background image

NDD Series - NO2 Transmitter                                                              

Installation Manual 

 

 
Feb 2, 2016

                            

                          NDD-INS-002 

 

  Page 1 

 
Introduction 

The NO2 Transmitter uses an electrochemical sensor to monitor the NO2 
level and outputs a 4-20 mA signal. It features a 3-wire analog output and 
an alarm relay . 
 

 
Before Installation 

Read these instructions carefully before installing and commissioning the 
NO2 transmitter. Failure to follow these instructions may result in product 
damage. Do not use in an explosive or hazardous environment, with 
combustible or flammable gases, as a safety or emergency stop device or 
in any other application where failure of the product could result in 
personal injury. Take electrostatic discharge precautions during 
installation and do not exceed the device ratings. 

 
 

Operation

 

In normal operation the sensor will measure the NO2 level in the surrounding air and output a proportional value on the 4-20 
mA output. The NO2 measurement range is 0 to 10 ppm. The relay can be used to indicate an alarm condition. The trip point 
for the relay can be programmed to three different settings with an on-board jumper. If the NO2 level exceeds the trip point 
then the relay is activated. The relay will remain activated until the NO2 level drops below the (trip level – hysteresis) where 
hysteresis is 3%

.

 

 
Start-up 

Verify that the NO2 Transmitter is properly wired according to the wiring diagrams and all connections are tight. Apply 
power to the device and the sensor will begin reading the NO2 level and output the analog signal. 

 
Mounting 

The NO2 enclosure should be mounted on a flat surface three to five feet from the floor of the area to be controlled. Do not 
mount the sensor near doors, opening windows, supply air diffusers or other known air disturbances. Avoid areas with 
vibrations or rapid temperature changes. 
 
 

Summary of Contents for NDD Series

Page 1: ... measure the NO2 level in the surrounding air and output a proportional value on the 4 20 mA output The NO2 measurement range is 0 to 10 ppm The relay can be used to indicate an alarm condition The trip point for the relay can be programmed to three different settings with an on board jumper If the NO2 level exceeds the trip point then the relay is activated The relay will remain activated until t...

Page 2: ...and does not require a loop power supply This means the signal current is generated by the transmitter and must not be connected to a powered input or device damage will result This is the typical operating mode of a three wire device Check the controller Analog Input to determine the proper connection before applying power Ensure the controller Analog Input AI matches the transmitter output signa...

Page 3: ...d directly to the port on the cover and monitor the output signal The device cover must be removed to perform an actual calibration In this case the gas calibration cap attaches to the sensor fixture inside the enclosure The sensor must be continuously powered for at least 1 2 hour prior to calibration Calibrate the sensor either in clean air or by applying Zero gas with a flow rate of 0 5 to 1 li...

Page 4: ... Pressure Atmospheric 10 Typical Area Coverage 700 m2 7500 ft2 or 15 m 50 ft radius Calibration Adjustments Zero and Span pots Wiring Connections Screw terminal block 14 to 22 AWG Enclosure 2 8 w x 4 1 h x 1 9 d 71 x 104 x 48 mm Power Supply 24 Vdc 20 or 24 Vac 10 non isolated half wave rectified Consumption 50 mA max Output Signal 4 20 mA sourcing Output Drive Capability 550 ohms max 24 Vac dc Re...

Reviews: