background image

4

Model H-G/H-GB Centrifugal Roof Exhaust Fan

Model H-GPF

or SD Curb

5/16 in. recommended

1/4 in. fastener minimum

See table for fastener quantities

Tie Down Detail (H-GB Only)

Fig. 7

Pre-Starting Checks

  1.  Check all fasteners and set screws for tightness. The 

wheel should rotate freely and be aligned as shown 
in figure 9.

  2.  Wheel position is preset and the unit is test run at the 

factory. Movement may occur during shipment and 
realignment may be necessary.

  3.  Only H-G unit - Centering height alignment can be 

accomplished by loosening the set screws in the 
wheel and moving the wheel to the desired position.

  4.  Only H-GB unit - Centering can be accomplished by 

loosening the bolts holding the drive frame to the 
shock mounts and repositioning the drive frame.

  5.  Only H-GB unit - Wheel and inlet cone overlap can 

be adjusted by loosening the set screws in the wheel 
and moving the wheel to the desired position.

  6.  Only H-GB unit - Fan RPM should be checked and 

verified with a tachometer.

  7.  Check wheel rotation (viewing from the shaft side) 

by momentarily energizing the unit. On a H-G unit 
the rotation should correspond to the rotation decal 
on the unit, see figure 10. On a H-GB unit rotation 
should be clockwise as shown in Fig. 10 and 
correspond to rotation decal on the unit. If wheel 
rotation is incorrect reverse two of the wiring leads or 
check motor wiring for single phase.

Table 1

Model

Fasteners Per Side

Total Fasteners

H-G 060 - 141

3

12

H-G 150 - 180

5

20

H-GB 071 - 161

3

12

H-GB 180 - 300

5

20

  5.  Secure fan to curb. Fasteners on each side of the fan 

are to be installed with one fastener 4 in. 

(102 mm)

 

from each edge and one fastener centered, see 
figure 6 and table 1. Remaining fasteners should be 
equally spaced in between. Shims may be required 

depending upon curb installation and roofing 

material.

  6.  Tie downs shall be run from one corner fastener thru 

tie down point and attach with other corner fastener. 

Tie downs are not required to meet 150 mph wind 

loads for sizes 240 and smaller. (Tie downs are 

included for sizes 260, 300 and 300HP.)

  7.  Verify power line wiring is de-energized before 

connecting fan motor to power source.

  8.  Connect power supply wiring to the motor as 

indicated on the motor nameplate or terminal box 

cover. Check the power source for compatiblity with 

the requirements of your equipment.

  9.  Check fan wheel for free rotation, re-center if 

necessary.

10.  Check all fasteners for tightness.
11.  Mount and wire safety disconnect switch under 

motor cover. Wire control switches at ground level, 

refer to figure 8.

12.  Replace motor cover.

MOTOR 

L1 

115/208-230/60/1 

208-230/460/60/3

MOTOR

J-BOX

J-BOX 

SUPPLY VOLTAGE 

SUPPLY VOLTAGE

L2 

L1

L2

L3

Typical Wiring Diagram

Fig. 8

Fan to Curb Mounting

Fig. 6

1/4 in. fastener minimum

5/16 in. recommended

FAN TO CURB MOUNTING DETAIL

H-GPF or SDCurb

Model H-G or H-GB

Fastener 4 in. 

from curb edge

Summary of Contents for H-G 060

Page 1: ...nt should be checked to make sure it is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediat...

Page 2: ...e necessary depending upon roofing material thickness The motor amperage and voltage ratings must be checked for compatibility to supply voltage prior to final electrical connection For H G H GB insta...

Page 3: ...of rust occur Immediately remove the original rust preventive coating with petroleum solvent and clean with lint free cloths Polish any remaining rust from surface with crocus cloth or fine emery pape...

Page 4: ...ring leads or check motor wiring for single phase Table 1 Model Fasteners Per Side Total Fasteners H G 060 141 3 12 H G 150 180 5 20 H GB 071 161 3 12 H GB 180 300 5 20 5 Secure fan to curb Fasteners...

Page 5: ...071 161 1 4 6 H GB 180 240 3 8 10 H GB 260 300 1 2 13 Do not force belt s Forcing the belt s will break the cords and cause belt failure Belts Fig 11 Slack Side Deflection Fig 14a Fig 14b 11 Belt ten...

Page 6: ...elt Bearing Maintenance H GB Unit 1 Belts tend to stretch after a period of time They should be checked periodically for wear and tightness When replacing belts use the same type as supplied with the...

Page 7: ...If unit is to be left idle for an extended period remove belts and store in a cool dry place to avoid premature belt failure Recommended Relubrication Frequency in Months NOTE If unusual environment...

Page 8: ...Deck Anchoring Metal Building Steel Deck Anchoring Wood Deck Anchoring Fig 15 Minimum Concrete Strength of 2000 PSI Roof Opening Roof Opening Center fasteners on flange Outside Flange Use 12 Wood Scre...

Page 9: ...uctwork Check proper operation of face and bypass dampers Check filters and access doors FAN DOESN T OPERATE Electrical Supply Check fuses circuit breakers Check for switches off Check for correct sup...

Page 10: ...on Model Volts Hertz Phase Amps Mark Supply hp Exhaust hp Serial Number Motor Voltage Motor Amperage Fan rpm Service Organization Address City State Zip Phone Fax Work Done By Field Start Up Documenta...

Page 11: ...ng service and replacement parts Before taking any corrective action make certain unit is not capable of operation during repairs CAUTION A fan manufactured with an explosion resistant motor does not...

Page 12: ...k will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Greenheck C...

Reviews: