Relative Humidity

Sensor Accuracy: ..................±2, 3, or 5% RH (5 to 95% RH)
Measurement Range: ........0 to 100% RH
Resolution:...............................0.01% RH
Hysteresis: ................................±0.8% RH @ 25°C (77°F)
Response Time: .....................8 seconds
Stability: ....................................<0.25% RH/year

Optional Temperature Sensor

Feed Through Sensor: ........Various RTD’s and thermistors available as
 

2 wire resistance output

General

Power Supply: ........................24 Vac/dc ~ ±10% typical
Consumption: ........................22 mA maximum @24Vdc, 70mA @24Vac
Operating Range: .................-40 to 60°C (-4 to 140°F)
Output Signal:........................4-20 mA current loop, 0-5 Vdc, 0-10 Vdc, or 0-1 Vdc
 

(field selectable)

Output Drive @ 24 Vdc: .....

Current:

 550 Ω max

 

Voltage:

 10K Ω min

Probe Material: ......................304 Series stainless steel with porous filter
Probe Diameter:....................12.7 mm (0.5")
Sun and Windshield: ...........White polycarbonate, vented
Enclosures:...............................

A:

 Polycarbonate - UL94-V0, IP65 (NEMA4X)

 

E: 

Same as A, with cable gland fitting

Termination: ...........................Screw terminal block (14, to 22 AWG)
Country of Origin: ................Canada

  

Figure 9

Figure 7

Figure 6

Figure 8

TS1

TS2

Optional Temperature Sensor

Wiring for voltage output signal

and 24 Vdc power from controller

Wiring for all output signals and 

external 24 Vdc power transformer

Wiring for 4-20 mA loop-powered

output and external 24 Vdc power from 

controller

Wiring for 4-20 mA loop-powered output 

and external 24 Vdc external power supply

PWR

OUT

COM

PWR

OUT

COM

PWR

OUT

COM

PWR

OUT

COM

+24 Vdc
0-5 or 10 Vdc AI
COMMON

24 Vdc
COMMON

COMMON
Analog Input

+24 Vdc
4-20 mA AI

+24 Vdc
COMMON

COMMON
4-20 mA AI

Controller

Controller

Temp. Sensor 

Input

Controller

Controller

24 Vac Transformer

Controller

24 Vdc Power Supply

ON

OUT  COM  PWR

TS1   TS2

mA

mA

VOLT

VOLT

10V  1V  5V

10V  1V  5V

WIRING

• 

Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment damage.

• 

Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive 
loads such as motors. Make all connections in accordance with national and local codes.

• 

Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the wire diagram for the applicable power 
supply and output signal type as shown in Figure 8.

• 

Select desired signal output type (mA or Vdc) by setting switch on PCB to desired output configuration (mA or V) as shown in Figure 6.

• 

If mA was selected, no further Output set up is required. If VOLT output is selected in Figure 6, Set DIP switch for desired voltage output as 
shown in Figure 7. Setting one DIP switch to ON position will select the output (10V, 5V or 1V). NOTE: Only one of the Voltage select switches 
should be in the ON position.

• 

Connect the DC positive or the AC voltage hot side to the PWR terminal. For voltage output or AC power, the supply Common is connected 
to the COM terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave power supply so 
the supply Common is the same as the signal Common. See Figure 8.

• 

The analog output is available on the OUT terminal. Check the controller Analog Input to determine the proper connection before applying 
power as shown in Figure 8.

• 

If installed, the resistance temperature output is available on the two terminals labeled TS1 and TS2 as shown in Figure 9.

• 

The RH and Temperature sensor PCB can be field replaced by removing filter at end of Duct Probe. Please refer to the product submittal sheet 
for replacement sensor selection.

 

PRINTED IN C

ANAD

A       

DIMENSIONS

 

92 mm

3.62"

38mm

1.5"

52.0 mm

2.05"

76.2 mm

3.00"

0.5" NPT

132 mm

5.19"

82.5 mm

3.25"

69.8 mm

2.75"