12. COMMMON PROGRAM PARAMETERS
SETTING
CODE
DESCRIPTION
ADVANCED
PARAMETER
Door Cycle
Counter
P.000
The content of this parameter indicates the number of previously counted
cycles.
Maintenance
Counter
P.005
The content of this parameter indicates the number of cycles remaining
until maintenance is due.
Auto Close Timer
P.010
The door is held at the open limit for the set time. The door is then
automatically closed.
NOTE:
A wire link is required at INPUT 10 (bridge
terminals 65 and 62) to enable auto close.
Boost for OPEN
P.140
The boost increases the output voltage and thus the power in the lower
speed range until the cut-off frequency (P.100) is reached. Range of
boost is from 0% to 30%.
Limit Setting
P.210
This parameter is used to start a new teaching of the end positions. The
corresponding end positions are moved to in deadman mode after
activating the procedure and saved by holding down the Stop key. Select
from the following settings:
0: Cancel, no end positions are taught.
1: Limit switch Lower, limit switch Upper and if appropriate limit switch
Intermediate Stop
are taught.
2: Limit switch Upper and if appropriate limit switch Intermediate Stop are
taught.
3: Limit switch Lower and limit switch Upper are taught.
4: Limit switch Intermediate Stop is taught.
5: All limit switches and the turn direction are taught.
Bottom Limit
Adjust
P.221
Correction of Closed Limit position. Range from -125 to +125
Top Limit Adjust
P.231
Correction of Open Limit position. Range from -60 to +60
Open Travel
Speed
P.310
Opening speed in Hz. (NOTE: Setting to more than 75Hz will reduce
power and the life of the operator and controller)
Close Travel
Speed
P.350
Closing speed in Hz. (NOTE: Setting to more than 75Hz will reduce
power and the life of the operator and controller)
Safety Bump Edge
P.460
Ensure this is set to 6 for use with a Safety Edge. If this is set to 0 the
Safety Edge will be deactivated
YES
Input Settings
P.501 – P.50F Input Parameter settings for Input 1 through to 15.
YES
Output Settings –
On board Relays
P.701 – P702 Output Parameter settings for the onboard mechanical relays at 10, 11,
12 and 20, 21, 22. See Advanced Parameters manual for further
configuration options
YES
Output Settings –
Soft and
Expansion
P.703 – P.70F Output Parameter settings for soft outputs 3 through to 15.
YES
Inch/Latch Mode
P.980
This parameter is used to set the operating mode for the controller.
0. OPEN and CLOSE move in self-holding (latch up and down)
1. OPEN move in self-holding, CLOSE move in manual mode (latch up,
inch down)
2. OPEN and CLOSE move in Manual mode (deadman – inch up and
down)
3. Deadman emergency operation
NOTE: All safety devices and limit switches are ignored.
See P.010
for Auto Close setting
Factory Reset
P.990
Set to 1 to perform a reset of the controller to factory settings
YES
Advanced
Parameters
P.999
Set to 3 for Advanced Parameter Selection mode
NOTE:
Some parameters require Advanced Parameter mode to be set.