Requirements regarding the installation site
Observe local installation directives, general guidelines and technical specifications.
● The installation site must be frost-proof and ensure the filter's protection from
chemicals, dyes, solvents, vapours and direct sunlight.
● A drain connection (DN 50) must be available to discharge the backwash water.
● The installation room must provide a floor drain. If no floor drain is available, an
appropriate safety device must be installed in order to prevent water damage. We
recommend using a protectliQ:A.
● The installation site must be easily accessible for maintenance purposes.
● A shock-proof socket is required within a distance of approx. 1.2 m of the system.
NOTE:
Power failure during the backwash process.
● Backwash will not be completed if the electrical power supply is interrupted.
● The backwash process continues until it is terminated manually.
► Do not connect the socket with light and heating switches.