File: LIQ User Manual V2.0
Page 22 of 37
3.2.1 Switching on the LIQ-60
The LIQ-
60’s power switch is located on the bottom panel. It is a rotating switch that turns through 90
degrees between the OFF and ON positions, as indicated by arrows.
•
Rotate the switch clockwise to the ON position. In the ON position it will be in line with the 2 (red)
fault indicating LEDs.
•
When the unit is powered on the red and amber
LED’s will start a flash sequence. The red LED
will flash 8 times followed by 8 flashes from the amber LED.
•
After the start up sequence, the red LEDs will illuminate once every second indicating that t h e unit
is in a non-sensing state, awaiting commissioning. Prior to commissioning the amber LED will
flash 3 times every 30 seconds. If after one hour the LIQ-60 has not been manually commissioned,
it will commission itself automatically.
Refer to Table 1 on page 17 for an explanation of LED status and fault indication sequences.
4 Configuration
Before the LIQ-Gateway and LIQ-60s are mounted and commissioned, they need to be configured.
Configuration of the LIQ-60 and the LIQ-Gateway is performed using LineMan and an LIQ-LocalLink.
4.1 LIQ-60 configuration
The LIQ-60 is configured using LineMan software.
Please refer to Appendix A for instruction on configuring the LIQ-60 with the LineMan software.
Commissioning
LIQ-60s must be commissioned after configuration.
5 Commissioning
5.1 Commissioning the LIQ-60
If the LIQ-60 is intended to operate
“stand alone”, without an associated LIQ-Gateway, it needs to be
commissioned directly using a laptop PC and an LIQ-LocalLink local-RF radio, with the LineMan software
interface. If the LIQ-60 is associated with an LIQ-Gateway, the LIQ-60 is then commissioned via the LIQ-
Gateway.
5.1.1 Pre-commissioning check of the LIQ-60s
Using a laptop running LineMan, connect to each LIQ-60.
Confirm that:
•
The internal battery voltage exceeds 2V.
•
There is some solar charge current when the solar panel is illuminated.
•
Event recording is enabled if required.
•
Load logging is enabled if required.
•
Line currents are as expected.
•
Voltage sensor values are as expected.
Summary of Contents for Line IQ LIQ60
Page 1: ...000 2166 Rev 3 0 Franklin Grid Solutions LLC December 20 2017 User Manual ...
Page 2: ......
Page 9: ...000 2166 Rev 3 0 Franklin Grid Solutions LLC Page 7 of 37 ...
Page 22: ...File LIQ User Manual V2 0 Page 20 of 37 Figure 4 The LIQ LocalLink modem ...
Page 39: ...000 2166 Rev 3 0 Franklin Grid Solutions LLC Page 37 of 37 ...