Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial UNIT INTRODUCTION
15
Model
NCHS1B(U)
NCHS2B(U)
NCHS4B(U)
NCHS8B(U)
Max. IDU Branches
/
1
2
4
8
No. of connectable IDU of each
branch
/
8
8
8
8
Total Connectable IDU
/
8
16
32
64
Max. Capacity of each branch
kW
14
14
14
14
KBtu/h
48.0
48.0
48.0
48.0
Max. Capacity of connectable IDU
kW
14
28
45
68
KBtu/h
48.0
96.0
153
232
Power supply
V/Ph/Hz
208/230V 1Ph 60Hz
Power consumption
W
8
20
32
80
Outdoor Unit Piping
Connection
Liquid
mm
9.52
9.52
12.7
15.9
In.
3/8
3/8
1/2
5/8
Gas(Low
pressure)
mm
22.2
22.2
28.6
28.6
In.
7/8
7/8
1 1/8
1 1/8
Gas(High
pressure)
mm
15.9
19.05
19.05
22.2
In.
5/8
3/4
3/4
7/8
Indoor Unit Piping
Connection
Liquid
mm
9.52
9.52
9.52
9.52
In.
3/8
3/8
3/8
3/8
Gas
mm
15.9
15.9
15.9
15.9
In.
5/8
5/8
5/8
5/8
3.3 Combination Mode
Single Model
GMV-VQ192WM/A-F(U)
Combined Model
GMV-VQ96W/A-F(U)+GMV-VQ96W/A-F(U)
No matter how many outdoor units there are,the total rated capacity of indoor units must not exceed
135% of the total rated capacity of outdoor units. Stable and safe operation can only be guaranteed in a
range of 50%~135%.
4 ELECTRICAL PARAMETERS
4.1 Power Cable Wire Gauge and Circuit Breaker Selection of ODU
Outdoor units
Power Supply
Fuse Capacity
MCA
MOP
V/ Ph /Hz
A
A
A
GMV-VQ72W/A-F(U)
208V/230V 3~ 60Hz
50
40
50
GMV-VQ96W/A-F(U)
208V/230V 3~ 60Hz
60
45
60
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...