background image

GR - UM -140-A- 01

Growatt 10000TL3-S

Growatt 12000TL3-S

Growatt 9000TL3-S

Growatt 12000TL3

Growatt 8000TL3-S

Growatt 7000TL3-S

Growatt 6000TL3-S

Growatt 5000TL3-S

Growatt 4000TL3-S

Growatt 3000TL3-S

Growatt 11000TL3-S

Growatt 13000TL3-S
Growatt 15000TL3-S

Installation   
                       

Operation Manual

Shenzhen Growatt New Energy Technology CO.,LTD

No.28 Guangming Road, Longteng Community, 
Shiyan, Bao'an District, Shenzhen, P.R.China

 + 86 755 2747 1942 
 

[email protected]

 www.ginverter.com

T
E
W

Summary of Contents for 10000TL3-S

Page 1: ...L3 S Growatt 5000TL3 S Growatt 4000TL3 S Growatt 3000TL3 S Growatt 11000TL3 S Growatt 13000TL3 S Growatt 15000TL3 S Installation Operation Manual Shenzhen Growatt New Energy Technology CO LTD No 28 Gu...

Page 2: ...3 4 Transportation Unpacking Index 1 2 3 4 2 2 Safety Precautions Installation 5 5 1 Safety instruction 5 2 Selecting the Installation Location 2 3 Assembly Warnings 2 4 Electrical Connection Warning...

Page 3: ...the Inverter 8 2 Checking the DC Disconnect Trouble shooting 9 10 1 Dismantling the Inverter 10 2 Packing the Inverter Decommissioning 10 10 3 Disposing of the Inverter Specification 11 Certificates...

Page 4: ...ch if not avoided could result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury NOTICE indicates a situation which if not...

Page 5: ...r coupling capacity does not exceed 2 2uF During feed in operation a leakage current flows from the cells to earth the size of which depends on the manner in which the PV modules are installed e g foi...

Page 6: ...AC current generated as follows 5 6 2 2 Safety Precautions The TL3 S series Inverter is designed and tested according to Internalational safety requirements however certain safety precautions must be...

Page 7: ...ions comply with all corresponding safety symbols and markings present on the unit and in this manual In special cases there may still be interference for the specified application area despite mainta...

Page 8: ...f there are lots of inverters need to be stored the maximum layers for original carton is four After long term storage local installer or service department of manufacturer should perform a comprehens...

Page 9: ...it values e g when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers In this case the operator is obliged to take proper action to r...

Page 10: ...c panel is exposed to light it generates a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors pres...

Page 11: ...me installation countries a second protective conductor is required to prevent a touch current in the event of a malfunction in the original protective conductor For installation countries falling wit...

Page 12: ...re to the sunlight may cause additional internal heating which will cause power derating More than one inverter need to be installed the dimensions below should be considered Fig5 6 Fig5 7 Fig 5 8 Rec...

Page 13: ...grid voltage and frequency Voltage 400Vac Frequency 50Hz 60Hz 3 Phase Open the breaker between the PV inverter and utility Specification of AC breaker Cable requirements 1 The AC side terminals of th...

Page 14: ...he inverter To reduce the risk of electric shock avoid touching the live components and treat the terminals carefully Information Please use the same brand male and female PV connectors Under any cond...

Page 15: ...e maximum string currents are varying from different inverter types Model Max current 7000TL3 S 3000 6000TL3 S 8000 9000TL3 S 10000 11000TL3 S 12000TL3 12000 15000TL3 S 11 5A 11 5A 11A 11A 11 5A 11 5A...

Page 16: ...es The inverter starts up automatically when DC power from the PV panel is sufficient Fault Mode The internal intelligent controller can continuously monitor and adjust the system status If inverter f...

Page 17: ...afety standard must be selected by the DIP switch The DIP switch is composed of four digit binary number PINS The different combination of the four PINS can represent different inverter s model which...

Page 18: ...4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 AS4777_Newzealand GT1XXXXXX0 Reserved GT1XXXXXX1 India GT1XXXXXX2 EN50438_Demark GT1XXXXXX3 EN50438_Sweden GT1XXXXXX4 EN50438_Norway G...

Page 19: ...l 2000 Kwh AC Volt A B C 230V 230V 230V Set Language Set Language English Once Once Once Double Fig6 3 Overall display interface Power on display After inverter restarts the background light will last...

Page 20: ...Com Address 001 Set Language Set Date Time AC V Control Disable Enable Once Once Once Setting Three Set Language English Double AC V Control Disable Double Double Date 2012 04 05 Time 14 20 38 Settin...

Page 21: ...ime Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 21 38 Set OK Double Once Double Once Double Once Dou...

Page 22: ...ication systems You can update firmware via RS232 or Rs485 The connecting diagram as follow Active power control with a ripple control signal receiver Through RS485 interface RS485 232 RS232 converter...

Page 23: ...t be more than 32 6 5 3 RS485 cable connection Rs485 cable connection Pin1 TR B Pin2 Shielding layer or no connection Definitions of RS485 PLUG standard as follows Pin1 TR B Pin2 Shielding layer or no...

Page 24: ...recommended as STP FTP ASTP 4 Plug in two terminals Cover the fix board Information Tighten 4 pcs screws first then tighten cable gland 5 Tighten 4pcs screws and cable gland Note 1 As to the connecti...

Page 25: ...off the DC switch of the inverter 3 Check the inverter operating status 4 Until the display of LCD goes out the inverter is shut down Once the output power is derating because of too high warming some...

Page 26: ...acing inverter Error message Description Suggestion Error 124 No AC connection Check AC wiring Check the status of AC breaker PV Isolation Low Insulation problem 1 Check if panel enclosure ground prop...

Page 27: ...oblem still exist Contact Growatt Warning 109 Warning 108 PV 1 or PV2 Circuit short PV 1 or PV2 boost broken Check the PV panel polarity Restart the inverter If the warning still exist please contact...

Page 28: ...unit and where applicable any accessories are disposed of in a proper manner 11 Specification 11 1 Specification of TL3 S Model 3000TL3 S 4000TL3 S 6000TL3 S 5000TL3 S Specification Input data Max DC...

Page 29: ...wer factor at rated power 1 1 1 1 Adjustable displacement power factor THDi Full load THDv 1 0 8leading 0 8laging AC grid connection type 3 3 3 3 3W N PE 3W N PE 3W N PE 3W N PE Protection devices DC...

Page 30: ...current 11 7A 13 3A 15A Rated AC output power 7kW 8kW 9kW Max AC apparent power 7 7kVA 8 8kVA 9 9kVA 33A 33A 33A 16A 20A 25A 310 476V 310 476V 310 476V 2 1 1 2 1 1 Efficiency Max efficiency 98 3 98 3...

Page 31: ...age 160V 160V 160V PV voltage range 160V 1000V 160V 1000V 160V 1000V MPP voltage range DC nominal voltage 200V 1000V 600V Max PV Isc 16A 16A 16A 16A 16A 16A Number of independent MPP trackers strings...

Page 32: ...monitoring unit yes yes yes General Data Dimensions W H D in mm Weight Operating temperature range 25 C 60 C 13 F 140 F With derating above 45 C 113 F Noise emission typical 35 dB A 480 448 200 22kg 2...

Page 33: ...current 19A 20 6A 23 8A Rated AC output power 12kW 13kW 15kW Max AC apparent power 13 2kVA 14 3kVA 16 5kVA 44A 44A 44A 25A 32A 32A 310 476V 310 476V 310 476V 2 2 1 2 2 1 Efficiency Max efficiency 98 3...

Page 34: ...tion night 0 5 W 11 2 DC connector info DC connector Specification 11 3 Torque Values Enclosure lid screws 0 7Nm 6 2 1bf in Shell and RS232 screws 0 7Nm 6 2 1bf in AC terminal 0 6Nm 5 2 1bf in M6 sock...

Page 35: ...or your dealer Name Description Communication interface Wi Fi Communication interface Shine WebBox Communication data logger Shine Vision receiver Communication data logger receiver Shine Vision emitt...

Page 36: ...14 Contact If you have technical problems concerning our products contact your installer or manufacturer During inquiring please provide below information 1 Inverter type 2 Modules information 3 Commu...

Page 37: ...TL3 S Growatt 7000TL3 S Growatt 11000TL3 S Growatt 13000TL3 S Growatt 15000TL3 S Installation Operation Manual Shenzhen Growatt New Energy Technology CO LTD No 28 Guangming Road Longteng Community Shi...

Page 38: ...3 4 Transportation Unpacking Index 1 2 3 4 2 2 Safety Precautions Installation 5 5 1 Safety instruction 5 2 Selecting the Installation Location 2 3 Assembly Warnings 2 4 Electrical Connection Warning...

Page 39: ...the Inverter 8 2 Checking the DC Disconnect Trouble shooting 9 10 1 Dismantling the Inverter 10 2 Packing the Inverter Decommissioning 10 10 3 Disposing of the Inverter Specification 11 Certificates...

Page 40: ...indicates a hazardous situation which if not avoided could result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury NOTIC...

Page 41: ...r coupling capacity does not exceed 2 2uF During feed in operation a leakage current flows from the cells to earth the size of which depends on the manner in which the PV modules are installed e g foi...

Page 42: ...AC current generated as follows 5 6 2 2 Safety Precautions The TL3 S series Inverter is designed and tested according to Internalational safety requirements however certain safety precautions must be...

Page 43: ...ply with all corresponding safety symbols and markings present on the unit and in this manual In special cases there may still be interference for the specified application area despite maintaining st...

Page 44: ...ty should be always between 0 and 95 If there are lots of inverters need to be stored the maximum layers for original carton is four After long term storage local installer or service department of ma...

Page 45: ...imit values e g when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers In this case the operator is obliged to take proper action to...

Page 46: ...c panel is exposed to light it generates a DC voltage When connected to this equipment a photovoltaic panel will charge the DC link capacitors Energy stored in this equipment s DC link capacitors pres...

Page 47: ...you need to hang on the inverter During the process please maintain the balance of the TL3 S Hang the inverter on the expansion bolt After confirming the inverter is stuck on expansion bolt fasten fo...

Page 48: ...re to the sunlight may cause additional internal heating which will cause power derating More than one inverter need to be installed the dimensions below should be considered Fig5 6 Fig5 7 Fig 5 8 Rec...

Page 49: ...ly disconnected under load Measure the public grid voltage and frequency Voltage 400Vac Frequency 50Hz 60Hz 3 Phase Open the breaker between the PV inverter and utility Specification of AC breaker Cab...

Page 50: ...he inverter To reduce the risk of electric shock avoid touching the live components and treat the terminals carefully Information Please use the same brand male and female PV connectors Under any cond...

Page 51: ...nverter 4 The maximum string currents are varying from different inverter types Model Max current 7000TL3 S 8000 9000TL3 S 10000 11000TL3 S 12000TL3 12000 15000TL3 S 11 5A 11 5A 11 5A 11 5A 13A 13A 11...

Page 52: ...nal system Notes The inverter starts up automatically when DC power from the PV panel is sufficient Fault Mode The internal intelligent controller can continuously monitor and adjust the system status...

Page 53: ...afety standard must be selected by the DIP switch The DIP switch is composed of four digit binary number PINS The different combination of the four PINS can represent different inverter s model which...

Page 54: ...4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 4 2 3 1 ON 5 AS4777_Newzealand GT1XXXXXX0 Reserved GT1XXXXXX1 India GT1XXXXXX2 EN50438_Demark GT1XXXXXX3 EN50438_Sweden GT1XXXXXX4 EN50438_Norway G...

Page 55: ...l 2000 Kwh AC Volt A B C 230V 230V 230V Set Language Set Language English Once Once Once Double Fig6 3 Overall display interface Power on display After inverter restarts the background light will last...

Page 56: ...Com Address 001 Set Language Set Date Time AC V Control Disable Enable Once Once Once Setting Three Set Language English Double AC V Control Disable Double Double Date 2012 04 05 Time 14 20 38 Settin...

Page 57: ...ime Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 14 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 20 38 Date 2013 05 06 Time 15 21 38 Set OK Double Once Double Once Double Once Dou...

Page 58: ...ication systems You can update firmware via RS232 or Rs485 The connecting diagram as follow Active power control with a ripple control signal receiver Through RS485 interface RS485 232 RS232 converter...

Page 59: ...RS485 cable connection Rs485 cable connection Pin1 TR B Pin2 Shielding layer or no connection Definitions of RS485 PLUG standard as follows Pin1 TR B Pin2 Shielding layer or no connection Pin3 TR A P...

Page 60: ...recommended as STP FTP ASTP 4 Plug in two terminals Cover the fix board Information Tighten 4 pcs screws first then tighten cable gland 5 Tighten 4pcs screws and cable gland Note 1 As to the connecti...

Page 61: ...off the DC switch of the inverter 3 Check the inverter operating status 4 Until the display of LCD goes out the inverter is shut down Once the output power is derating because of too high warming some...

Page 62: ...acing inverter Error message Description Suggestion Error 124 No AC connection Check AC wiring Check the status of AC breaker PV Isolation Low Insulation problem 1 Check if panel enclosure ground prop...

Page 63: ...oblem still exist Contact Growatt Warning 109 Warning 108 PV 1 or PV2 Circuit short PV 1 or PV2 boost broken Check the PV panel polarity Restart the inverter If the warning still exist please contact...

Page 64: ...he installation site at that time Ensure that the old unit and where applicable any accessories are disposed of in a proper manner 11 Specification 11 1 Specification of TL3 S Model 7000TL3 S 8000TL3...

Page 65: ...ency 99 5 99 5 Power factor at rated power 1 1 1 Adjustable displacement power factor THDi Full load THDv 1 0 8leading 0 8laging AC grid connection type 3 3 3 3W N PE 3W N PE 3W N PE Protection device...

Page 66: ...x output current 16 7A 18 3A 19A Rated AC output power 10kW 11kW 12kW Max AC apparent power 11kVA 12 1kVA 13 2kVA 33A 33A 44A 25A 25A 25A 184 300V 184 300V 184 275V Efficiency Max efficiency 98 3 98 3...

Page 67: ...Voltage 160V 160V 160V PV voltage range 160V 1000V 160V 1000V 160V 1000V MPP voltage range DC nominal voltage 200V 1000V 600V Max PV Isc 16A 16A 16A 16A 16A 16A Number of independent MPP trackers str...

Page 68: ...ated all pole sensitive leakage current monitoring unit yes yes yes General Data Dimensions W H D in mm Weight Operating temperature range 25 C 60 C 13 F 140 F With derating above 45 C 113 F Noise emi...

Page 69: ...ture range 40 to 90 Strip length 7 0mm 9 32 Cable jacket diameter 4 5 to 7 8mm 3 16 to 5 16 Rated current at 90 Additional ground screws 2Nm 181bf in 11 4 Spare Parts and Accessories In the following...

Page 70: ...0438 G83 G59 CE IEC62109 NB T32004 2013 G59 14 Contact If you have technical problems concerning our products contact your installer or manufacturer During inquiring please provide below information 1...

Reviews: