Model IGX Make-Up Air
10
®
1. Install Curb and/or Equipment/Leg Support(s)
Position curb and/or equipment/leg support(s) on
the roof (reference the unit submittal for placement
in relation to the unit). Verify that unit supports are
level; shim if necessary. Attach curb to roof and flash
into place using appropriate methods. Attach the
equipment/leg support(s) to the roof, remove metal
cover, flash to wooden nailer, and reinstall cover.
Metal Cover
Equipment
Support
Roof Curb
Curb and Equipment Support
Leg Supports
Unit Profile and Leg Support
2. Install Ductwork
Follow good duct practices for all ductwork. Install
ductwork in accordance with SMACNA and AMCA
guidelines, NFPA 96 and local codes. Reference
Installation, Duct Sizes
section in this Installation,
Operation, and Maintenance Manual for proper
duct sizes.
The use of a duct adapter is recommended on a
downblast (DB) arrangement to align the ductwork with
the supply unit. The duct adapter is only a guide and is
not to be used as a support for the ductwork.
3. Apply Sealant
Apply an appropriate sealant around the perimeter of
the curb and duct to isolate fan vibration and prevent
water penetration.
Supply Air Ductwork
(Arrangement DB only)
Sealant
Ductwork
Installation
Outdoor Unit Mounting
Standard Curb