
Page 1
INTRODUCTION
The High Current Switch / Dryer Fan Control is a solid-state current switches with N.O. triac
outputs to control high current line-voltage AC loads. All models have a factory set trip level of
approximately 1 Amp and require no field adjustment for easy installation. Internal circuits are
powered by induction from the line being monitored
The High Current Switch / Dryer Fan Control series can operate a dryer booster fan directly. These
devices sense when a clothes dryer is drawing 1 Amp of current and then closes the output
switch to activate the dryer vent booster fan. When the dryer cycle is complete and the current
drops below the threshold, the output switch will open or remain closed for a pre-set delay time
to allow heat to be removed from the vent before the switch is opened again. The device output
can switch 120 Vac loads up to 2.5 Amps. All models are UL certified.
*WARNING*
•
Electric Shock Hazard, Use Caution
•
Disconnect and lock out power before installation
•
Follow national and local electrical codes
•
Read and understand these instructions before installing
•
Installation only by qualified electrical personnel
•
Do not rely on this device to indicate line power
•
Only install this device on insulated conductors
•
Only install on 600 Vac maximum conductors
•
Do not use this device for life-safety applications
•
Do not install in hazardous or classified locations
•
Install this product in a suitable electrical enclosure
•
Failure to follow these instructions may result in serious injury or death.
INSTALLATION
Read all warnings before beginning. Ensure the selected device has the correct ratings
for application.
Select a convenient location, with-in or adjacent to the breaker panel. Alternatively
the sensor can be installed inside the dryer electrical compartment. Refer to Figure 4
through 7 for typical installations.
Mount the sensor with two screws through the base. The base has integrated
mounting tabs to allow screw mount to a surface. If predrilling is required, the actual
device may be used to mark holes. The mounting holes in the base will accommodate
up to a #10 size screw (Not supplied). See Figure 1.
For 3-Phase systems, Disconnect and loop the neutral power wire, white, through the
current sensor and reconnect. Connect the fan power supply, as shown 120 Vac max,
to the top terminals of the current sensor. See Figure 2
For 220 Vac 3-wire single-phase systems, Determine which of the Hot wires is active
for the dryer only. (this is necessary for stacked washer/dryer units). Verify that there
is sufficient current to trip the current switch (minimum of 1 amp). If required the wire
can be looped through twice to increase the current read by the switch. Connect the
fan power supply, as shown 120 Vac max, to the top terminals of the current sensor.
See Figure 3.
Figure 3
Figure 4
Figure 1
Figure 2
Exhaust Fan
Power Supply
120 Vac Max
Exhaust Fan
Power Supply
120 Vac Max
Power to
Dryer
Three Phase Wiring
220 Vac Three Wire
Single-Phase Wiring
Power to Dryer
HOT
Neutral
Neutral/
White
Dryer
Junction
Installation as a dryer junction box (3 phase)
Power to
Dryer
Neutral / White
Dryer junction box
Current sensor
120 Vac
Fan
IN-GE-CS425HCXXX-01
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
Current Switch
CS-425-HC Series - Installation Instructions