INTRODUCTION

The high accuracy single point strap-on temperature transmitter has a precision 

platinum RTD bonded to a 38.1 mm x 38.1 mm (1.5” x 1.5”) aluminum plate and 

adhered to a 25.4 mm (1“) compressible foam. A 25.4 cm (10”) S/S Pipe clamp 

is provided to secure the assembly to various sizes of pipes. All probes are 

constructed to provide excellent heat transfer, fast response and are potted to 

resist moisture penetration. A transmitter that provides a high accuracy signal 

with excellent long term stability, low hysteresis and fast response is available 

with various ranges. A compact ABS enclosure with a hinged and gasketed cover 

is provided for ease of installation. 

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the 

temperature transmitter. Failure to follow these instructions may result in 

product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in 

any other application where failure of the product could result in personal 

injury. 

Do not exceed the device ratings

.

MOUNTING

The strap-on sensor installs directly onto any pipe where an immersion sensor with thermowell cannot be installed. 

Once a suitable spot is selected, remove a small block of insulation, if present. It is recommended that thermal compound be used to improve 

heat transfer. Spread a liberal amount on the pipe. Open the worm gear clamp by swiveling the worm gear away from the clamp and pull the 

clamp apart, as shown in Figure 1. 

Place the sensor plate on the selected mounting area and wrap clamp around the pipe. Re-insert 

clamp under the worm gear and pull until snug. Lock in place by swiveling the worm gear towards 

the clamp. Tighten worm gear clamp by using a standard screw driver or hex nut driver as shown 

in Figure 2. 

The enclosure has a hinged cover with latch. Open cover by pulling slightly on the latch on the right 

side of the enclosure. At the same time pulling on the cover, as illustrated in Figure 3. 

A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw the EMT 

connector or cable gland connector in until tight. See Figure 4. It is recommended that weatherproof 

conduit or cable gland fittings be used. The E style enclosure includes a 1/2" NPT to M16 thread 

adapter and cable gland fitting. 

Make wiring connections as per the “Wiring” illustrations on Page 2.

Swing door closed until securely latched. For added security, 2 screws are provided that may be 

installed in the integrated screw tabs. See Figure 5.

EMT Connector

Thermal Compound

Thread adapter and 

cable gland fitting

Figure 3

Figure 4

Figure 5

Figure 2

Figure 1

IN-GE-HATXSOXXX-02

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

High Accuracy Strap-on 

Temperature Transmitter

HATXSO Series - Installation Instructions