Gree GMV6 HR DC Inverter VRF Units Service Manual
401
Appendixes
Appendix 1 Temperature Senor Resistance and Temperature
Relationship Table
Environmental temperature sensor
15kΩ resistance ~ voltage correspondence table (including
outdoor and indoor environment temperature sensors)
Temperature
(°C)
Resistance
(kΩ)
Voltage (V)
Temperature
(°C)
Resistance
(kΩ)
Voltage (V)
-20
144
0.311
71
2.523
2.825
-19
138.1
0.323
72
2.439
2.838
-18
128.6
0.345
73
2.358
2.852
-17
121.6
0.362
74
2.28
2.865
-16
115
0.381
75
2.205
2.877
-15
108.7
0.4
76
2.133
2.889
-14
102.9
0.42
77
2.064
2.901
-13
97.4
0.44
78
1.997
2.912
-12
92.22
0.462
79
1.933
2.923
-11
87.35
0.484
80
1.871
2.934
-10
82.75
0.506
81
1.811
2.945
-9
78.43
0.53
82
1.754
2.955
-8
74.35
0.554
83
1.699
2.964
-7
70.5
0.579
84
1.645
2.974
-6
66.88
0.605
85
1.594
2.983
-5
63.46
0.631
86
1.544
2.992
-4
60.23
0.658
87
1.497
3.001
-3
57.18
0.686
88
1.451
3.009
-2
54.31
0.714
89
1.408
3.017
-1
51.59
0.743
90
1.363
3.025
0
49.02
0.773
91
1.322
3.033
1
46.8
0.801
92
1.282
3.04
2
44.31
0.835
93
1.244
3.047
3
42.14
0.866
94
1.207
3.054
4
40.09
0.899
95
1.171
3.061
5
38.15
0.931
96
1.136
3.068
6
36.32
0.965
97
1.103
3.074
7
34.58
0.998
98
1.071
3.08
8
32.94
1.033
99
1.039
3.086
9
31.38
1.067
100
1.009
3.092
10
29.9
1.102
101
0.98
3.098
11
28.51
1.138
102
0.952
3.103
12
27.18
1.174
103
0.925
3.108
13
25.92
1.21
104
0.898
3.114
14
24.73
1.246
105
0.873
3.119
15
23.6
1.282
106
0.848
3.123
16
22.53
1.319
107
0.825
3.128
17
21.51
1.356
108
0.802
3.133
Summary of Contents for GMVVQ1015WM/C-X
Page 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Page 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Page 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Page 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Page 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Page 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Page 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Page 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Page 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Page 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Page 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Page 433: ...JF00304244...