Greystone Energy Systems CS-425-HC Series Installation Instructions Download Page 1

Page  1

INTRODUCTION

The High Current Switch / Dryer Fan Control is a solid-state current switches with N.O. triac 

outputs to control high current line-voltage AC loads. All models have a factory set trip level of 

approximately 1 Amp and require no field adjustment for easy installation. Internal circuits are 

powered by induction from the line being monitored

The High Current Switch / Dryer Fan Control series can operate a dryer booster fan directly. These 

devices sense when a clothes dryer is drawing 1 Amp of current and then closes the output 

switch to activate the dryer vent booster fan. When the dryer cycle is complete and the current 

drops below the threshold, the output switch will open or remain closed for a pre-set delay time 

to allow heat to be removed from the vent before the switch is opened again. The device output 

can switch 120 Vac loads up to 2.5 Amps.  All models are UL certified. 

*WARNING*

• 

Electric Shock Hazard, Use Caution

• 

Disconnect and lock out power before installation

• 

Follow national and local electrical codes

• 

Read and understand these instructions before installing

• 

Installation only by qualified electrical personnel

• 

Do not rely on this device to indicate line power

• 

Only install this device on insulated conductors

• 

Only install on 600 Vac maximum conductors

• 

Do not use this device for life-safety applications

• 

Do not install in hazardous or classified locations

• 

Install this product in a suitable electrical enclosure

• 

Failure to follow these instructions may result in serious injury or death.

INSTALLATION

Read all warnings before beginning. Ensure the selected device has the correct ratings 

for application. 

Select a convenient location, with-in or adjacent to the breaker panel. Alternatively 

the sensor can be installed inside the dryer electrical compartment. Refer to Figure 4 

through 7 for typical installations. 

Mount the sensor with two screws through the base. The base has integrated 

mounting tabs to allow screw mount to a surface. If predrilling is required, the actual 

device may be used to mark holes. The mounting holes in the base will accommodate 

up to a #10 size screw (Not supplied). See Figure 1.

For 3-Phase systems, Disconnect and loop the neutral power wire, white, through the 

current sensor and reconnect. Connect the fan power supply, as shown 120 Vac max, 

to the top terminals of the current sensor. See Figure 2

For 220 Vac 3-wire single-phase systems, Determine which of the Hot wires is active 

for the dryer only. (this is necessary for stacked washer/dryer units). Verify that there 

is sufficient current to trip the current switch (minimum of 1 amp). If required the wire 

can be looped through twice to increase the current read by the switch. Connect the 

fan power supply, as shown 120 Vac max, to the top terminals of the current sensor. 

See Figure 3.

Figure 3

Figure 4

Figure 1

Figure 2

     

     

 

 

Exhaust Fan

Power Supply

120 Vac Max

Exhaust Fan

Power Supply

120 Vac Max

Power to 

Dryer

Three Phase Wiring

220 Vac Three Wire 

Single-Phase Wiring

Power to Dryer 

HOT

Neutral

Neutral/

White

Dryer 

Junction

Installation as a dryer junction box (3 phase)

Power to

Dryer

Neutral / White

Dryer junction box

Current sensor

120 Vac

Fan

IN-GE-CS425HCXXX-01

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Current Switch

CS-425-HC Series - Installation Instructions

Reviews: