Model IGX Make-Up Air
41
®
Troubleshooting
Supply Fan
Problem: Motor overamps.
Motor voltage correct?
Yes
È
No
Æ
Provide proper power supply
. Reference Supply Fan, Start-Up.
Fan rotation correct?
Yes
È
No
Æ
Reverse fan rotation
. Reference Supply Fan, Start-Up.
Air volume too high?
No
È
Yes
Æ
Adjust drives or increase external static pressure as needed
.
Reference Supply Fan, Start-Up.
Actual static pressure lower than
design?
No
È
Yes
Æ
Adjust drives to reduce fan RPM
. Reference Supply Fan, Start-Up.
All three phases supplied to motor?
Yes
È
No
Æ
Supply motor fuse (FU1) blown
. Test and replace blown fuse(s).
Motor horsepower too low?
No
È
Yes
Æ
Resize motor.
Shorted windings in motor?
Yes
Æ
Replace motor.
Everything is working properly, consult factory.
Problem:
Insufficient airflow.
Damper(s) not fully opened?
No
È
Yes
Æ
Adjust damper linkage(s), or replace faulty actuator(s).
Damper
actuators may take a few minutes to open.
Fan rotation correct?
Yes
È
No
Æ
Reverse fan rotation.
Reference Supply Fan, Start-Up.
Filters dirty or clogged?
No
È
Yes
Æ
Clean or replace filters.
Reference Maintenance, General, Filters.
Belt slipping or broken?
No
È
Yes
Æ
Replace or tighten belt
. Reference Maintenance, General, V-Belt
Drives.
Fan speed too low?
No
È
Yes
Æ
Adjust drives as needed
. Reference Supply Fan, Start-Up section.
System static losses too high?
No
È
Yes
Æ
Reduce losses by improving ductwork
.
Leaks in ductwork?
Yes
Æ
Repair leaks.
Everything is working properly, consult factory.
Problem: Excessive noise or vibration.
Belts worn or loose?
No
È
Yes
Æ
Replace worn belts or tighten loose belts.
Reference
Maintenance, General, V-Belt.
Sheaves aligned?
Yes
È
No
Æ
Align sheaves.
Reference Maintenance, General, V-Belt Drives.
Wheel(s) unbalanced?
No
È
Yes
Æ
Clean and/or balance wheel(s).
Bearings worn or need lubrication?
No
È
Yes
Æ
Replace worn bearings or lubricate bearings as needed.
Reference Maintenance, General, Bearings.
Wheel(s) rubbing on inlet?
No
È
Yes
Æ
Adjust wheel(s) or inlet.
Fan rotation correct?
Yes
È
No
Æ
Reverse fan rotation.
Reference Supply Fan, Start-Up.
Everything is working properly, consult factory.