5. DDI-07 AND DDI-12 WALL CONTROLLER
Alternatively, the Safety Brake can be wired directly into the Encoder (on the operator side) as shown below:
Note: Wire Safety Brake Switch in series with existing switches.
5.7.8 INSTALLING AN EMERGENCY INPUT LINK WIRE IF NOT USING A SAFETY BRAKE
It is recommended that an External Brake is installed on all
Chain Drive installations.
CAUTION
Power terminals L1, L2, L3 are spring terminal type.
Care must be taken to ensure loose wire strands are not left
outside of the terminal.
5.7.9 FERRITE INSTALLATION
The controller is supplied with four ferrites that must be installed to reduce EMC interference.
CABLE
COLOUR
LOCATION
Mains input power
White
At controller
Motor power
Black
Outside of controller
Motor power
White
Inside controller over 3xPhase Lines (T1/T2/T3)
Encoder cable
White
At controller
5.7.10 COMPLETING SET-UP
Mains and operator wiring is now complete.
Proceed to the section for Entrapment Protection Devices or Commissioning to complete set-up.