Installation Instructions
LOAD 2
LOAD 1
120/277 VAC
BLACK
RED
BLUE
RED
NEUTRAL
GROUND
GREEN
Model # VNW-P-1001-DMV-W
Model # VNW-P-1001-DMV-V
Model # VNW-P-1001-DMV-G
NeoSwitch Passive Infrared (PIR)
Dual Relay Vacancy Sensing Wall Switch
(Ground Required)
• Read all instructions on both sides of this
sheet first
• Install in accordance with ALL local codes
• For indoor use only
Technology:
Passive Infrared (PIR)
Electrical Ratings:
120 VAC:
• Incandescent/Tungsten – Max. load: 6.7 amps,
800W, 50/60 Hz
• Fluorescent/Ballast – Max. load: 10 amps, 1200W,
50/60 Hz
Motor Load: ¼ HP @ 125 VAC
277 VAC:
• Fluorescent/Ballast – Max. load: 9.8 amps,
2700W, 50/60 Hz
Ballast Compatibility:
Compatible with magnetic and
electronic ballasts
No Minimum Load Requirement
Time Delays:
Self-Adjusting, 15 seconds/test (10 min
Auto), Selectable 5, 15, 30 minutes
Coverage:
Major motion – 1000 sq. ft.
Minor motion – 300 sq. ft.
Light Level Sensing:
0 to 200 foot-candles
Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% non-condensing
Housing:
Durable, injection molded housing.
Polycarbonate resin complies with UL94VO.
Size:
• Mounting Plate/Strap Dimensions:
4.195" H x 1.732" W (106.553 mm x 44 mm)
• Product Housing Dimensions: 2.618" H x 1.752"
W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)
LED Indicators:
Red LED indicates PIR detection; Green
LED acts as EcoMeter or night light locator.
The VNW-P-1001-DMV Vacancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control
and conventional wall switch all-in-one, used for energy savings and convenience.
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature
that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
The VNW-P-1001-DMV allows the control of two separate loads with one occupancy sensor switch.
The lights are turned ON by pressing the universally recognized light icon pushbutton. In either mode, the
lights stay ON as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF
automatically after a preset Time Delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and time
delay in real-time. By adjusting sensitivity and time delay automatically, the sensor is maximizing the potential energy
savings that are available in the particular application.
The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding
individuals to take control of their lighting to maximize energy savings.
The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.
Bathroom Mode – When selected, bathroom mode keeps the second relay ON for an additional 8 minutes, after
the first relay has been turned off. Combine this with changing the pushbutton to the light/fan graphic and you now
have the universally recognized and easy to use bathroom solution.
Relay Swap Option – A common problem in electric wiring is wiring the wrong switch to the wrong load. This can
make control of loads confusing to an end user. The Relay Swap option solves the problem by allowing the switch
buttons on the face of the unit to be swapped, after the unit is wired and installed.
The VNW-P-1001-DMV is designed for offices up to 300 square feet.
When installing the VNW-P-1001-DMV in a new junction box, choose the switch location carefully to provide optimum
coverage of the occupied area. When replacing an existing wall switch, bear in mind that there must be a clear line-of-
sight between the sensor and the area to be covered. Avoid pointing the VNW-P-1001-DMV directly into the hallway
where it may detect passers-by.
The VNW-P-1001-DMV can be installed in any standard single gang box. It
may be installed in the same manner as an ordinary wall switch.
• Wire the VNW-P-1001-DMV as described in the wiring section.
• Mount the VNW-P-1001-DMV in the junction box.
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to wall box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install wall switch plate.
EcoMeter Operation
Load 1 Load 2
EcoMeter LED
OFF
OFF
100%
ON
OFF
50%
OFF
ON
50%
ON
ON
OFF
Action
EcoMeter
Benefit
A person enters the space and one of
the loads is activated
50%
Increased awareness of energy savings
Both loads are ON
OFF
The area is vacated and the lights turn
OFF automatically
100%
Increased awareness of energy savings;
Acts as a night light locator
A person turns the lights OFF
manually upon exiting an area
100%
Increased awareness of energy savings
and reminds individuals to take control
of their lighting for additional savings;
Acts as a night light locator
If the daylighting function is activated
for one of the two loads and there is
sufficient daylight in the space, the unit
will hold that load OFF
50%
Increased awareness of energy
savings; Lets persons know that the
daylight sensor is holding the lights OFF;
Acts as a night light locator
If the daylighting function is activated
for both loads and there is sufficient
daylight in the space, the unit will hold
that loads OFF
100%
Increased awareness of energy
savings; Lets persons know that the
daylight sensor is holding the lights OFF;
Acts as a night light locator
Wiring Diagram 1:
120/277 VAC dual level single circuit wiring diagram
,
36
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
8
,
Minor Motion, IR
Major Motion, IR
P/N 9850-000287-02
LOAD 2
LOAD 1
BLACK
RED
BLUE
RED
NEUTRAL (CIRCUIT 1)
NEUTRAL (CIRCUIT 2)
GROUND
CIRCUIT 1
GREEN
CIRCUIT 1
120/277 VAC
CIRCUIT 2
120/277 VAC
Wiring Diagram 2:
120/277 VAC dual level dual circuit wiring diagram
Coverage
Description
Specifications
General Information
Location
Installation
Wiring