background image

Centrifugal Inline Fans

9

®

Grease Manufacturers

Manufacturer 

Grease (NLGI #2)

U.S. Electric Motors

Grease No. 83343

Chevron U.S.A. Inc

Chevron SRI Grease #2

Mobil Oil Corporation

Mobilith

Mobil 532

Texaco, Inc.

Premium BRB #2

Texaco Multifak #2

Amoco Oil Co.

Rykon Premium #2

Exxon

Unirex N2

Shell

B Shell Alvania #2

Suggested Fan Bearing Greasing Intervals

Interval 

(months)

Type of Service

1 to 3

Heavy duty in dirty, dusty locations; high ambient 
temperatures; moisture laden atmosphere; vibration.

3 to 6

12 to 24 hours per day, heavy duty, or if moisture  
is present

6 to 12

8 to 16 hours per day in clean, relatively dry 
atmosphere

12 to 18

Infrequent operation or light duty in clean 
atmosphere

Recommended Relubrication & 
Frequency Intervals in Months

NOTE: If unusual environment conditions exist (extreme 
temperature, moisture or contaminants) more frequent 
lubrication is required.

A good quality lithium base grease, conforming to  
NLGI Grade 2 consistency, such as those listed here 
may be used.

Summary of Contents for BSQ-M 100

Page 1: ...erify that the power source is compatible with the equipment 7 Never open access doors to a duct while the fan is running Model SQ M Direct Drive Model SQ M is a direct drive centrifugal inline exhaus...

Page 2: ...parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts...

Page 3: ...886 347 8 762 30 508 20 406 16 0 1192 x CFM 159 350 18 ga 889 x 889 35 x 35 300 300HP 1168 46 965 38 1168 46 1064 417 8 864 34 559 22 457 18 0 0826 x CFM 244 537 16 ga 1067 x 1067 42 x 42 360 360HP 13...

Page 4: ...ss panels are located on the two sides adjacent to the motor Figure 5 Vertical Hanging or Base Mount G B B D D Hanging rails by others Mounting Dimensional Data Model A B C D G SQ M 70 270 105 8 432 1...

Page 5: ...8 BSQ M 160 420 35 13 8 35 13 8 64 2 Spring Base Isolators Model H J J1 L I K SQ M 70 90 38 1 51 2 70 2 152 6 SQ M 100 160 35 13 8 51 2 150 515 16 BSQ M 70 140 35 13 8 35 13 8 60 23 8 150 515 16 BSQ...

Page 6: ...itical Reversed rotation will result in poor air performance motor overloading and possible burnout Check wheel rotation by momentarily energizing the unit all SQ M and BSQ M fans have clockwise wheel...

Page 7: ...not striking the venturi or any obstacle 3 Start the fan and shut it off immediately to check rotation of the wheel with directional arrow in the motor compartment see Figure 8 4 When the fan is star...

Page 8: ...dition that will cause vibration in the fan WARNING This unit should be made non functional when cleaning the wheel or housing fuses removed disconnect locked off Torque Speci cations for Bushings Ref...

Page 9: ...y duty in dirty dusty locations high ambient temperatures moisture laden atmosphere vibration 3 to 6 12 to 24 hours per day heavy duty or if moisture is present 6 to 12 8 to 16 hours per day in clean...

Page 10: ...l Inline Exhaust Fan VENTURI WHEEL ACCESS PANEL HOUSING VENTURI PANEL WHEEL MOTOR COVER MOTOR MOTOR COVER MOTOR ACCESS PANEL BSQ M Belt Drive Centrifugal Inline Exhaust Fan Parts List Each fan bears a...

Page 11: ...tighten See Pre Start Up Checks pages 6 7 Foreign objects in wheel or housing Remove objects check for damage or unbalance Reduced air ow System resistance too high Check system Proper operation of ba...

Page 12: ...ct area tab and in the Technical Data Library Greenheck s Centrifugal Inline Fans catalog Models SQ M and BSQ M provides additional information describing the equipment fan performance available acces...