Greengate ONW-P-1001-SP-W Installation Instructions Download Page 1

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Installation Instructions

Model # ONW-P-1001-SP-W

Model # ONW-P-1001-SP-V

Model # ONW-P-1001-SP-LA

Model # ONW-P-1001-SP-G

Model # ONW-P-1001-SP-B

NeoSwitch Passive Infrared (PIR) Technology 

Low Voltage Occupancy Sensing Wall Switch

•  Read all instructions on both sides of this sheet first
•  Install in accordance with ALL local codes
•  For indoor use only 

 

•  For use with Greengate Switchpacks & Systems 

Only. For use with other systems, contact  
Technical Support

•  Do not run any Greengate Low Voltage wiring in the 

same conduit as power conductors

General Information  

Technology:

 Passive Infrared (PIR)

Electrical Ratings:

Input:

•  10-30VDC from Greengate Switchpack or 

Greengate System.  Maximum current needed is 
25mA per sensor.

Output:

•  Open collector ouput to switch up to ten Greengate 

Switchpacks.

•  Isolated Form C Relay
•  Isolated Form C Relay Ratings: 1A 30VDC/VAC

Time Delays:

 Self-Adjusting, 15 seconds/test (10 min 

Auto), Selectable 5, 15, 30 minutes

Coverage:

 Major motion – 1000 sq. ft.

 

Minor motion –  300 sq. ft.

Light Level Sensing:

 0 to 200 foot-candles

Operating Environment:

•  Temperature: 32° F – 104° F (0° C – 40° C)
•  Relative Humidity: 20% to 90% Non-condensing

Housing:

 Durable, injection molded housing.  

Polycarbonate resin complies with UL94VO.

Size:

•  Mounting Plate/Strap Dimensions: 

4.195" H x 1.732" W (106.553 mm x 44 mm)

•  Product Housing Dimensions: 2.618" H x 1.752" 

W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)

LED Indicators:

 Red LED indicates PIR detection;  

Green LED acts as EcoMeter or night light locator.

Specifications  

Description  

Coverage  

The ONW-P-1001-SP Occupancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control 

and conventional Wall Switch all-in-one, used for energy savings and convenience.

PIR Technology

The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature 

that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.  

The ONW-P-1001-SP allows the control of one Greengate switchpack or input to a Greengate Panel.
The sensor may be interfaced to an energy management system that accepts either a normally open or normally 

closed dry contact via the sensor’s Form C relay.

The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room.  In Manual ON Mode, the 

lights are turned ON by pressing the universally recognized light icon Pushbutton.  In either mode, the lights stay ON 
as long as the sensor detects motion in the room.  When the room is vacated, the lights turn OFF automatically after 
a preset Time Delay interval.

The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and 

Time Delay in Real-time.  By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential 
energy savings that are available in the particular application.

The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding 

individuals to take control of their lighting to maximize energy savings.

The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.  
Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy.  The 

sensor will switch the lights ON when it detects a person entering the area.  If the sensor does not continue to detect 
motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.  

Tracking Mode allows the load connected to the Form C relay to follow the state of the sensor’s blue lead.  
HVAC Mode allows the load connected to the Form C relay to remain ON when the lights are turned OFF manually.  

Applications may include keeping the room at a desired temperature while giving a presentation and the lights are OFF.

The ONW-P-1001-SP is designed for offices up to 300 square feet.  

Location  

When installing the ONW-P-1001-SP in a new junction box, choose the switch location carefully to provide 

optimum coverage of the occupied area.  When replacing an existing Wall Switch, bear in mind that there must be a 
clear Line-of-sight between the sensor and the area to be covered.  Avoid pointing the ONW-P-1001-SP directly into 
the hallway where it may detect passers-by.

EcoMeter Operation

Load 1

EcoMeter LED

OFF

ON

ON

OFF

Action   

EcoMeter

Benefit

A person enters the space and 

the load is activated

OFF

The area is vacated and the 

lights turn 

OFF

 automatically

ON

Increased awareness of energy savings;  

Acts as a night light locator

A person turns the lights 

OFF

 

manually upon exiting an area

ON

Increased awareness of energy savings and 

reminds individuals to take control of their  

lighting for additional savings;  Acts as a night 

light locator

The daylight feature prevents 

the lights from automatically  

turning ON when a person 

enters an area

ON

Increased awareness of energy savings and 

lets individual know that the daylighting 

feature is working

Wiring  

CAUTION:  Before installing or performing any service on a Greengate system, the power MUST be turned OFF 
at the branch circuit breaker.  According to NEC  240-83(d), if the branch circuit breaker is used as the main 
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.”  All installations should be 
in compliance with the National Electric Code and all state and local codes.

NOTE REGARDING COMPACT FLUORESCENT LAMPS:  The life of some compact fluorescent lamps (CFLs) is 

shortened by frequent automatic or manual switching.  Check with CFL and ballast manufacturer to determine the 
effects of cycling.

1. Make sure power is turned 

OFF

 at the branch circuit breaker.

2. Wire units as shown in wiring diagrams per applicable voltage requirements.  
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.

RED (10-30VDC)

BLUE (CONTROL)

BLACK (COMMON)

ORANGE (N.O.)

GRAY (COMMON)

PURPLE (N.C.)

RED

BLUE

BLACK

HOT

LOAD

BLUE

BLUE

HO

T

WHITE

NEUTRAL

LINE

Wiring Diagram 1

Installation  

The ONW-P-1001-SP can be installed in any standard single gang box.  

It may be installed in the same manner as an ordinary Wall Switch.

•  Wire the ONW-P-1001-SP as described in the wiring section.
•  Mount the ONW-P-1001-SP in the junction box.

,

36

20

,

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

8

,

Minor Motion, IR

Major Motion, IR

CAUTION:  If a room is wired for two circuits using two separate hot leads, it is very important to connect 
only one circuit per relay.  Both circuits must be fed from the same phase.