background image

Vibration

Excessive vibration may be experienced during initial 
start-up. Left unchecked, excessive vibration can 
cause a multitude of problems, including structural and/
or component failure. The most common sources of 
vibration are listed.

Many of these 
conditions can be 
discovered by careful 
observation. Refer to 
the Troubleshooting 
section of this manual 
for corrective actions. 
If observation cannot 
locate the source of 
vibration, a qualified 

technician using vibration analysis equipment should be 
consulted. If the problem is wheel unbalance, in-place 
balancing can be done.

Generally, fan vibration and noise is transmitted to other 
parts of the building by the ductwork. To eliminate this 
undesirable effect, the use of heavy canvas connectors 
is recommended.

Wheel Unbalance
Drive Pulley Misalignment
Incorrect Belt Tension
Bearing Misalignment
Mechanical Looseness
Faulty Belts
Drive Component Unbalance
Poor Inlet/Outlet Conditions
Foundation Stiffness

Drive Belt

Inspect the drive belt. Make sure the belt rides smoothly 
through the pulley and over the wheel rim.

Air Seals

Check that the air seals located around the outside of 
the wheel and across the center (both sides of wheel) 
are secure and in good condition. Air seal clearance 
is determined by placing a sheet of paper, to act as a 
feeler gauge, against the wheel face. To access seals, 
follow the instructions in the Energy Recovery Wheel 
Maintenance section. To adjust the air seals, loosen all 
eight seal retaining screws. These screws are located 
on the bearing support that spans the length of the 
cassette through the wheel center. Tighten the screws 
so the air seals tug slightly on the sheet of paper.

Replace cassette into unit, plug in wheel drive, replace 
access door and apply power. Observe by opening door 
slightly (remove filters if necessary to view wheel) the 
wheel should rotate freely at about 20-40 RPM.

Energy Recovery Wheel

The ERVe models contain a total energy recovery 
wheel. The wheels are inspected for proper mechanical 
operation at the factory. However, during shipping 
and handling, shifting can occur that may affect 
wheel operation. The wheel is accessible through the 
access door marked 
“Energy Wheel 
Cassette Access”.

Turn the energy 
recovery wheels 
by hand to verify 
free operation. The 
wheel should rotate 
smoothly and should 
not wobble.

Inside layout of ERVe

Drive Belt

Adjustable 

Air Seals

Label showing 

cassette serial # 

and date code

Bearing 

Support

Drive Pulley

Optional Start-Up Components

Dirty Filter Switch

To adjust the switch, the unit must be running with 
all of the access doors in place, except for the 
compartment where the switch is located (exhaust 
intake compartment). The adjusting screw is located on 
the top of the switch. 

1.  Open the filter compartment and place a sheet of 

plastic or cardboard over 50% of the filter media. 

2.  Replace the filter compartment door. 

3.  Check to see if there is power at the alert signal 

leads (refer to electrical diagram). 

4.  Whether there is power or not, turn the adjustment 

screw on the dirty filter gauge (clockwise if you did 
not have power, counterclockwise if you did have 
power) until the power comes on or just before the 
power goes off. 

5.  Open the filter compartment and remove the 

obstructing material. 

6.  Replace the door and check to make sure that you 

do 

not

 have power at the alert signal leads. 

The unit is now ready for operation. 

Setscrew (on front of switch) must 
be manually adjusted after the 
system is in operation.

Negative pressure connection 
is toward the ‘front or top’ of 
the switch. 

(Senses pressure on the 

blower side of filters)

Positive pressure connection is toward the ‘back or bottom’ 
of the switch. 

(Senses pressure at air inlet side of filters)

Energy Recovery Ventilator

16

®

Summary of Contents for ERVe Series

Page 1: ...is not exceeding the motor nameplate amps 5 Do not allow the power cable to kink or come in contact with oil grease hot surfaces or chemicals Replace cord immediately if damaged 6 Verify that the pow...

Page 2: ...0 Routine Maintenance 21 23 Troubleshooting Economizer Alarms 24 Air ow 25 Unit 25 27 Maintenance Log Backcover Our Commitment Backcover Unit Overview Basic Unit The ERVe units are prewired such that...

Page 3: ...ter ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic...

Page 4: ...es Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A B C D E F G H ERVe 20 11 8 18 0 12 2 1...

Page 5: ...h must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 950 ERVe 35 25 44 5 1270 ERVe 45...

Page 6: ...53 48 286 106 ERVe 45 67 353 55 478 67 353 55 286 120 ERVe 55 78 228 65 416 78 228 65 224 148 All dimensions are in inches Weights are for 14 inch high GKD type curbs W L W WF LF L Curb Outside Dimens...

Page 7: ...based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Examples of poor and good fan to duct...

Page 8: ...le in the cabinet bottom and wire to the disconnect switch Seal penetration in cabinet bottom to prevent leakage The electric supply to the unit must meet stringent requirements for the system to oper...

Page 9: ...carrying the supply power Make sure that eld supplied conduit does not interfere with access panel operation If wire resistance exceeds 0 75 ohms an industrial style plug in relay should be added to...

Page 10: ...tion sensor light NC C NO NC C NO SUPPLY DIRTY FILTER SWITCH EXHAUST DIRTY FILTER SWITCH DIRTY FILTER HOT COMMON 24V SEC Dirty Filter Indicator powered by others C C C R R R G 4 Y1 6 7 12 S6 ECONOMIZE...

Page 11: ...ptured Exhaust Only Operation This option allows for the exhaust fan to run continuously while the supply fan is off Frost Control Extremely cold outdoor air temperatures can cause moisture condensati...

Page 12: ...eel should stop rotating the sensor will close a set of contacts in the unit control center Field wiring of a light or other alarm between terminals R and 12 in the unit control center will notify mai...

Page 13: ...__________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remove any foreign objects that a...

Page 14: ...s No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Control Panel Yes No N A Variable...

Page 15: ...nd belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in this section Fan Belt Installati...

Page 16: ...by opening door slightly remove lters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a total energy recovery wheel The whee...

Page 17: ...ton to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter to return the current menu para...

Page 18: ...PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTING PARAMETER A1 01 CHANGE TO 0 USER TO PROVIDE CONTACTS AND ISO...

Page 19: ...multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provided from the factory for field m...

Page 20: ...n 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H1 02 Multi Function Input Term...

Page 21: ...tors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the motor housing assists proper motor...

Page 22: ...ds upon the cleanliness of the incoming air These lters should be cleaned prior to start up Clean lters by rinsing with a mild detergent in warm water Outdoor Air Filters Access to the outdoor air lte...

Page 23: ...sh remove any heavier accumulation A detergent water solution can also be used Avoid aggressive organic solvents such as acetone The energy recovery wheel segments can be soaked in the above solution...

Page 24: ...denti ed and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired alarm 2 Press the enter 3...

Page 25: ...information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Unit 2 Unit 3 Unit 4 Model Number...

Page 26: ...lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check motor namepl...

Page 27: ...heel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start Up Section Excessive noise or...

Page 28: ...tes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ __...

Reviews: