background image

Sidewall Propeller Fans

6

®

DANGER

Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect power 
source can result in fire, shock or serious injury.

Once the fan has been put into operation, a periodic 
maintenance program should be set up to preserve the 
reliability and performance of the fan. Items to be 
included in this program are fasteners and setscrews, 
lubrication, and removal of dust and dirt.

Fasteners and Setscrews

Any fan vibration has a tendency to loosen mechanical 
fasteners. A periodic inspection should include checking 
all fasteners and setscrews for tightness. Particular 
attention should be paid to setscrews or taper-lock 
bushings attaching the propeller to the motor shaft and 
the motor shaft to the bearings. In addition, check all 
fasteners attaching the motor to the motor plate.

Lubrication

Many fractional horsepower motors installed on 
the smaller fans are lubricated for life and require 
no further attention. Motors equipped with oil holes 
should be oiled in accordance with the manufacturer’s 
instructions printed on the motor. Use a high grade SAE 
20 machine oil and use caution not to over lubricate. 
Motors supplied with grease fittings should be greased 
according to directions printed on the motor.
Removal of Dust and Dirt
Dirt clogs cooling openings on the motor housing, 
contaminates bearing lubricant and collects on propeller 
blades causing severe imbalance if left unchecked. 
The exterior surface of the motor, fan panel and entire 
propeller should be thoroughly cleaned periodically. 
Use caution and do not allow water or solvents to enter 
the motor or bearings. Motors or bearings must not be 
sprayed with steam or water.

Maintenance

Summary of Contents for AER-M

Page 1: ...quately grounded 4 Do not spin fan propeller faster than max cataloged fan RPM Adjustments to fan speed significantly affects motor load If the fan RPM is changed the motor current should be checked t...

Page 2: ...build up Leave coverings loose to permit air circulation and to allow for periodic inspection The unit should be stored at least 3 1 2 inch 89 mm off the floor on wooden blocks covered with moisture...

Page 3: ...it be operated in a completely level position For further details on safety practices involving industrial and commercial fans please refer to AMCA Publication 410 Electrical Disconnects All fan motor...

Page 4: ...ortant to reduce turbulence and damper flutter which may lead to premature damper failure Pre Installation Checks Fan Size Damper Size Square Recommended Wall Opening W O Square M Minimum Figure 1 Fig...

Page 5: ...heavy motors and all Filtered Supply Wall Housings need additional bracing Typical Installation Check all fasteners and setscrews for tightness This is especially important for bearing setscrews The...

Page 6: ...o the bearings In addition check all fasteners attaching the motor to the motor plate Lubrication Many fractional horsepower motors installed on the smaller fans are lubricated for life and require no...

Page 7: ...ises sometimes heard during operation by adjusting a simple setting on the controller Debris Remove all debris from the fan Fan does not operate Electrical supply Check fuses circuit breakers Check fo...

Page 8: ...Phase _______ Actual Voltage ________ Hertz _______ Phase __________ Amps ________________ Mark _________________ Actual Amperage ______________________________________ Supply hp ____________ Exhaust...

Reviews: