Multi Variable Air Conditioners Ducted Type Indoor Unit
6
(1)
Use copper wire only as unit’s power cord. Operating temperature should be within its rated value.
(2) If the power cord is more than 15m (49-1/4 ft.) long, please increase properly the sectional area of power
cord to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at 40° (104°F)
Ambient temperature when laying across plastic pipe. Air switch is D type and used at 40°C (104°F). If
actual installation condition varies, please lower the capacity appropriately according to the specifications
of power cord and air switch provided by manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off device should be
3mm (1/8 in.) (The same for both indoor unit and outdoor unit).
4 Installation Instructions
Note!
This series duct type unit is only for one room.
4.1 Installation of Indoor Unit
4.1.1 Outline Dimension and Installation Spots
Equip with an inspection hatch after lifting the unit. For the convenience of maintenance, the
service port should be on one side of the electric box and below unit’s lower level.
Below are the outline dimension applicable to indoor units of GMV-ND07PLS/A-T (U) ~
GMV-ND22PLS/A-T (U).
Fig 4.1.1