Grille Installation

Mount grille to underside of ceiling radiation damper 
using #10 x 

1

2

 in. Phillips head stainless steel sheet 

metal screws provided with SP fan.

ETL Installation - 1 Hour Combustible Floor/Ceiling Assemblies

(formerly Warnock Hersey)

Ceiling Exhaust Fan Installation

1.  Fan/damper assemblies installed in combustible floor 

ceiling assemblies with gypsum board ceilings require 
the use of a plaster flange (

Item 3 in Figure 6

). A plaster 

flange kit, which comes with all of the necessary 
mounting hardware, is supplied with the unit.

2.  The fan/damper assembly is to be attached to the 

trusses using 2 - 1 in. x 1 in. x 16 ga. 
(25mm x 25mm x 1.5mm) or 2 - 11/4 in. x 1 in. x 20 ga. 
(32mm x 25mm x 1mm) mounting angles. Attach 
mounting angles to the damper with a minimum of 
2 - #8 screws or 

5

32

 in. (4mm) diameter steel rivets.

Note: Make sure the fasteners do not interfere with the 
damper operation.
3.  Install the fan/damper assembly, with attached mounting 

angles, between the trusses as shown in 

Figure 6

 and 

attach mounting angles to the trusses using 4 - 11/4 in. 
long steel screws per mounting angle.

4.  Run a minimum of 4 - 1 in. (25mm) long #6 screws 

through the gypsum board into the plaster flange as 
shown in 

Figure 6

.

Figure 6: CRD with SP Fan

CRD Series for SP Fans

5

®

Summary of Contents for CRD-3 Series

Page 1: ...D 700 Series for SP Fans Installation Operation and Maintenance Manual Please read and save these instructions for future reference Read carefully before attempting to assemble install operate or main...

Page 2: ...Motors for fan models used in conjunction with CRD shall be equipped with thermal cut off fuse control Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage...

Page 3: ...he assembly around the damper in the orientation shown in Figure 1 Connect the open ends of the flange together 2 Align the edge of the plaster flange with the edge of the damper frame Clamp the flang...

Page 4: ...B200 CRD 320 CRD 320L CRD 320 41 2 155 8 141 2 123 8 SP A50 SP A70 SP A90 SP A110 SP A125 SP A190 CRD 310WT CRD 310 CRD 310L CRD 310 WT CRD 310 51 2 145 8 135 8 111 8 SP A250 SP A290 SP A390 SP A200...

Page 5: ...with the unit 2 The fan damper assembly is to be attached to the trusses using 2 1 in x 1 in x 16 ga 25mm x 25mm x 1 5mm or 2 11 4 in x 1 in x 20 ga 32mm x 25mm x 1mm mounting angles Attach mounting...

Page 6: ...minimum of 2 8 screws or 5 32 in 4mm diameter steel rivets Note Make sure the fasteners do not interfere with the damper operation 3 Install the fan damper assembly with attached mounting angles betwe...

Page 7: ...when using with a suspended ceiling UL cUL Installation 3 Hour Non Combustible Floor Ceiling Assemblies SP Fan 10 32 Threaded Steel Rod Hanging Vibration Isolation Ceiling Radiation Damper Fire Rated...

Page 8: ...eals Adjust frame such that it is square and plumb Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oi...

Reviews: