background image

16

Canopy Hood

®

HOOD SECTION VIEW

DEFLECTOR TO BE PLACED CENTERED
UNDER THE SUPPLY DUCT COLLAR

SUPPLY
FIRE DAMPER

INTERNAL

SUPPLY

CHAMBER

HOOD

INSULATED
SUPPLY PLENUM

EXHAUST

CAPTURE

SUPPLY LOCATION DETAIL FOR

AIR CURTAIN AND COMBINATION

Hanger Bracket

Exhaust Plenum

Duct Cut Out Area

Duct Cut Out Area

Supply Plenum

Hood Length

Hood Width

Front of Hood

Exhaust Plenum

8.00

8.00

8.00

3.00

3.00

16.00

14.00

8.00

1.00

12.00

A CONTINUOUS LIQUID TIGHT WELD TO HOOD.

EXHAUST DUCT CONNECTION IS TO BE

CONNECTION

EXHAUST DUCT

FRONT OF HOOD

HANGER BRACKET

EXHAUST PLENUM

EXHAUST PLENUM

SUPPLY PLENUM

DUCT CUT OUT AREA

LABELED SUB-ASSEMBLY FOR EXHAUST HOOD WITHOUT EXHAUST DAMPER PART NO. DC.

2. U.L. LISTED HOOD ASSEMBLY TO BE USED ONLY WITH GREENHECK FAN CORP.

CENTER OF HOOD LENGTH TO CENTER OF DUCT CONNECTION.

NOTES: 1. EXHAUST DUCT CONNECTION TO BE LOCATED WITH IN 48" FROM

1" TO 2" TACKS OR SHEET METAL SCREWS AT 3" TO

6" SPACING TO HOOD.

SUPPLY DUCT CONNECTION TO BE TACK WELDED WITH

CONNECTION

SUPPLY DUCT

DUCT CUT OUT AREA

Hanger Bracket

Exhaust Plenum

Duct Cut Out Area

Duct Cut Out Area

Supply Plenum

Hood Length

Hood Width

Front of Hood

Exhaust Plenum

8.00

8.00

8.00

3.00

3.00

16.00

14.00

8.00

1.00

12.00

Back View of the Hood

Fig 25

Fig. 26

Fig. 27

Fig. 28

 

Note: UL listed hood 
assembly to be used 
only with Greenheck 
Fan Corp. labeled 
subassembly for 
exhaust hood without 
exhaust damper part 
Number DC.

Hood Top

1.  The exhaust duct 

connection needs to 
be located within 48 in. 
(121.92 cm) from the 
center of the hood 
length to the center of 
the duct connection. 
(see Fig. 24, back view 
Fig. 25)

2.  The exhaust duct 

connection is to be 
a continuous liquid- 
tight weld. 

Weld with 

a non-ferrous filler 
wire, such as silicon 
bronze or stainless 
steel filler wire. Protect 
all stainless steel areas 
from weld splatter.

3.  The supply duct 

connection is tack-
welded at 1 to 2 in. 
(2.54 to 5.08 cm) 
intervals, or sheet metal 
screws at 3 to 6 in. 
(7.62 cm to 15.24 cm) 
spacing to the hood. 
(Fig. 26)

4.  The deflector is 

centered under the 
supply duct collar.  
(Fig. 28)

5.  For hoods that are 

insulated, the edges of  
the insulation need to 
be taped after the hole 
is cut, (the insulation 
tape is to be provided 
by others).

6.  On combination hoods, 

make sure the fire 
damper is located over 
the internal supply 
chamber. (Fig. 29)

Top View of the Hood

Fig. 24

Installing Duct Collars

Summary of Contents for 452413

Page 1: ..._________ Model _______________________ Mark __________________ Serial ________________________ Model _______________________ Mark __________________ Serial ________________________ Model _______________________ Mark __________________ Serial ________________________ Model _______________________ Mark __________________ Serial ________________________ Model _______________________ Mark ___________...

Page 2: ...Hanging the Back Supply Unit 10 Hanging the Hood 11 Air Diffusers 11 Enclosure Panel Installation Instructions 12 End Skirt Installation Instructions 13 Backsplash Panel Installation Instructions 14 15 Duct Collar Installation Instructions for GH GK and GX Series Hoods 16 Exhaust Air Balancing Baffle 17 Balancing the Kitchen Exhaust 18 Baffle Filters GH Series 18 21 High Velocity Cartridge Filters...

Page 3: ...3 Canopy Hood Maintenance 32 Grease Grabber Cleaning and Maintenance 33 34 Filter Cleaning Frequency Chart 35 Troubleshooting Guide 36 37 Replacement Parts 38 39 Warranty 40 Table of Contents ...

Page 4: ...ft 59 52 kg m 44 lbs ft 65 47 kg m 48 lbs ft 71 42 kg m 52 lbs ft 77 38 kg m GH GK GXCW 48 lbs ft 71 42 kg m 51 lbs ft 71 89 kg m 54 lbs ft 81 35 kg m 57 lbs ft 84 82 kg m GH GK GXSW 44 lbs ft 65 47 kg m 48 lbs ft 71 42 kg m 52 lbs ft 77 38 kg m 56 lbs ft 83 33 kg m GGEW 39 lbs ft 58 03 kg m 41 lbs ft 61 01 kg m 44 lbs ft 65 47 kg m 47 lbs ft 69 94 kg m 49 lbs ft 72 91 kg m GGDW 45 lbs ft 66 96 kg...

Page 5: ...iling supports All hanger brackets must be used and the hood must be properly supported while lifting to prevent damage or distortion to the hood The hood must be hung level to operate properly After hood is secured make the exhaust duct connections The fire system distributor must be contacted at this time After the fire system has been installed mount the enclosures then the supply plenums If an...

Page 6: ...CLIPS 1 4 in BOLTS 5 CAULK ALL SEAMS AS NECESSARY CAP NUTS AS INDICATED HOOD FRONT 1 REMOVE SUPPORT ANGLE ON OPEN END PANEL HOOD ACORN NUT BOLT U CLIP CAULK 2 RAISE ALL HOODS INTO APPROPRIATE LOCATION AND SUPPORT PER CONSTRUCTION PLANS 3 FASTEN TOP ANGLES TOGETHER USING 1 4 in BOLTS NUTS BY OTHERS 4 FASTEN HOODS TOGETHER USING U CLIPS 1 4 in BOLTS 5 CAULK ALL SEAMS AS NECESSARY CAP NUTS AS INDICAT...

Page 7: ...lights must be wired to multiple circuits Each circuit must have less than 14 lights total Standard Greenheck light switches shipped on hoods are rated for 15 amps and shall not have more than 14 lights connected to them Higher amperage switches are available upon special request Exhaust As specified in NFPA 96 Ch 7 5 latest edition exhaust duct systems must be constructed in the following manner ...

Page 8: ... to the supply plenum hanger brackets HOOD STANDING SEAM HANGING CLIP BOLTED TO PLENUM SHELL HANGING CLIP HOOD FRONT C CLAMP SUPPLY PLENUM SHELL HANGER BRACKET END VIEW THREADED ROD HOOD ATTACH HANGING CLIP TO HOOD STANDING SEAM WITH THE SUPPLIED C CLAMPS OPTIONAL DRILL AND BOLT A 1 4 20 SS BOLT THROUGH THE CLIP AND HOOD STANDING SEAM HANGING METHODS FOR SUPPLY PLENUMS ASP FSP AND VSP TOP VIEW HOO...

Page 9: ...o 6 in 7 62 to 15 24 cm intervals External Supply Plenum Weights Dimensions and Supply Rates Fig 10 Fig 9 Using the UL Listed Fastener Provided 1 Drill a 9 32 in hole for the 1 4 in bolt from the inside of the supply plenum to inside the hood Fasteners are to be located max 6 in 15 24 cm from the end of the hood with max spacing between bolts 36 in 91 44 cm DO NOT include utility cabinets or fille...

Page 10: ... 24 to 25 4 cm of space below the plenum for access to the air diffusers 6 Fasten the Back Supply to the wall going through the lower Back Supply wall Fig 15 L 2 L 2 L MODULE LENGTH THE SUGGESTED LOCATION ABOVE CUT 1 4 in X 24 in OPENING AT CENTERED ON WIDTH OF THE SUPPLY IF MODULE 6 ft STEP 1 Fig 12 Fig 14 Installing the Back Supply Plenum Hanging the Back Supply Plenum Installing the Supply Duct...

Page 11: ...Y STYLE HOOD INSTRUC SEAMS 5 CONNEC HOOD 4 LIFT THE HOOD IS THE HOO 1 THE HOO SHOULD 3 DUCTWO 2 BEFORE INSTRUC PROPER STE Fig 16 Canopy Style Hood Proximity Style Hood Removable Air Diffusers The air diffusers located at the bottom of the back supply Fig 17 will need to be cleaned as often as the application dictates Inspect periodically to determine the cleaning schedule 1 To clean the air diffus...

Page 12: ...lt the end enclosure panels together fasteners are not provided 3 Position the front enclosure panel s on the hood and bolt to the end enclosure panels with the 5 16 in bolts provided in the hardware package 4 Tack weld or clamp the front enclosure panel s to the hood If clamps are used they must be positioned 4 in 100 mm from the ends and in the center of the front enclosure panel 5 To allow for ...

Page 13: ...nd cap nut to the inside of the hood or tack weld the end skirt to the hood 3 Position the end skirt against the wall and attach The method depends on the wall construction fasteners for this are not provided 4 Caulk the internal joint formed by the end skirt and the hood end panel with NSF Approved silicone caulk GE SCS1009 or its equivalent The caulk is not provided 5 To allow for ease in cleani...

Page 14: ...46 IN 1168 4 MM IN MULTIPLE PIECES NOTE PANELS UP TO 48 IN 1219 2 MM WIDE SHIP IN ONE PIECE OVER 48 IN 1219 2 MM IN MULTIPLE PIECES LENGTH 1 IN 25 4 MM HEIGHT LENGTH HEIGHT LENGTH QTY Inches Millimeters 48 1219 2 1 48 94 1219 2 2387 6 2 94 141 2387 6 3581 4 3 141 188 3581 4 4775 2 4 188 235 4775 2 5969 5 LENGTH QTY Inches Millimeters 46 1168 4 1 46 91 1168 4 2311 4 2 91 136 2311 4 3454 4 3 136 181...

Page 15: ...anel to the wall 3 Caulk the joints between the hood and the backsplash panel with NSF Approved silicone caulk GE SCS1009 or its equivalent The caulk is not provided 4 Caulk the joint between the backsplash panels when multiple panels are required with NSF Approved silicone caulk GE SCS1009 or its equivalent The caulk is not provided HOLES SHOULD BE SPACED TO ADEQUATELY SECURE THE PANEL TO THE WAL...

Page 16: ...27 Fig 28 Note UL listed hood assembly to be used only with Greenheck Fan Corp labeled subassembly for exhaust hood without exhaust damper part Number DC Hood Top 1 The exhaust duct connection needs to be located within 48 in 121 92 cm from the center of the hood length to the center of the duct connection see Fig 24 back view Fig 25 2 The exhaust duct connection is to be a continuous liquid tight...

Page 17: ...Duct velocity 2 After the range for each hood is calculated it should be compared to the hood with the highest static pressure If the highest hood falls inside of the range then the hoods can be balanced with the EABB If it is higher than the range the hoods cannot be balanced Example 1 Hood 1 Ps 0 58 in wg Duct Velocity 1900 FPM Hood 2 Ps 0 44 in wg Duct Velocity 1800 FPM Hood 2 has the lower Ps ...

Page 18: ...ld be drawn from the kitchen to the dining area Therefore exhaust or supply air should be adjusted to provide a slight positive pressure in the dining area B To determine proper kitchen air balance 1 Refer to engineering drawings to determine total exhaust from the kitchen area Exhaust hoods dishwasher hoods etc 2 Determine total CFM of make up air supplied to kitchen area Make up air hoods heatin...

Page 19: ...eating the process for the remaining filters and summing the individual filter volumes x x x x x 2 in H 4 H 2 H 4 H Airflow Rotating Vane Anemometer Fig 30 Nominal Filter Size H x L Imperial Conversion Factor Metric Conversion Factor Inches Millimeters 16 x 16 400 x 400 1 63 157 16 x 20 500 x 400 2 13 198 20 x 16 400 x 500 1 90 177 20 x 20 500 x 500 2 48 230 Total hood volume Filter 1 Volume Filte...

Page 20: ...ume Avg Velocity Length m Height m 0 72 5 Calculate the system s volume by repeating the process for the remaining panels and adding the individual panel volumes together Total system volume Panel 1 Volume Panel 2 Volume Panel 3 Volume 606 4 614 3 593 8 1814 5 cfm 1029 1044 1009 3082 m3 hr Example Face Supply Hood with three 28 in 711 m Perforated Panels Measured velocities in FPM for one perforat...

Page 21: ...wo measurements For 16 in 400 mm wide filters position the grid as shown in Fig 34 Take velocity readings for each filter 3 Calculate each filter s volumetric flow rate by summing the flow rate of each individual filter in the hood 4 Calculate the total hood s volumetric flow rate by summing the flow rate of each individual filter in the hood Note For best accuracy multiply the velocity of each fi...

Page 22: ...the velocity of each location A digital 2 75 in 70 mm rotating vane anemometer or its equivalent is suggested The center of the anemometer should be held 2 in 50 mm from the face of the filters as in Fig 31 It is helpful to make brackets to keep the anemometer at the 2 in 50 mm distance and parallel to the filter Both squareness and distance are important for accuracy 3 Calculate the average slot ...

Page 23: ...er openings The conversion factor takes this into account Position the grid over each filter as shown Take velocity readings for each filter 3 Calculate each filter s volumetric flow rate by summing the flow rate of each individual filter in the hood 4 Calculate the total hood s volumetric flow rate by summing the flow rate of each individual filter in the hood Note For best accuracy multiply the ...

Page 24: ...on System Rotat Anem 1 2 Width 1 4 Width 1 4 Width 1 2 Height Fig 39 Filter 1 225 201 187 210 238 197 Filter 2 228 222 226 237 240 220 Filter 3 230 245 240 250 223 219 Filter 4 225 265 219 245 221 200 Average slot velocity for Filter 1 Sum of Velocity Readings Number of Readings 1258 6 209 7 fpm repeat for each filter For a nominal filter size of 20 x 20 the conversion factor is 1 65 Volume for Fi...

Page 25: ...ig 42 and 43 Average the two measurements For 16 in 400 mm high filters position the grid as shown in Fig 44 For 20 in 500 mm wide filters position the grid over the left and right side of the filter Average the two measurements Take velocity readings for each filter 3 Calculate each filter s volumetric flow rate by summing the flow rate of each individual filter in the hood 4 Calculate the total ...

Page 26: ...rage slot velocity 3 Calculate the CFM per linear foot by dividing the average velocity by a conversion factor of 5 52 per ft or 1 68 per m 4 Calculate the hoods exhaust volume by multiplying the CFM per linear foot by the total hood length Fig 45 Testing Hood Air Volume Example 4 ft 1 22 m short circuit hood 36 in 914 m short circuit opening Number of readings 36 in 8 in 6 readings 914 m 2 m 6 re...

Page 27: ...CROSWITCH IN NORMAL INSTALLATION THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER ALARM LIGHTS CIRCUITS ETC L1 L2 PUSHBUTTON SWITCH 120V 60HZ K1 Ka K1b CURRENT DRAW MAX 8A RESISTIVE 8A INDUCTIVE 120VAC NOTES 1 DENOTES FIELD INSTALLATION 2 DENOTES FACTORY INSTALLATION 3 GAS VALVE UL LISTED ELECTRICALLY OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND TEMPERATURE ...

Page 28: ...as shown Four typical examples shown Power to cooking equipment Shunt Trip Breaker 120 VAC N Input NO NC Electric gas valve If reset relay is used see option A or B at right Mechanical gas shut off valve does not require electrical connection NO NC NO Input NC Voltage Free Contacts for Building Alarm s Power to Fan s Fan Starter Terminal strip in Waterwash Control Panel NO NC 3 4 5 6 NO NC 120 VAC...

Page 29: ... JUNCTION BOX ON HOOD FOR HOOD LIGHTS JUNCTION BOX ON TOP OF HOOD FOR FIELD CONNECTION OF SUPPLY POWER FIVE 5 CONTROL WIRES FROM SWITCH JUNCTION BOX ON HOOD TO MAKE UP AIR CONTROL CENTER CONTROL CENTER MAKE UP AIR UNIT FIELD WIRING SUPPLY POWER TO MAKE UP AIR CONTROL CENTER TWO 2 CONTROL WIRES FROM ANSUL SNAP ACTION SWITCH TO MOTOR CONTROLS AREA ELECTRICAL CONTRACTOR TO PROVIDE HANDIBOX ON SIDE OF...

Page 30: ...OL 115VOLT N H STR FAN EXH CTRL SUP HTR SUP FAN OPTIONAL OL FSC1 LIGHT SWITCH EXHAUST SUPPLY SWITCH HEATER SWITCH LIGHT SWITCH EXHAUST SWITCH SUPPLY SWITCH HEATER SWITCH HOOD SWITCH PANEL DETAIL THE DIAGRAMS BELOW SHOW A TYPICAL HOOD SWITCH PANEL REMOTE MOUNTED FOR HOOD MOUNTED SWITCHES REFER TO THE WIRING CONNECTION DECAL ON THE COVER OF THE JUNCTION BOX ON THE HOOD TOP HOOD SWITCH PANEL DETAIL C...

Page 31: ... activated Off if both are not activated On if both are activated Off if either are not activated Off if both are activated On if either is activated On if either is activated On if both are activated Off if both are not activated Off if either not activated Single Throw Single Pole Double Pole Double Throw Double Throw Center Off Series Circuit Normally Open Contacts Parallel Circuit Normally Clo...

Page 32: ...ed cleaners or iron wool pads to clean the hood They may scratch or mar the material Always rub with the grain of the stainless 3 To maintain optimum performance of your hood and fan duct cleaning should be performed as often as the application and code requires 4 Re caulk the hoods with an NSF Approved silicone caulk GE SCS1009 or its equivalent as needed 1 Grasp the baffle with drain holes facin...

Page 33: ...h continue to push the top of the filter into the channel 3 When the filter is even with the bottom rear filter channel set the filter into the channel Fig 54 4 Slide the filter to one end of the hood and repeat until all the filters are installed Make sure the filters are placed tightly together with no visible gaps 5 Latch filters together by connecting hooks to handle on next filter Fig 55 6 In...

Page 34: ...e to wash 3 to 4 filters each day cycling all of the filters in three days Note The beads will discolor Standard cooking will turn the beads yellow in color Open flame cooking will cause the beads to blacken Neither affects the performance of the filters Periodic Inspection Each filter may be soaked in hot soapy water for two hours once a month prior to washing if grease build up is found Inspect ...

Page 35: ...eater 180º F Min Griddle Pot Pan Detergent Every 3 days 10 Minutes Every 3 days 5 minutes Fryer Weekly 10 Minutes Twice a week 5 minutes Charbroiler Daily 15 Minutes Daily 5 minutes Wok Daily 15 Minutes Daily 5 minutes 4 Power Wash Sink Whirlpool no Heater 140º F Griddle Pot Pan Detergent Every 3 days 15 Minutes Daily 5 minutes Fryer Weekly 15 Minutes Twice a week 5 minutes Charbroiler Daily 25 Mi...

Page 36: ...ve Check to see if there is a strong draft through an open door Check make up air unit increase make up air make up air should be evenly distributed throughout the kitchen Does the current cooking equipment match the original design Adjust or replace fan to match the cooking equipment load Are there multiple hoods on one fan One hood may be over exhausting and the other hood not drawing enough Res...

Page 37: ...to the air curtain heat the supply air Is the make up air part of the hood or an attached plenum Try turning off or reducing the amount of make up air heat the supply air Problem The kitchen gets hot Is the hood capturing Hood is not drawing enough air see sections above on fan performance and hood capture Is this an air curtain hood Turn off or reduce the amount of air supplied to the air curtain...

Page 38: ...6 x 2 Stainless Steel Baffle Filter 457629 16 x 20 x 2 Stainless Steel Baffle Filter 457633 20 x 16 x 2 Stainless Steel Baffle Filter 457635 20 x 20 x 2 Stainless Steel Baffle Filter 851656 16 x 16 High Velocity Cartridge Filter 851657 16 x 20 High Velocity Cartridge Filter 851659 20 x 16 High Velocity Cartridge Filter 851660 20 x 20 High Velocity Cartridge Filter 851703 16 x 16 Grease X Tractor A...

Page 39: ... 850551 Light Switch Only 851776 Fan Switch Only 851777 Light Switch Fan Switch 2 switches 851778 Fan Switch Heat Switch 2 switches 851779 Exhaust Fan Supply Switch 2 switches 851780 Light Fan Heat Switch 3 switches 851781 Light Exhaust Supply Separate Switch 3 switches 851782 Exhaust Supply Heat Separate Switch 3 switches 851783 Light Exhaust Supply Heat Separate Switch 4 switches 851784 Fan Swit...

Page 40: ...repaid Motors are warranted by the motor manufacturer for a period of one year Should motors furnished by Greenheck prove defective during this period they should be returned to the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specificat...

Reviews: