background image

8

Model PV

e

 Heat Recovery Unit

Dimensional Data

Drain Trap

Unit 

Size

A

B

C

D

E

PVe-20

104.1 

(2650)

59.7 

(1520)

41.5 

(1060)

20.3 

(520)

20.7 

(530)

PVe-35

104.1 

(2650)

59.7 

(1520)

49.2 

(1250)

25.2 

(640)

17.7 

(450)

PVe-45

110.6 

(2810)

59.7 

(1520)

61.1 

(1560)

25.2 

(640)

19.0 

(490)

PVe-55

116.5 

(2959)

59.7 

(1520)

76.1 

(1940)

25.2 

(640)

23.8 

(610

)

All dimensions are shown in inches 

(millimeters)

Door handles, hinges and other protrusions are not 

included in the dimensions above. Dimensions are 

rounded up to the nearest .1 inch 

(2.54 millimeters)

.

Bypass 

Damper

Face 

Damper

Outdoor Air Hood

Filters

Filters

Filters

Exhaust 

Air Hood

Control Center

Face/Bypass Damper

Plate Heat

 Exchanger

Plate Heat 

Exchanger

Outdoor 

Air Hood

C

B

A

D

E

CLEARANCE

CLEARANCE

B

C

A

D

D

Top view

Bypass 

Damper

Face 

Damper

Outdoor Air Hood

Filters

Filters

Filters

Exhaust 

Air Hood

Control Center

Face/Bypass Damper

Plate Heat

 Exchanger

Plate Heat 

Exchanger

Outdoor 

Air Hood

C

B

A

D

E

CLEARANCE

CLEARANCE

B

C

A

D

D

Side view

The PVe plate heat exchanger is provided with two 
stainless steel drain pans and each is equipped with 
a one inch MPT drain fitting. A drain trap must be 
installed on each drain fitting to allow excess water 
to flow out of the drain pans. More importantly, 
though, due to the negative internal static pressure 
inside the PVe cabinet, installing drain traps prevents 
outdoor air from being pulled into the cabinet and 
consequently causing overfilling of the drain pans or 
misting of PVe components.
To ensure the drain trap works properly, the trap 
height must account for the difference in static 
pressure between ambient conditions outside the 
unit and the negative static pressure inside the PVe 
cabinet. An assumption of 3.0 in. wg differential is 
normally sufficient for all PVe units and this would 
require a trap design as shown. If the internal static is 
believed to be higher, consult the factory.

Refer to local codes to determine drainage 
requirements. If draining onto a roof, place a drip pad 
beneath the drain outlet to protect the roof. If draining 
onto a roof is not acceptable, a drain line must be 
attached to the drain trap. The drain line must be 
pitched away from the unit at least 1/8-inch per foot. 
On longer runs, an air break should be incorporated 
to ensure proper drainage. Local codes may require 
drainage into a waste water system.
Drainage problems result not only from improper 
drain trap design, but also from lack of maintenance 
in the PVe cabinet. Algae can form in the drain pans 
and traps and cause reduced water flow, which can 
in turn result in a backup in the drain system. Regular 
maintenance and inspection will prevent this from 
occurring. If the drains have a cleanout opening, be 
sure and close the opening after cleaning and refill 
the trap with water.

4 in.

2 in.

Summary of Contents for PVE-20

Page 1: ...as the National Electrical Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 All moving parts must be free to rotate without striking...

Page 2: ...rect quantity of each item have been received If any items are missing report shortages to your local representative to arrange for obtaining missing parts Sometimes it is not possible that all items...

Page 3: ...t exchanger transfers energy from the exhaust air to the incoming outdoor air When used in the cooling mode heat energy is transferred from incoming outdoor air to the exhaust air Simply put this unit...

Page 4: ...check should be made to ensure that the unit has been installed level by using the bottom of the cabinet as a reference not the top the cabinet roof is sloped to the rear Ensure that all ductwork has...

Page 5: ...920 36 920 60 1530 PVe 45 60 1530 36 920 36 920 60 1530 PVe 55 72 1830 36 920 36 920 60 1530 All dimensions are shown in inches millimeters The weatherhoods include 2 inch aluminum mesh filters that a...

Page 6: ...5 PVe 35 99 4 44 6 216 PVe 45 105 9 56 3 261 PVe 55 111 7 71 3 316 All dimensions are shown in inches Curb Cap Details for Factory Supplied Roof Curbs Ductwork Connections Examples of poor and good fa...

Page 7: ...clearance for installation of water drain traps Rails should be designed to handle the weight of the PVe unit taking into consideration weight per square inch on bearing surfaces Rails should be posi...

Page 8: ...outdoor air from being pulled into the cabinet and consequently causing overfilling of the drain pans or misting of PVe components To ensure the drain trap works properly the trap height must account...

Page 9: ...Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate Voltage Imbalance In a 3 phase system excessive voltage im...

Page 10: ...er warms the outdoor air prior to being drawn through the PVe plate heat exchanger Electric heaters are available in 208 230 or 460 VAC Refer to heater nameplate for voltage rating Preheaters If an op...

Page 11: ...frost control is only initiated during a real frost condition Field wiring of a light or other alarm between 6 C in the control center will notify personnel when unit is in frost control mode refer to...

Page 12: ...ting or multispeed control of the blowers One VFD is provided for each blower supply air and exhaust The VFD s provided are either Yaskawa model V1000 or J1000 Refer to the tables in this section for...

Page 13: ...otor FLA Motor FLA H1 04 Multfunction Input Sel 4 Terminal S4 3 3 H1 05 Multifunction Input Sel 5 Terminal S5 4 4 H1 06 Multifunction Input Sel 6 Terminal S6 5 NA H3 10 A2 Not Used F NA A1 01 Access L...

Page 14: ...led wiring diagram located within the control panel This diagram illustrates typical factory wiring and also illustrates circuits that must be field wired Included with this drawing are 1 variable fre...

Page 15: ...wer goes off Open the filter compartment and remove the obstructing material Replace the door and check to make sure that you do not have power at the alert signal leads The unit is now ready for oper...

Page 16: ...remote panel is a series of junction boxes ganged together and includes a stainless steel faceplate The remote panel is available with a number of different alarm lights and switches to control the u...

Page 17: ...abels Terminal Strip Labels EF A Exhaust Fan Amps OAF A Supply Fan Amps Sensors Mounted by Factory Factory mounted temperature pressure and current sensors are available in the locations indicated on...

Page 18: ...ber ________________________________ Pre Start Up Checklist check as items are completed o Disconnect and lock out all power switches o Remove any foreign objects that are located in the energy recove...

Page 19: ...o OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Vapor Tight Lights Yes No N A Yes No Remote Control Pa...

Page 20: ...cessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Belt Drive Installation 1 Remove the protective coating from t...

Page 21: ...rrective actions If observation cannot locate the source of vibration a qualified technician using vibration analysis equipment should be consulted If the problem is wheel unbalance in place balancing...

Page 22: ...are various optional motorized dampers and sensors that may also be found in the unit The heart of the PVe unit is the Plate Heat Exchanger and this is the component that actually accomplishes heat e...

Page 23: ...assists proper motor cooling Never wash down motor with high pressure spray Greasing of motors is only intended when fittings are provided Many fractional motors are permanently lubricated for life a...

Page 24: ...requency of cleaning depends upon the cleanliness of the incoming air These filters should be cleaned prior to start up Clean filters by rinsing with a mild detergent in warm water Internal Filter Mai...

Page 25: ...ture is decreased by the transfer of energy from the cooler drier exhaust air via the aluminum heat exchanger The preconditioned air is typically mixed with return air going back to the air handler fo...

Page 26: ...low prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with...

Page 27: ...ed Static pressures are higher or lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor vo...

Page 28: ...haft Bearings Replace defective bearing s Lubricate bearings Tighten collars and fasteners Wheel out of balance Replace or rebalance Loose wheel on shaft Tighten wheel setscrew Loose motor or blower s...

Page 29: ..._______________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _____________________...

Page 30: ..._______________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _____________________...

Page 31: ..._______________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _____________________...

Page 32: ...nsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355...

Reviews: