P1/PD
Installation Instructions
Please read all instructions before commencing
installation.
1.
Observe appropriate safety precautions if working off
steps or ladders.
2.
Wear eye protection when breaking out wall or
ceiling materials etc.
3.
Siting notes:
To avoid short circuiting of air flow, fans should be
sited at a high level and as far away as possible
from
the main source of replacement air. The fan
should
not be sited where it would be subject to a
direct
source of heat in excess of 40
o
C. If installed
in a
room containing a fuel burning appliance of a
non-
balance flue design, it is the responsibility of
the
installer to ensure that sufficient replacement
air is
provided to prevent products of combustion
from
being drawn down the flue when the fan is
operating
and that the air intake is located at least
500mm
away from the flue. Exhaust air from the fan
must not
be allowed to discharge into a flue used for
extracting
fumes from an appliance other than those
powered
by electricity. Regulations regarding the
discharge of
exhaust air must be observed.
4.
When installing wall mounted fans, cable run, or
switches, ensure that there are no buried cables
or pipes in the way. Greenwood Air
vac
recommends
that this fan is mounted 1.8m above
floor level.
5.
This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision
or instruction concerning use of the appliance in
a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning
and user maintenance shall not be made by children
without supervision.
Note:
I
f no TIMER is fitted or likely to be fitted to P1 or PD fans,
omit connection to terminal No.1.
Cable Size:
4 core 1.00mm
2
max
230V 50Hz
Motor Ratings:
P1 25 Watts
PD 28 Watts
Electrical Details
2
3
1
External wiring for P1 and PD1 Fans
– one room ventilation.
Fan
terminal
Fuse
1 room
Double pole
isolating switch
N
L
Light switch
2
3
1
External wiring for P1 and PD1 Fans
– two room ventilation room light operation.
Fan
terminal
Room 1
Room 2
Double pole
light switch
Fuse
Double pole
isolating switch
N
L
External wiring for two room ventilation light operation
Service Instructions
This unit must periodically cleaned to free any dust and fluff
and must be carried out by a competent person.
The inside of the unit is to be cleaned to avoid build up of
talcum powder etc. Handle fan wheel carefully, do not
distort blades.
The motor is lubricated for a serviceable life.
05.10.134 Issue
6
Sept
ember 201
8
2
3
1
External wiring for P1 and PD1 Fans
– one room ventilation.
Fan
terminal
Fuse
1 room
Double pole
isolating switch
N
L
Light switch
2
3
1
External wiring for P1 and PD1 Fans
– two room ventilation room light operation.
Fan
terminal
Room 1
Room 2
Double pole
light switch
Fuse
Double pole
isolating switch
N
L
External wiring for one room ventilation
Electrical connector in
assembled position
Earth test wire
(Remove)
Rear face of
Connector