Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
49
PART 6 PIPE INSTALLATION AND INSULATION
1 PIPE INSTALLATION FOR THE COOLING SYSTEM
1.1 Precautions on Pipe Direction Design
Refrigerant pipe layout must be designed in accordance with the following principles:
(1) The air conditioning installation should not damage the bearing structure or the decorative style.
Air conditioning pipes should be laid out along the bottom of beam as possible. If pipes meet one
another at the same elevation, process based on the following principles:
Drain pipes enjoy the highest priority. Air ducts and pressure pipes should leave places for gravity
pipes.
Air ducts and small pipes should leave places for major pipes.
(2) The refrigerant pipe layout must be optimal in actual engineering with minimum pipe length and
bends. In this way, the performance of the unit can be maximized.
(3) The refrigerant pipe cannot affect air discharge and return of internal units. The minimum
distance between the refrigerant pipe with an insulation layer and the air return box is 300 mm (11.8inch).
If the air return or manhole is at the right lower part of the unit, the minimum distance is 150 mm
(5.9inch). When the refrigerant pipe needs to be laid at the air outlet side, avoid laying the pipe at the
front of the air outlet. The refrigerant pipe cannot connect to any part of the unit except the joint points. If
the preceding principles are not followed, performance of the unit will be affected and running noises will
be increased.
(4) The refrigerant pipe must be laid away from the manhole of the unit so that sufficient space can
be reserved for maintenance.
(5) The riser should be installed in the air conditioning tube well, and the horizontal pipe should be
placed in the ceiling, if possible.
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...