Gree GMV6 HR DC Inverter VRF Units Service Manual
412
Appendix 4 Electric Specifications
Every unit should have corresponding short-circuit and overload protection. And also a main switch
is required to control power supply or disconnection.
Please refer to the following table for outdoor unit power cord specifications and circuit breakers
Model
Combination
method
Power supply
Capacity of
circuit breaker
of each
combination
module (A)
Minimum
cross-sectional
area of grounding
wire (mm
2
)
Recommended wire
(cross-sectional area)
(mm
2
)
GMV-VQ224WM/C-X
-
380-415V 3N~
50/60Hz
25
2.5
2.5×5
GMV-VQ280WM/C-X
-
380-415V 3N~
50/60Hz
25
2.5
2.5×5
GMV-VQ335WM/C-X
-
380-415V 3N~
50/60Hz
25
4.0
4.0×5
GMV-VQ400WM/C-X
-
380-415V 3N~
50/60Hz
40
6.0
6.0×5
GMV-VQ450WM/C-X
-
380-415V 3N~
50/60Hz
40
6.0
6.0×5
GMV-VQ504WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ560WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ615WM/C-X
-
380-415V 3N~
50/60Hz
50
10.0
10.0×5
GMV-VQ680WM/C-X
280+400
380-415V 3N~
50/60Hz
25+40
2.5+6.0
2.5×5+6.0×5
GMV-VQ730WM/C-X
280+450
380-415V 3N~
50/60Hz
25+40
2.5+6.0
2.5×5+6.0×5
GMV-VQ784WM/C-X
280+504
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ840WM/C-X
280+560
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ895WM/C-X
280+615
380-415V 3N~
50/60Hz
25+50
2.5+10.0
2.5×5+10.0×5
GMV-VQ950WM/C-X
335+615
380-415V 3N~
50/60Hz
25+50
4.0+10.0
4.0×5+10.0×5
GMV-VQ1015WM/C-
X
400+615
380-415V 3N~
50/60Hz
40+50
6.0+10.0
6.0×5+10.0×5
GMV-VQ1065WM/C-
X
450+615
380-415V 3N~
50/60Hz
40+50
6.0+10.0
6.0×5+10.0×5
GMV-VQ1119WM/C-
X
504+615
380-415V 3N~
50/60Hz
50+50
10.0+10.0
10.0×5+10.0×5
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...