40
10. PARAMETER OPTIONS (INC AUTO CLOSE SETUP)
10.1 SERVICE SWITCH FUNCTION
The purpose of the Service Switch is to Enable (ON) or Disassemble (OFF) the Parameter settings to be changed via
the facia buttons. See Service Switch Activation section for details on the location.
10.2 POWER CYCLE RESET
Press and hold the UP, STOP and DOWN fascia buttons (at the same time) for 3 seconds (or until the controller resets).
10.4 ENTERING PARAMETER MODE
Use the follow procedure to enter the Parameter Operation mode:
1. Isolate power. Open the enclosure and set MCB dip switch to ON to enable Service Mode (see
Service Switch Function section).
2. Close the cover of the enclosure and energise the controller.
3. Press and hold the UP and STOP buttons for 3 seconds to enter the Parameter Operation
Mode.
10.6 TIMING OUT
CAUTION
The Wall Controller will time-out from the Parameter Operation mode after 60 minutes of inactivity.
After 60 minutes of inactivity the Wall Controller will time-out, requiring the unit to be Reset. To Reset press the UP, STOP & DOWN
for 3 seconds, which will power cycle the unit.
10.3 FACTORY RESET
To perform a Reset back to factory settings, set P.999 to 3 and set P.990 to 1.
10.5 ENTERING ADVANCED EXTENDED PARAMETER MODE
1. Use the UP and DOWN buttons to navigate to P.999
2. Press STOP briefly to enter the P.999 parameter setting.
3. Use the UP or DOWN buttons to change the value to ‘3’.
4. Press and hold the STOP button for 3 seconds to save the setting.
5. Press STOP briefly to return to Extended Parameter Mode setting menu.
6. Use the UP or DOWN buttons to navigate to the required parameter.
7. Press STOP briefly to enter the parameter.
8. Use the UP or DOWN buttons to change the value to of the parameter.
9. Press and hold the STOP button for 3 seconds to save the new value.
10. Press STOP briefly to return to Extended Parameter Mode setting menu.
11. Press and hold the STOP button for 3 seconds to exit Extended Parameter Mode.