Model IGX Make-Up Air
43
®
Troubleshooting
Evaporative Cooling
Problem: Evaporative Cooling Module Does Not Operate - Recirculating Pump Control
Is fan operating correctly?
Yes
È
No
Æ
Refer to Troubleshooting, Supply Fan.
24 VAC between terminals Y1 and C
Yes
È
No
Æ
Cool switch (S4) off.
Turn cool switch (S4) on.
Cool switch not wired
. Wire cool switch (S4).
If a cool switch is not required and a cooing inlet air sensor is
provided, place jumper from R to Y1 to allow the cooling to enable
based on the cooling inlet air sensor.
24 VAC between terminal A2 and A1 on
cooling relay (RC)?
Yes
È
No
Æ
Optional inlet air sensor (TS4) holding.
Adjust TS4 setting.
Reference Blower, Start-Up.
Fan Interlock (ST1 or RF) open.
Refer to Troubleshooting, Supply
Fan.
Line voltage at primary side of TR3?
Yes
È
No
Æ
Transformer fuses (FU7) blown.
Check and replace blown fuse(s).
115 VAC between terminals 102 and
101?
Yes
È
No
Æ
Transformer secondary fuses (FU8) blown.
Check and replace
blown fuse(s).
Transformer TR3 wired incorrectly.
Refer to wiring diagram on
transformer and correct wiring.
Transformer TR3 faulty
. Replace transformer.
115 VAC between
terminals 116 and 101?
Yes
È
No
Æ
Cooling relay (RC) failure.
Check for loose connections or bent relay
pins, repair or replace relay.
Evaporative cooling pump(s) (P1)
running?
Yes
È
No
Æ
Evaporative cooling pump(s) (P1) wired incorrectly or not wired.
Correct any wiring issues.
Evaporative cooling pump(s) (P1) faulty.
Replace evaporative
cooling pump(s).
Everything is working properly, consult factory.