Greenheck FD150X Installation, Operation And Maintenance Instructions Download Page 1

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job 
is complete.

“UL CLASSIFIED (see complete marking on product)”

“UL CLASSIFIED to Canadian safety standards (see 

complete marking on product)”

 

UL Standard 555 (Listing #R13317) 

RECEIvIng AnD HAnDLIng

Upon receiving dampers, check for both obvious and 
hidden damage. If damage is found, record all necessary 
information on the bill of lading and file a claim with the 
final carrier. Check to be sure that all parts of the shipment, 
including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage 
and protection from dirt, dust and the weather is highly 
recommended. Do not store at temperatures in excess of 
100°F.

Part number 453946

InStALLAtIon SUPPLEmEntS

Refer to the appropriate Greenheck installation 
supplements for special requirements:
• 

Support Mullions

• 

Shaftwall Supplement

• 

Drywall Supplement

• 

Grille Installation Supplement

• 

Drive Slip Supplement

• 

Sealant Supplement

• 

Sleeve Extension Supplement

• 

Single sinde Retaining Angles Supplement

Note:  Refer to Greenheck IOM, Part #461335, for 

CFSD models to be installed in corridor ceiling 
applications.

FD & DFD 150X moDELS

1

2

 Hour

Curtain Fire Dampers

vertical or Horizontal mount

  FD and DFD 150X Series models are intended for

  installation in accordance with fire damper requirements 

  established by:

 national Fire Protection Association

 NFPA Standard 80, 90A, & 101

 IBC International Building Codes
 CSFm California State Fire marshal

 Fire Damper Listing (#3225-0981:102)
 

new York City 

(BSA/MEA listing #260-91-M)

34

!4

% /

& #!,)&/2.

)!

3

4!

4%

&)2

% -!2 3 (

!,

,

3 % 2

6 ) # %

, )

3 4 ) . '

Installation, Operation and Maintenance Instructions

Due to continuing research, Greenheck reserves the right to change specifications without notice.

SAFEtY WARnIng:

Improper installation, adjustment, alteration, service 
or maintenance can cause property damage, injury 
or death. Read the installation, operating, and 
maintenance instructions thoroughly before installing 
or servicing this equipment.

WARRAntY

Greenheck warrants this equipment to be free from 
defects in material and workmanship for a period of one 
year from the purchase date. Any units or parts which 
prove to be defective during the warranty period will be 
repaired or replaced at our option. Greenheck shall not 
be liable for damages resulting from misapplication or 
misuse of its products. Greenheck will not be responsible 
for any installation or removal costs. Greenheck will not be 
responsible for any service work or backcharges without 
prior written authorization. 

Summary of Contents for FD150X

Page 1: ...ications FD DFD 150X Models 11 2 Hour Curtain Fire Dampers Vertical or Horizontal Mount FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements establis...

Page 2: ...ulking may be applied to the retaining angles 8 ACCESS Suitable access such that fusible links can be changed must be provided for damper inspection and servicing Where it is not possible to achieve s...

Page 3: ...ll floor material The angles should only sandwich the wall floor and allow for damper expansion during periods of intense heat Galvanized steel fire dampers and sleeves 1 8 in 3mm per linear foot of d...

Page 4: ...Size for Multi Section Dampers in mm FD 150X H or V 48 x 48 1219 x 1219 96 x 48 or 120 x 40 2438 x 1219 or 3048 x 1016 DFD 150X V 36 x 36 914 x 914 72 x 48 or 60 x 60 1829 x 1219 or 1524 x 1524 DFD 15...

Page 5: ...ons described may have duct sealant PA2084T duct sealant adhesive manufactured by Precision DP1010 water base duct sealant by Design Polymetrics Grey Pookie or Ductmate PROseal applied in accordance w...

Page 6: ...469 U485 U494 11 2 Hour Design U449 U452 U470 U471 2 Hour Design U403 U411 U412 U421 U425 U428 U429 U443 U453 U474 U475 U477 U484 U491 U495 3 FRAMING OF WALL OPENING Form a wall opening 1 8 in 3mm to...

Page 7: ...st Damper Trouble Shooting The following is a cause and correction list for common concerns with the dampers Item Description 1 FD150X fire damper with SSC option 2 Steel stud wall see UL Fire Resista...