Installation Instructions

LOAD 2

LOAD 1

120/277 VAC

BLACK

RED

BLUE

RED

NEUTRAL

GROUND

GREEN

Model # VNW-P-1001-DMV-W

Model # VNW-P-1001-DMV-V

Model # VNW-P-1001-DMV-G

NeoSwitch Passive Infrared (PIR) 

Dual Relay Vacancy Sensing Wall Switch

(Ground Required)

•  Read all instructions on both sides of this  

sheet first

•  Install in accordance with ALL local codes
•  For indoor use only

Technology:

 Passive Infrared (PIR)

Electrical Ratings:

120 VAC:

•  Incandescent/Tungsten – Max. load: 6.7 amps, 

800W, 50/60 Hz

•  Fluorescent/Ballast – Max. load: 10 amps, 1200W, 

50/60 Hz

Motor Load: ¼ HP @ 125 VAC
277 VAC:

•  Fluorescent/Ballast – Max. load: 9.8 amps, 

2700W, 50/60 Hz

Ballast Compatibility:

 Compatible with magnetic and 

electronic ballasts

No Minimum Load Requirement
Time Delays:

 Self-Adjusting, 15 seconds/test (10 min 

Auto), Selectable 5, 15, 30 minutes

Coverage:

 Major motion – 1000 sq. ft.

 

Minor motion –  300 sq. ft.

Light Level Sensing:

 0 to 200 foot-candles

Operating Environment:

•  Temperature: 32° F – 104° F (0° C – 40° C)
•  Relative Humidity: 20% to 90% non-condensing

Housing:

 Durable, injection molded housing. 

Polycarbonate resin complies with UL94VO.

Size:

•  Mounting Plate/Strap Dimensions: 

4.195" H x 1.732" W (106.553 mm x 44 mm)

•  Product Housing Dimensions: 2.618" H x 1.752" 

W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)

LED Indicators:

 Red LED indicates PIR detection; Green 

LED acts as EcoMeter or night light locator.

The VNW-P-1001-DMV Vacancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control 

and conventional wall switch all-in-one, used for energy savings and convenience.

PIR Technology

The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature 

that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.

The VNW-P-1001-DMV allows the control of two separate loads with one occupancy sensor switch.  
The lights are turned ON by pressing the universally recognized light icon pushbutton. In either mode, the 

lights stay ON as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF 
automatically after a preset Time Delay interval.

The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and time 

delay in real-time. By adjusting sensitivity and time delay automatically, the sensor is maximizing the potential energy 
savings that are available in the particular application.

The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding 

individuals to take control of their lighting to maximize energy savings.

The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.
Bathroom Mode – When selected, bathroom mode keeps the second relay ON for an additional 8 minutes, after 

the first relay has been turned off. Combine this with changing the pushbutton to the light/fan graphic and you now 
have the universally recognized and easy to use bathroom solution.

Relay Swap Option – A common problem in electric wiring is wiring the wrong switch to the wrong load. This can 

make control of loads confusing to an end user. The Relay Swap option solves the problem by allowing the switch 
buttons on the face of the unit to be swapped, after the unit is wired and installed.

The VNW-P-1001-DMV is designed for offices up to 300 square feet. 

When installing the VNW-P-1001-DMV in a new junction box, choose the switch location carefully to provide optimum 

coverage of the occupied area. When replacing an existing wall switch, bear in mind that there must be a clear line-of-

sight between the sensor and the area to be covered. Avoid pointing the VNW-P-1001-DMV directly into the hallway 

where it may detect passers-by.

The VNW-P-1001-DMV can be installed in any standard single gang box. It 

may be installed in the same manner as an ordinary wall switch.

•  Wire the VNW-P-1001-DMV as described in the wiring section.
•  Mount the VNW-P-1001-DMV in the junction box.

CAUTION:  Before installing or performing any service on a Greengate system, the power MUST be turned 
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the 
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations 
should be in compliance with the National Electric Code and all state and local codes.

NOTE REGARDING COMPACT FLUORESCENT LAMPS:  The life of some compact fluorescent lamps (CFLs) is 

shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the 
effects of cycling.

1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to wall box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install wall switch plate.

EcoMeter Operation

Load 1 Load 2

EcoMeter LED

OFF

OFF

100%

ON

OFF

50%

OFF

ON

50%

ON

ON

OFF

Action   

EcoMeter

Benefit

A person enters the space and one of 

the loads is activated

50%

Increased awareness of energy savings

Both loads are ON

OFF

The area is vacated and the lights turn 

OFF automatically

100%

Increased awareness of energy savings; 

Acts as a night light locator

A person turns the lights OFF 

manually upon exiting an area

100%

Increased awareness of energy savings 

and reminds individuals to take control 

of their lighting for additional savings;  

Acts as a night light locator

If the daylighting function is activated 

for one of the two loads and there is 

sufficient daylight in the space, the unit 

will hold that load OFF

50%

Increased awareness of energy  

savings;  Lets persons know that the 

daylight sensor is holding the lights OFF;  

Acts as a night light locator

If the daylighting function is activated 

for both loads and there is sufficient 

daylight in the space, the unit will hold 

that loads OFF

100%

Increased awareness of energy  

savings;  Lets persons know that the 

daylight sensor is holding the lights OFF;  

Acts as a night light locator

Wiring Diagram 1:

  120/277 VAC dual level single circuit wiring diagram

,

36

20

,

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

8

,

Minor Motion, IR

Major Motion, IR

P/N 9850-000287-02

LOAD 2

LOAD 1

BLACK

RED

BLUE

RED

NEUTRAL (CIRCUIT 1)

NEUTRAL (CIRCUIT 2)

GROUND

CIRCUIT 1

GREEN

CIRCUIT 1 
120/277 VAC

CIRCUIT 2 
120/277 VAC

Wiring Diagram 2: 

120/277 VAC dual level dual circuit wiring diagram

Coverage  