MiniCore

Symptom

Possible Cause

Corrective Action

Unit is NOT 
operating

Electrical

Check fuses/circuit breakers, replace if needed. Check for On/
Off switches. Check for correct supply voltage.

Motor

Check motor horsepower is correct and not tripping overloads.

Excessive noise

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or bearing 
collars on shaft.

Bearings

Replace defective bearing(s). Lubricate bearings. Tighten collars 
and fasteners.

Wheel out of balance

Clean, replace or rebalance.

Low airflow (cfm)

Fan speed too low

Increase fan speed.

Dirty filters or energy core

Replace filters and/or follow the cleaning procedures.

High static pressure

Incorrect fan-to-duct connections. Make sure dampers open 
appropriately. Increase fan speed

High airflow (cfm)

Fan speed too high

Decrease fan speed.

Low static pressure

Make sure grilles, filters and access doors are installed. 
Decrease fan speed.

Always provide the unit model and serial number when requesting parts or service information. Always check 
motor amps and compare to nameplate rating.

Troubleshooting

®

Summary of Contents for MiniCore 10

Page 1: ...ing or rubbing any stationary objects 3 Unit must be securely and adequately grounded 4 Do not spin fan wheel faster than maximum cataloged fan RPM Adjustments to fan speed signi cantly affects motor...

Page 2: ...g delivery Alert the carrier of any damage detected The customer will make a notation of damage or shortage of items on the delivery receipt and all copies of the bill of lading which is countersigned...

Page 3: ...ng Schematics 7 System Start Up Unit Documentation Record 8 Pre Start Up Checklist 8 Start Up Checklist 8 General 9 Check Voltage 9 Blower Wheel Rotation 9 Air Volume Check Measurement 9 Voltage Amper...

Page 4: ...e sheet metal block off Install where the damper had been located Step 6 Using a 1 2 inch wrench remove the four 4 bolts from the discharge end of the unit that holds the blowers Step 7 Remove the fou...

Page 5: ...C 5 44 8 14 39 4 10 44 8 19 2 39 4 All dimensions are in inches A B C Isolator Flat Washer Lock Washer Nut 1 2 inch threaded rod provided by others Flat Washer Lock Washer Nut Hanger bracket factory...

Page 6: ...turn the supply blower off Time exhaust using default timer setting will shut down the supply fan for 5 minutes every 30 minutes to allow exhaust to defrost energy core Use the Frost Control Test Pro...

Page 7: ...MB Blower Motor B T1 Frost Control Timer Typical Settings t1 OFF 5 min t2 ON 30 min TH Thermostat non adjustable 5 setting Required to be mounted in outdoor air duct TR Transformer Solid State Speed M...

Page 8: ...but will also provide valuable information to personnel performing future maintenance Should an issue arise which requires factory assistance this completed document will allow unit experts to provide...

Page 9: ...afety precaution could result in serious injury or death Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating an...

Page 10: ...eaners on the core This will result in a damaged core Optional EC Motor Features Soft start All motors feature soft start technology which eliminates inrush current at start up The motors will reliabl...

Page 11: ...Tighten collars and fasteners Wheel out of balance Clean replace or rebalance Low air ow cfm Fan speed too low Increase fan speed Dirty lters or energy core Replace lters and or follow the cleaning p...

Page 12: ...____Time _____________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _____________________...

Reviews: