background image

T20.0.4X.6C-03 

 Operating Manual GTMU - MP 

page 5 of 6 

 

 

_____________________________________________________ 

_____________________________________________________________________________ 

 

10 Configuration of the device 

Follow these instructions to configure the functions of the device:  

  Press 

SET

 until the first parameter  

UNIT

 appears in the display 

  If a parameter should be changed, press 

▼ 

or

 

,  

The device changed to the setting 

– edit with 

▼ 

or

 

 

  Confirm the value with 

SET

 

  Jump to the next parameter with 

SET.

 

 

 

Parameter 

value 

information

 

SET 

▼ and ▲

 

 

UNIT 

Unit of  temperature displays

   

factory setting: °C

 

°C 

Temperatures in °Celsius 

°F 

Temperatures in °Fahrenheit 

VT

 

Display at zero output of humidity display value (output scaling) 

-

xxx.0 … +xxx.0

 

Entry of display value at which the temperature output should deliver 
4 mA (or 0V)  

(factory setting: 0.0)

 

VT

 

Display at maximum output for humidity display value (output scaling) 

-

xxx.0 … +xxx.0

 

Entry of display value at which the temperature output should deliver 
20 mA (or 1 V / 10 V)  

(factory setting: 100.0)

  

 

Offset correction of humidity measuring *) 
oFF 

deactivated (

factory setting)

 

-5.

0 … +5.0 

Selectable from -5.0 to +5.0 % rel. humidity 

Scale correction of humidity measuring *) 
oFF 

deactivated (

factory setting)

 

-15.

00 … +15.00 

Selectable from -15.00 to +15.00 % scale correction 

 Pressing 

SET

 again stores the settings, the instruments restarts (segment test) 

Please note:   

If there is no key pressed within the menu mode within 2 minutes, the 
configuration will be cancelled, the entered settings are lost! 

*)

  if higher values are needed, please check sensor, if necessary return to manufacturer for inspection. 

Calculation: corrected value = (measured value 

– Offset) * (1+Scale/100) 

 

 

ATTENTION! 

 

If the jumper is removed from 
the shown contacts, the 
configuration is inaccessible, 
values are protected. 

Never connect other contacts!

 