8
Technical Information
Service Manual
Heating operation ambient temperature range is -22°C~24°C
-12 -9
-6
-3
-1
Cooling
Heating
32 33 34 35 36 37 38 39
43
–15
–10
–5
40 41 42
100
105
95
90
85
80
75
70
65
60
55
50
110
100
90
80
70
60
50
40
0
5
7
10
Conditions
Indoor:DB27°C/WB19°C
Indoor air flow:Super High
Pipe length: 5m
Conditions
Indoor:DB20°C/WB15°C
Indoor air flow:Super High
Pipe length: 5m
Outdoor temp.(°C)
Outdoor temp.(°C)
Capacity ratio (%
)
Capacity ratio (%
)
50
60
70
80
90
100
110
Capacity ratio(%)
Condition
Indoor air flow: Super High
Pipe length:
5m
Outdoor temp. (°C)
0
20
-22
40
60
80
100
120
Capacity ratio(%
)
Condition
Indoor air flow: Super High
Pipe length:
5m
Outdoor temp. (°C)
Indoor:DB 20°C
Indoor:DB 27°C
WB19
°C
10
7
2
5
43
-15
-5
7
19
31
Cooling:
Heating:
2.4 Cooling and Heating Data Sheet in Rated Frequency
Cooling:
Rated cooling
condition(°C) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
revolution
(rps)
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
27/19
35/24
09K
0.8 ~ 1.1
12 to 15
65 to 38
TURBO
High
49
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5m.
Heating:
Rated cooling
condition(°C) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
revolution
(rps)
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
20/-
7/6
09K
2.8 ~ 3.2
35 to 63
2 to 5
TURBO
High
59