                               Installation Procedures

Page 5

Page 6

Installation Procedures

9. Making the Wiring Connections

Single-Phase 2-wire

Wiring Diagram

for GRUNDFOS Motors

Black

Black

Pressure

Switch

Pump & Motor

Quick Disconnect

Green

10 2- Wire Pump

with Ground

 A capacitor or control box should NEVER be

connected to a Redi-Flo3 submersible pump.

WARNING!

To reduce the risk of electric shock during operation of this pump

requires the provision of acceptable grounding. If the means of

connection to the supply connected box is other than grounded metal

conduit, ground the pump back to the service by connecting a copper

conductor, at least the size of the circuit supplying the pump.

SINGLE-PHASE    60 HZ 

 Maximum Cable Length Motor Service to Entrance

         Motor Rating

Copper Wire Size

VOLTS

HP

14

12

10

8

6

4

2

0

00

115

 1

/

3

130

210

340

540

840

1300

1960

2910

1

/

2

100

160

250

390

620

960

1460

2160

230

 

1

/

3

550

880

1390

2190

3400

5250

7960

 

1

/

2

400

650

1020

1610

2510

3880

5880

 

3

/

4

300

480

760

1200

1870

2890

4370

6470

1

250

400

630

990

1540

2380

3610

5360

6520

1

/

2

190

310

480

770

1200

1870

2850

4280

5240

10.  Cable Sizing

Fig. 5

11.  Motor Cable

Redi-Flo3 pumps are specifically designed to be used with Grundfos SQE-
NE Tefzel motor leads. Standard SQE-NE Tefzel motor leads are
available between 25 and 300 foot lengths in 5 foot increments. Custom
lengths longer than 300 feet are available in 10 foot increments up to 600
feet from the factory.

Summary of Contents for 10SQE03A-100-NE

Page 1: ...t Permanent Magnet Motor High Starting Torque Soft Start 2 seconds to reach maximum rpm and maximum pressure Built in Smart Motor Protection with automatic restart Communication Through the Redi Flo3...

Page 2: ...ORANYINCIDENTALORCONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHERCAUSES THEREARENOEXPRESSORIMPLIEDWARRANTIES INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PU...

Page 3: ...p life and optimal performance can best be obtained through proper well development and in the case of higher fluid temperatures use a cooling shroud A check should be made to ensure that the installa...

Page 4: ...uid It is recommended to check and if needed refill the motor with GRUNDFOS motor fluid SML 2 If the pump is to be installed horizontally e g in a tank and there is a risk that the pump might be cover...

Page 5: ...l position with an inclination of approx 10 3 Remove the filling plug using a screwdriver or a similar tool 4 Inject motor liquid into the motor with a filling syringe or similar tool see fig 3 5 To a...

Page 6: ...the pump is connected to an installation where a Ground Fault circuit breaker GFI is used as additional protection this circuit breaker must trip out when ground fault currents with DC content pulsat...

Page 7: ...trol box should NEVER be connected to a Redi Flo3 submersible pump WARNING To reduce the risk of electric shock during operation of this pump requires the provision of acceptable grounding If the mean...

Page 8: ...50 1020 1610 2510 3880 5880 3 4 300 480 760 1200 1870 2890 4370 6470 1 250 400 630 990 1540 2380 3610 5360 6520 1 1 2 190 310 480 770 1200 1870 2850 4280 5240 10 Cable Sizing 11 Motor Cable Redi Flo3...

Page 9: ...Check that the motor socket is clean and dry 4 Press the cable plug into the motor socket The plug will only fit one way see fig 6 5 Install and tighten the four nuts see fig 6 When the plug has been...

Page 10: ...l cut and fit together tightly to ensure that they do not work loose 15 Installing the Pump Installation Depth The dynamic water level should always be above the pump see fig 11 A Dynamic water level...

Page 11: ...e correct size generator for the motor HP 16 Installing the Pump cont 4 Lower the pump into the well Make sure the motor cable is not damaged when the pump is lifted or lowered into the well especiall...

Page 12: ...denly falls the reason might be that the pump is pumping more water than the well can yield Water Impurities If there are impurities in the water the valve should be opened gradually as the water beco...

Page 13: ...overload overtemperature MSE 3NE Motors Note To set Dry Run limit in the MSE NE pumps you need to connect the pump to a Redi Flo3 status box Refer to Redi Flo3 status box I O for proper connections To...

Page 14: ...shaft end with a vegetable based grease 3 Screw the pump end on the motor A spanner may be used on the clamping faces of the pump part see fig 12 4 Install cable guard as described on page 7 When pump...

Page 15: ...is larger than anticipated capacity b The valve s in the discharge pipe are partly closed blocked c The discharge pipe is partly chocked by impurities Iron bacteria d The non return valve of the pump...

Page 16: ...e the valve oked Pull out the pump Check and clean or replace the pump if necessary Clean the pipes Repair replace the pump Check and repair the piping Replace Check the electricity supply Increase th...

Page 17: ...sed in the product please deliver the product or any hazardous materials from it to your nearest GRUNDFOS company or service center Insulation Test Resistance Test High voltage Test Measure the voltag...

Page 18: ...15SQE NE 1 1 4 NPT 22 30SQE NE 1 1 2 NPT STORAGE CONDITIONS Minimum Ambient Temperature 4 F Maximum Ambient Temperature 140 F Freeze Protection If the pump has to be stored after use it must be store...

Page 19: ...7 6 10SQE10C 260 NE 1 C 230V 7 6 10SQE10C 300 NE 1 C 230V 7 6 10SQE15C 340 NE 1 1 2 C 230V 11 1 15SQE03A 70 NE 1 3 A 230V 115V 3 9 7 8 15SQE05A 110 NE 1 2 A 230V 115V 4 9 9 8 15SQE05B 130 NE 1 2 B 23...

Page 20: ...s SPP1 Potentiometer 625468 RediFlo3 Motor Leads available in 5ft increments See price list 25ft 96037428 50ft 96037429 75ft 96037430 100ft 96037431 125ft 96037432 150ft 96037433 175ft 96037434 200ft...

Reviews: