Installation
20 | 80
B
A
_
T
D3
-B
M
0
0
2
e
n
_
0
0
4
_
so
ft
liQ
-MD
4.1
Requirements for the installation site
Observe local installation directives, general guidelines and technical specifications.
● The installation site must be frost-proof and ensure the product is protected from
chemicals, dyes, solvents and vapours.
● If the softened water is intended for human consumption in the sense of the
German Drinking Water Ordinance, the ambient temperature must not exceed
25 °C. For applications that are purely technical, the ambient temperature must not
exceed 40 °C.
● Always install a drinking water filter and, if required, a pressure reducer (e.g. fine
filter pureliQ:KD) upstream of the product.
● A shock-proof socket is required within a distance of approx. 1.2 m of the system.
The socket requires a permanent power supply and must not be connected to light
switches, emergency heating switches or similar devices.
● A drain connection (DN 50) must be available to discharge the regeneration water.
● There must be a water withdrawal point near the product.
● A floor drain suitable for the system size must be available at the installation site
or a protection device e.g. protectliQ or a protection device with water stop of the
same quality must be installed.
● Ensure that lifting systems are resistant to salt water or use our regeneration water
delivery pump (refer to chapter 3.7).