by a
temperature sensor.
S
-
S
-
16
InletTemp
8
°C
Provides the inlet temperature measured by a temperature
sensor.
S
-
-
-
17
OutletTemp
8
°C
Provides the outlet temperature measured by a
temperature sensor.
S
-
-
-
18
TemperatureDifference
8
°C
Provides the differential temperature.
S
-
-
-
19
OperationTime
8
h
Provides the total operating hours of the booster system.
●
●
●
●
20
ActualSetpoint
8
%
Selected system control-loop setpoint.
See description of scaling for a setpoint in
module (ControlModule, module 2)
●
●
●
●
21
RelativePerformance
8
%
Value of speed control signal to pumps that are not
stopped or running at maximum speed.
●
●
●
●