Gree XE76-33/H Owner'S Manual Download Page 1

Owner's Manual 

Original Instructions 

Wired Controller (XK86 and XE76-33/H)

Summary of Contents for XE76-33/H

Page 1: ...Owner s Manual Original Instructions Wired Controller XK86 and XE76 33 H...

Page 2: ...the appliance by a person responsibility for their safety Children should be supervised to ensure that they do not play with the appliance 2 This instruction manual is a universal manual some functio...

Page 3: ...ric Appliances Inc of Zhuhai This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health f...

Page 4: ...Instructions 5 5 Installation and Commissioning 7 5 1 Installation of Wired Controller 11 5 2 Commissioning 20 6 Operation Instructions 30 6 1 On Off 30 6 2 Mode Setting 31 6 3 Temperature Setting 33...

Page 5: ...ld Function 52 6 12 Gate control Function 53 6 13 Inquiry of Indoor Temperature with One Button 53 7 Error Display 53 7 1 Table of Error Codes for Outdoor Unit 54 7 2 Table of Error Codes for Indoor U...

Page 6: ...y cause severe damage or death to people This sign indicates that the items must be observed Improper operation may cause damage to people or property WARNING This product can t be installed at corros...

Page 7: ...indoor unit can be set to any mode including auto mode while the slave indoor unit can t set to the mode that conflicts with the system mode When the system mode priority is Cooling mode is prioritize...

Page 8: ...stem mode priorities When two wired controllers control one or more indoor unit s the address of wired controller should be different Functions with are optional for indoor units If a function is not...

Page 9: ...Wired Controller XK86 and XE76 33 H 4 3 Appearance and Display Fig 3 1 Appearance and display...

Page 10: ...the names of buttons 6 Temperature display Display set temperature or environment temperature 7 Fan speed display Indicating set fan speed 8 Status bar Indicating date time and activated functions 4...

Page 11: ...eld Shield status Gate control Indicating the gate control card is pulled out Child lock Child lock status Invalid Indicating invalid operation Malfunction Indicating that the unit is malfunctioning M...

Page 12: ...Wired Controller XK86 and XE76 33 H 7 5 Installation and Commissioning 1 Dimension and parts of XE76 33 H Unit mm Fig 5 1 Dimension of XE76 33 H...

Page 13: ...ontroller XK86 and XE76 33 H 8 Fig 5 2 Parts of XE76 33 H No Name Panel of wired controller Screw M4 25 Soleplate of wired controller Junction box mounted in the wall space QTY 1 2 1 Parts supplied by...

Page 14: ...Wired Controller XK86 and XE76 33 H 9 2 Dimension and parts of XK86 Unit mm Fig 5 3 Dimension of XK86...

Page 15: ...Controller XK86 and XE76 33 H 10 Fig 5 4 Parts of XK86 No Name Panel of wired controller Screw M4 25 Soleplate of wired controller Junction box mounted in the wall space QTY 1 2 2 Parts supplied by u...

Page 16: ...feet Wire size mm2 A WG Material standard Remarks Light Ordinary polyvinyl chloride sheathed cord 60227 IEC 52 60227 IEC 53 L 250m L 820 1 5feet 2 0 75 2 1 25 2 AWG 18 2 A WG16 IEC 60227 5 2007 Total...

Page 17: ...g to this instruction manual strictly 5 1 2 Installation Requirements 1 Prohibit installing the wired controller at wet places 2 Prohibit installing the wired controller at direct sunshine places 3 Pr...

Page 18: ...XE76 33 H 13 5 1 3 Wiring Requirements There are four network wiring methods between wired controller and indoor unit Fig 5 6 One wired controller controls one indoor unit Fig 5 7 Two wired controller...

Page 19: ...Wired Controller XK86 and XE76 33 H 14 Fig 5 8 One wired controller controls multiple indoor units simultaneously Fig 5 9 Two wired controllers control multiple indoor units simultaneously...

Page 20: ...rent One should be master controller and the other should be slave controller Please refer to section 5 2 2 Parameter Setting for the setting method 3 When two wired controllers control multiple indoo...

Page 21: ...connection method shown in fig 5 7 and 5 9 there should be only one master wired controller address is 01 and one slave wired controller address 02 The quantity of wired controller can t exceed two NO...

Page 22: ...Wired Controller XK86 and XE76 33 H 17 5 1 4 Installation Fig 5 10 Installation diagram of XE76 33 H...

Page 23: ...Please pay attention to the following items 1 Before installation please cut off the power for indoor unit 2 Pull out the 2 core twisted pair from the installation hole on wall and pull this wire thro...

Page 24: ...to H1 and H2 wiring column and then fix the screws 5 Bundle the front panel of wired controller to its soleplate and the installation is completed 5 1 5 Disassembly Fig 5 12 Disassembly diagram of XE...

Page 25: ...on on homepage to enter the menu page Then select View to enter the interface of view Then select Project View to enter the interface of project view as shown below 1 IDU project No view and locating...

Page 26: ...ne indoor unit error codes will be displayed circularly at an interval of 3 seconds If there is no error Null will be displayed After entering the interface of IDU project number view and locating buz...

Page 27: ...r to large number at an interval of 3 seconds After turning on View All IDU Project No you can enter the interface of View All IDU Project No to turn this function off or you can press On Off button o...

Page 28: ...re are multiple indoor units press IDU or IDU to switch different indoor units Parameters of the corresponding unit will be shown as below When enquiring outdoor unit parameters if there are multiple...

Page 29: ...1 2 Number of IDUs 1 16 Master IDU s Project No 1 255 Time Left to Clean Filter 0 416 days Online IDUs of CAN1 1 100 CAN2 Address 1 255 Max Distribution Ratio 110 135 150 Cool Heat Modes Cool only He...

Page 30: ...de 0 9 A Z a z Outdoor Temp 30 139 Comp1 Operation Freq 0 200Hz Comp2 Operation Freq 0 200Hz ODU Fan Operation Freq 0 100Hz Module High Pressure 40 70 Module low pressure 69 38 Comp1 Discharge Temp 30...

Page 31: ...ting Unit parameters can be set in unit On or Off status Press Menu button on homepage to enter the menu page Then select Set to enter the interface of settings Then select Project set to enter the in...

Page 32: ...yed on homepage Slave wired controller cannot set any parameter except switching to be a master wired controller Master IDU ON OFF OFF After turning on this setting the current indoor unit will be a m...

Page 33: ...ure unit is Celsius Clear Filter Cleaning Time Clear Don t Clear Don t Clear Reset WiFi Reset Don t reset Don t reset Only applicable to the unit connected to G Cloud IDU Fan Static Pressure 1 9 5 Num...

Page 34: ...to temperature humidity dual control duct type indoor unit Resume After Inserting Card Yes No Yes When it is set as No it will keep the status after inserting the gate control card that is if it is O...

Page 35: ...word Under the status of parameter setting signals from remote controller are ineffective 6 Operation Instructions 6 1 On Off Press On Off button on homepage to turn on the air conditioner Press On Of...

Page 36: ...homepage can switch modes circularly in the following order Auto Cool Dry Fan Heat Floor Heat 3D Heat Space Heat Auto If wired controller is connected to temperature humidity dual control duct type in...

Page 37: ...his unit can switch to any mode if multiple indoor units have been turned on system mode will be the mode of the unit that is first turned on and other units cannot switch to a mode that is in conflic...

Page 38: ...d by 1 in every 0 3 second After setting the temperature press button to return to homepage Under the mode of Cool Dry Reheat Fan Heat Floor Heat 3D Heat and Space Heat temperature setting range is 16...

Page 39: ...er the interface of temperature setting and set the temperature and relative humidity at the same time If wired controller is connected to fresh air indoor unit homepage will not display set temperatu...

Page 40: ...If auto fan speed is set indoor unit will change fan speed automatically according to indoor ambient temperature 6 5 Schedule Setting Wired controller has two types of schedule setting general schedul...

Page 41: ...der ON status you can set General schedule to turn unit off Under OFF status you can set General schedule to turn unit on On the interface of schedule setting select General Schedule to enter the sett...

Page 42: ...lect Schedule 1 or Schedule 2 or Schedule 3 to enter the setting of periodical schedule See below take Schedule 1 as an example To ensure time accuracy please check the current system date and time be...

Page 43: ...ed that unit is going to perform when it is turned on through schedule If you want to just turn unit on through schedule set the time for unit ON If you want to just turn unit off through schedule set...

Page 44: ...Repeat to enter the following interface where you can set the days for schedule to be effective Press or button to switch to a different selection Press OK button to confirm or cancel the correspondin...

Page 45: ...ion setting as shown below Press or button to to switch among different items Press OK button to turn on or off the corresponding function showing on the left means the corresponding function is ON wh...

Page 46: ...alid Invalid functions are displayed in grey Press or button will skip the invalid function After Child lock function is ON wired controller will be back to the homepage and buttons will be invalid Un...

Page 47: ...y upon startup Rapid function can be enabled only in Cool mode or Heat mode Absence This is used to maintain indoor temperature so that unit can perform heating quickly upon startup Absence function c...

Page 48: ...g of up and down swing position as shown below Press or button to switch to a different selection When selecting the first item press or to select ON or OFF When selecting the icon of air swing press...

Page 49: ...ct ON or OFF When selecting the icon of air swing press or to switch to a different swing angle The icon of air swing will be displayed in the following order Press OK to save the setting and return t...

Page 50: ...select ON or OFF When selecting the second item press or to switch between Quiet and Auto Quiet Press OK to save the setting and return to the previous page NOTES When Quiet mode is ON indoor unit wi...

Page 51: ...ON or OFF When selecting the second item press or to switch to a different air degree The range of air level is 1 10 Press OK to save the setting and return to the previous page NOTES Air function is...

Page 52: ...time of fresh air valve 60 6 60 12 60 18 60 24 60 30 60 36 60 42 60 48 60 54 Open all the time NOTE Above time indicates unit operating time min fresh air valve opening time min 6 6 4 Setting of Save...

Page 53: ...the upper or lower limit of temperature Press OK to save the setting and return to the previous page If Save function is ON under Cool mode Dry mode or Dry Reheat mode set temperature displayed on ho...

Page 54: ...ter cleaning reminding function as shown below Press or button to switch to a different selection When selecting the first item press or to select ON or OFF When selecting the second item press or to...

Page 55: ...rs Every increase of 1 indicates an increase of 400 hours in running time When clean cycle is 9 the accumulative running time is 5000 hours 4 Severe pollution Cleaning degree of current environment is...

Page 56: ...mber will only be displayed after an aftersales Tel is set Select Set First or phone number then press OK to enter the next page to set up the phone number After the phone number is set select Clear t...

Page 57: ...ion Remote Shield Function Remote monitor or central controller can disable the relevant functions of wired controller so as to realize the function of remote control Remote Shield Function includes a...

Page 58: ...rol display and gate control function it has to be used with wired controller that includes gate control signal detecting function used as master and salve wired controller 6 13 Inquiry of Indoor Temp...

Page 59: ...on of Low High pressure E4 Excess Discharge Temperature Protection of Compressor JE Oil Return Pipe is Blocked Ed Low Temperature Protection of Driver Module JF Oil Return Pipe is Leaking F0 Bad Perfo...

Page 60: ...r FA Compressor 6 Discharge Temperature Sensor Error bA Oil return Temperature Sensor Error FC Compressor 2 Current Sensor Error bH System Clock Malfunction FL Compressor 3 Current Sensor Error bE Mal...

Page 61: ...2 Over current Protection P2 Protection of Compressor Drive Board Power Supply J3 Compressor 3 Over current Protection P3 Protection of Compressor Drive Board Module Reset J4 Compressor 4 Over current...

Page 62: ...L7 No Master Indoor Unit Error y3 Middle Tube Temperature Sensor 2 Error L8 Power Insufficiency Protection y7 Fresh Air Inflow Temperature Sensor Error L9 Quantity Of Group Control Indoor Units Setti...

Page 63: ...ection d3 Ambient Temperature Sensor Error o4 IDU Startup Failure d4 Inlet Pipe Temperature Sensor Error o5 IDU Overcurrent Protection d5 Malfunction of Middle Tube Temperature Sensor o6 IDU Current D...

Page 64: ...ror between master control and inverter compressor drive U5 Wrong Address of Compressor Drive Board C3 Communication error between master control and inverter fan motor drive U6 Valve Abnormal Alarm C...

Page 65: ...protection CP Error of Multiple Master Wired Controller UP Protection shutdown error of thermal storage module CU Communication Error between Indoor Unit and Remote Receiver UU Electronic expansion v...

Page 66: ...w temperature protection revision value b A5 Online Testing q9 Setting of defrosting mode A8 Vacuum pumping Mode qL Setting of static pressure A9 Operate in Setback Function qE EVI Operating Mode AH H...

Page 67: ......