20
Energy Recovery Ventilator
CO
2
PROPORTIONAL CONTROL
Parameter
Setting
V1000
J1000
B1-17
VFD Start-Up Setting
1
1
C6-02
Carrier Frequency
1
1
D2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
FLA
FLA
H3-03
Analog Frequency
Reference (Gain)
150%
150%
H3-04
Analog Frequency
Reference (Bias)
25%
25%
L2-01
Ride Thru Power Loss
2
2
L4-05
Frequency Ref Loss
0
NA
L5-01
Auto Restart Attempt
5
5
A1-01
Access Level
0
0
VARIABLE FREQUENCY DRIVES
FOR ENERGY RECOVERY WHEEL
Parameter
Setting – J1000
A1-01
Access Level
2
B1-17
VFD Auto Start
1
C1-04
Decel Time
600
*C4-01
Torque Gain
0.6
C6-02
Carrier Frequency
2
D2-01
Ref Upper Limit
40 or 50*
D2-02
Ref Lower Limit
5%
E2-01
Motor Rated FLA
Motor FLA
E2-03
Motor No-Load Current
Must be less
than FLA
H1-02
Multi-Function Input
(Terminal S2)
6
H2-01
Multi-Function Output
(MA, MB, MC)
4
H1-04
Multi-Function Input Sel 4
(Terminal S4)
7
Economizer Signal Source
(0-10 VDC)
Setting
Honeywell
Module
Carel
Controller
H3-03
Analog Frequency
Reference (Gain)
0
40 or
50*
H3-04
Analog Frequency
Reference (Bias)
40 or
50**
0
L1-01
Elect Thermal Overload
2
L2-01
Ride Thru Power Loss
2
L4-01
Frequency Detection
Level
15
L5-01
Auto Restart Attempt
5
A1-01
Access Level
0
* 208/230 volt only
**36 through 52 inch wheels are 40 (24 Hz)
58 or 74 inch wheel is 50 (30 Hz)