background image

Installation Instructions

Model # OAC-DT-2000-MV

Model # OAC-DT-2000-DMV

Dual Technology Ceiling Mounted Line

Voltage Occupancy Sensor

• Read all instructions on both sides of this sheet first
• Install in accordance with ALL local codes

• For indoor use only

Power Requirements:

120 to 347 VAC, 50/60 Hz - Neutral Required 
120 VAC:

•   Incandescent/Tungsten - 0 to 800W, 50/60 Hz
•  Fluorescent/Ballast - 0 to 1200W, 50/60 Hz

Motor Load: ¼ HP @ 125 VAC
230 VAC:
  •  Fluorescent/Ballast - 0 to 1200W, 50/60 Hz

277 VAC:
  •  Fluorescent/Ballast - 0 to 2700W, 50/60 Hz
347 VAC:
  •  Fluorescent/Ballast - 0 to 1500W, 50/60 Hz

Operating Environment:

•  Temperature: 32° F – 104° F (0° C – 40° C)
•  Relative Humidity: up to 90% non-condensing

Ultrasonic

Activated

  The OAC-DT Ceiling Mount Line Voltage Occupancy Sensor is a Passive Infrared (PIR) and Ultrasonic (US) motion 

sensing lighting control, used for energy savings and convenience. PIR is used to turn the lights ON and then either  

technology is used to keep the lights ON. 

The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and time 

delay in real-time.

  The maximum coverage area may vary somewhat according to room shape and the presence of obstacles. Decrease 

total coverage area by 15% for “soft” rooms (for example, heavy draperies or heavy carpeting). The sensor must have 

a clear view of the area to be controlled. The sensor will not “see” through glass. Mounting height should not exceed 

12 feet. Optimum mounting height is 8 to 10 feet. Mount the sensor so the grills face the open portion of the room and 

are not facing a nearby wall, door, window, or other obstructing object. Avoid pointing into hallways. Mounting at fixture 

height is most effective. *To prevent false activation, the sensor should be mounted away from the air supply duct a 

minimum of 4 to 6 feet.

  The OAC-DT sensor can be mounted to a standard 2.125” deep x 4” octagon or 2.125” deep x 4” foursquare 
electrical boxes (foursquare box requires a two-gang mud ring).

CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at 

the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch 

for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in com-

pliance with the National Electric Code and all state and local codes.  

 

NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened 

by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.

1.  Make sure power is turned OFF at the branch circuit breaker.

2.  Wire units as shown in wiring diagrams per applicable voltage requirements. (Use twist-on wire connectors 

  for all connections) CAP ALL UNUSED WIRE LEADS. 

3.  Mount unit to ceiling, junction box, or round fixture with raceway.

4.  Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.

5.  Make necessary adjustments. (See Checkout and Adjustments section)

Minor Motion, Ultrasonic

Major Motion, Ultrasonic

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

The NEMA WD 7 Guide and robotic

method were utilized to verify

coverage patterns.

Minor Motion, IR

Major Motion, IR

0

23 ft

(7.01 m)

5 ft

(1.52 m)

0

5 ft

(1.52 m)

32 ft

(9.75 m)

32 ft

(9.75 m)

12 ft

(3.65 m)

16 ft

(4.87 m)

15 ft

(4.57 m)

23 ft

(7.01 m)

15 ft

(4.57 m)

8.5 ft

(2.59 m)

0

12 ft

(3.65 m)

16 ft

(4.87 m)

20 ft

(6.096m)

20 ft

(6.096m)

10 ft

(3 m)

10 ft

(3 m)

3 ft

(0.91)

OAC-DT-2000-MV/DMV Coverage Diagram

Load 1

Neutral

120-347 VAC

Line

White 

Blue 

Black 

One Sensor, One Load

30 ft

9.14 m

30 ft

9.14 m

OAC-DT-2000

P/N 9850-000186-01

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Load 1

Neutral

120-347 VAC

Line

Blue   

White 

Black 

Red   
Red    

Load 2

Red leads are non-polorarity sensitive. 

One Sensor, Two Loads

Installation

Location

General Information

Specifications

Description

Coverage

Wiring

Reviews: