Multi VRF Floor Standing Indoor Unit 

1 Safety Precautions 

Means items that must be forbidden! Otherwise, it may lead to personal injury or death or serious damage. 

Means items that must be followed! Otherwise, it may lead to personal injury or property loss. 

Follow this instruction to   

complete the installation   

work. Please carefull read 

this manual before unit   

startup and service. 

Installation should be conducted by 

dealer    or qualified   

personnel. Please do not attempt   

to install the unit by   

yourself. Improper handling may   

result in waterleakage, electric   

shock or fire disaster etc. 

Before installation,please 

check if the power supply 

is in accordance with the   

requirements specified on 

the nameplate.And also   

take care of the power   

safety. 

Make sure the unit can be earthed 

properly and soundly after   

plugging into the socket so as to   

avoid electric shock. Please do not 

connect the ground wire to gas   

pipe, water pipe, lightning rod or   

telephoneline.   

Be sure to use the   

exclusive accessory and 

part to prevent the water 

leakage, electric shock   

and fire accidents. 

If refrigerant leakage happens   

during installation, please   

ventilate immediately. Poisonous 

gas will emerge if the   

refrigerant gas meets fire. 

Wire size of power cord   

should be large enough. 

The damaged power cord 

and connection wire   

should be replaced by   

exclusive cable. 

After connecting the power cord,   

please fix the electric box cover   

properly in order to avoid accident. 

Never fail to comply with 

the nitrigen charge   

requirements.Charge   

nitrogen when welding   

pipes. 

Never short-circiut or cancel   

the pressure switch to prevent 

unit damage.   

Please firstly connect the 

wired controller before   

energization,otherwise   

wired controller can not be 

used. 

Before using the unit, please 

check if the piping and wiring 

are correct to avoid water   

leakage,refrigerant leakage,   

electric shock, or fire etc. 

Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.

Summary of Contents for GMV-ND100L/A-T

Page 1: ...eproducts es or sent email to info greeproducts es for electronic version GREE reserves the right to interpret this manual which will be subject to any change due to product improvement without furthe...

Page 2: ...to prevent units from being damaged or operating normally because of improper disassembly please do not disassemble the unit by yourself If you need to disassemble and check units please contact our...

Page 3: ...oard 9 5 2 Power Cord Connection 9 5 3 Connection of Communication Line of IDU and ODU 9 5 4 Connection of Communication Line of Wired Controller 10 5 5 Illuminate for Connection of Wired Controller a...

Page 4: ...water pipe lightning rod or telephoneline Be sure to use the exclusive accessory and part to prevent the water leakage electric shock and fire accidents If refrigerant leakage happens during installa...

Page 5: ...time halting to protect the compressor Volatile liquid such as diluent or gas will damage the unit appearance Only use soft cloth with a little neutral detergent to clean the outer casing of unit Unde...

Page 6: ...pipe Front panel Wrapping tape Remote control box 2 2 Rated Operating Condition Item Indoor Condition Outdoor Condition DBTemperature C WBTemperature C DBTemperature C WBTemperature C Rated Cooling 27...

Page 7: ...the inconvenience of the business contact It should be guided under the professional personnel when the air conditioner unit is moved to other place 3 2 Requirements for Communication Line Note If th...

Page 8: ...elded wire 3 2 2 Select communication line for indoor unit and indoor unit outdoor unit Fig 3 2 2 Material Type Total Length L m feet of Communication Cable between Indoor Unit and Indoor Outdoor Unit...

Page 9: ...0V 60HZ 6 1 0 AWG18 1 0 AWG18 4 Installation Instructions 4 1 Installation of Indoor Unit Fig 4 1 Unit mm Item Model W H D GMV ND100L A T GMV ND140L A T 580 1870 400 4 2 Debugging Setting of master in...

Page 10: ...being damaged when passing through the hole 4 4 Installation of the drainage pipe 1 Make sure drainage pipe is led outdoors discharge side 2 Butt joint drainage pipe in the unit with blowing drainage...

Page 11: ...work incorrect wiring could cause malfunction or even damage the unit The unit should be powered by independent circuit and specific socket The wiring should be in accordance with related regulations...

Page 12: ...pping and cutting tool Loosen the wiring screws on terminal board Insert the wire into the ring tongue terminal and tighten by crimping tool Use the screwdriver for tightening the terminal Fig 5 1 1 F...

Page 13: ...ed to H1 H2 3 One indoor unit can only connect to one wired controller 4 One wired controller can only conntect to one floor standing indoor unit Notes The display of floor standing type unit correspo...

Page 14: ...for display panel 2 Under power on or power off status press Light button to turn on and turn off the light of display panel 3 When the light of display panel is turned off press the other buttons ot...

Page 15: ...ng the time press ON OFF button or without pressing any buttons for consecutive 5 seconds the setting time is confirmed and quit the function setting status After quiting the function setting status t...

Page 16: ...e air conditioner operate in a smaller temperature range thus save energy Turn on cooling energy saving with the unit is started up under cooling or dry mode press Function button to switch to energy...

Page 17: ...r being de energized that is after de energizing and energizing the unit the unit will resume to be the status before it is de energized if 88 LED displays oF it means it will not memorized the on and...

Page 18: ...ectly for long time and making indoor temperature too low for it is bad for health 5 Do not pour water to unit or clean it by water otherwise a malfunction or electric shock may happen 6 Do not mangle...

Page 19: ...dry the filter and reinstall it as shown in Fig 7 2 Note Do not dry the filter by exposing it under direct sunshine or near a heating oven or it may get deformed Fig 7 2 8 3 Check before the usage se...

Page 20: ...personnel Check the following items before contacting the service center as it could save your time and cost Malfunction Phenomena Malfunction Analyzing The air conditioner could not start up just aft...

Page 21: ...the voltages of batteries in the wireless remote controller are sufficient Otherwise change the batteries 10 1 Service center When the following phenomena appeared please stop operating immediately cu...

Page 22: ...tacto con su agente local visite www greeproducts es o env enos un mensaje de correo electr nico a info greeproducts es para que le enviemos la versi n electr nica GREE se reserva el derecho de interp...

Page 23: ...amente y ha sido aprobada antes de su salida de f brica Para evitar da os en la unidad por desmontaje inadecuado as como para garantizar su buen funcionamiento no la desmonte por s mismo Si necesita d...

Page 24: ...2 Conexi n del cable de alimentaci n 9 5 3 Conexi n de la l nea de comunicaci n de la UI y UE 9 5 4 Conexi n de la l nea de comunicaci n del controlador por cable 10 5 5 Instrucciones de conexi n del...

Page 25: ...ios exclusivos Aseg rese de emplear los accesorios y piezas exclusi vos para evitar fugas de agua electrocuci n e incendios Si se produce una fuga de refrigerante durante la instalaci n ventile inmedi...

Page 26: ...ra proteger el compresor Los l quidos vol tiles como disolventes o gasolinas pue den deteriorar el aspecto de la unidad Emplee un pa o sua ve con un poco de detergente neutro para limpiar la carcasa e...

Page 27: ...renaje Panel delantero Cinta adhesiva Caja de mando a distancia 2 2 Condiciones de funcionamiento nominales Condiciones interiores Condiciones exteriores Temperatura DB C Temperatura WB C Temperatura...

Page 28: ...rior maestra puede establecer el modo autom tico En modo autom tico si la unidad interior est refrigerando los iconos y se iluminar n si la unidad est en modo de calefacci n los iconos y se encender n...

Page 29: ...ica que la funci n X FAN Ventilaci n X se encuentra activada si el icono est apagado significa que la funci n X FAN Ventilaci n X est desactivada 4 Ajustes de la funci n de programador Funci n de prog...

Page 30: ...cuando el bot n comience a parpadear pulse los botones o para activar o cancelar la funci n de sue o Si el ico no est encendido significa que la funci n de sue o se encuentra activada si el icono est...

Page 31: ...refrigeraci n nC para la unidad de calefacci n nH y para la unidad con oscilaci n nF 3 Ajuste de la funci n de memoria en caso de fallo de potencia Con la unidad apagada pulse a la vez los botones Mod...

Page 32: ...os o disminuir la eficiencia de la unidad 4 Evite que el aire refrigerado incida directamente en su cuerpo durante periodos prolongados as como ajustar una temperatura interior demasiado baja es malo...

Page 33: ...elo del modo indicado en la fig 7 2 Nota No seque el filtro exponi ndolo a la radiaci n solar directa o junto a un horno podr a deformarse Fig 7 2 8 3 Comprobaciones previas a la temporada de uso 1 Co...

Page 34: ...tura de aire de salida 10 An lisis de problemas Advertencia No repare el aire acondicionado por s mismo una reparaci n incorrecta podr a producir descargas el ctricas o incendios P ngase en contacto c...

Page 35: ...rrumpiendo y reanudando el suminis tro el ctrico del mando inal mbrico Se encuentra el mando dentro del rea de recepci n Hay alg n obst culo Compruebe si las pilas del mando a distancia inal mbrico pr...

Page 36: ...tilisateur veuillez contacter votre agent local visiter www greeproducts es ou envoyer un e mail info greeproducts es pour obtenir la version lectronique GREE se r serve le doit d apporter des modific...

Page 37: ...vant son d part de l usine Afin d viter des dommages ou des dysfonctionnements des unit s dus un d montage in correct vitez de d monter l unit vous m me Si vous devez d monter et inspecter des unit s...

Page 38: ...ion 10 5 3 Connexion de la ligne de communication de l UI et l UE 10 5 4 Connexion de la ligne de communication de la commande filaire 10 5 5 Connexion de la commande filaire au r seau d unit s int ri...

Page 39: ...les risques d incendie En cas de fuite de r frig rant pendant l installation a rez im m diatement Un gaz toxique se forme lorsque le gaz r frig rant entre en contact avec le feu exclusif La section d...

Page 40: ...endommager l aspect de l unit Utilisez uniquement un chiffon doux avec un peu de d tergent neutre pour nettoyer le bo tier ext rieur de l unit En mode climatisation ne r glez pas la temp rature de la...

Page 41: ...yau d vacuation Panneau frontal Ruban d emballage Bo tier de t l commande 2 2 Conditions nominales de travail Conditions int rieures Conditions ext rieures Temp rature DB C Temp rature WB C Temp ratur...

Page 42: ...que le service apr s vente agr de Gree fera l objet d un d lai de traitement plus long Le d m nagement du climatiseur doit tre supervis par un technicien professionnel 3 2 Exigences de la ligne de co...

Page 43: ...ommunication entre une unit int rieure et une unit int rieure unit ext rieure Unit int rieure 1 Unit int rieure 2 Unit int rieure n Unit ext rieure 1 Unit ext rieure 2 Unit ext rieure 3 Unit ext rieur...

Page 44: ...50 Hz 208 V 230 V 60 Hz 6 1 0 AWG18 1 0 AWG18 4 Instructions de pose 4 1 Pose de l unit int rieure Fig 4 1 Unit mm l ment Mod le W H D GMV ND100L A T GMV ND140L A T 580 1870 400 4 2 D pannage Le r gla...

Page 45: ...d vacuation est dirig vers l ext rieur c t d chargement 2 Joindre bout bout le tuyau d vacuation dans l unit avec le tuyau d vacuation de souf flage et les fixer avec du ruban isolant 3 Si le tuyau d...

Page 46: ...iagramme lectrique avant de proc der aux travaux de c blage un c blage erron pourrait causer des dysfonctionnements ou endommager l unit L unit doit tre mise sous tension par un circuit ind pendant et...

Page 47: ...Fig 5 1 1 Fig 5 1 2 5 2 Connexion du c ble d alimentation Remarque Toutes les unit s int rieures doivent tre raccord es l alimentation afin de pouvoir tre mise sous tension arr t es au m me moment al...

Page 48: ...ilaire au r seau d unit s int rieures 1 Le c ble de communication de l unit int rieure et de l unit ext rieure ou unit int rieure est connect D1 D2 2 La commande filaire est connect e H1 H2 3 Une unit...

Page 49: ...glage de la fonction luminosit 1 La fonction Light ON OFF permet d activer et d sactiver l clairage du panneau lumineux 2 L unit en marche ou l arr t appuyer sur la touche Light pour activer ou d sac...

Page 50: ...arr t du climatiseur R glage du temporisateur appuyer sur la touche Fonction pour passer la fonction temporisateur Lorsque l ic ne clignote appuyer sur les touches ou pour ajuster l heure de r glage...

Page 51: ...t oscillation 7 R glage de la fonction conomie d nergie Fonction d conomie d nergie peremet de r gler la limite inf rieure de temp rature des modes climatisation et d shumidification et la temp rature...

Page 52: ...n cas de d faut d alimentation L unit l arr t appuyer simultan ment sur les touches Mode et pendant 5 secondes pour passer la m thode de m moire si l cran LED affiche ON cela signifie que l unit m mo...

Page 53: ...ur la climatisation 3 Lorsque le climatiseur fonctionne ne laissez pas les fen tres ouvertes dans le cas contraire l efficacit de l unit sera r duite 4 Ne laissez pas le flux d air froid dirig vers vo...

Page 54: ...uer l g rement le filtre ou nettoyer le filtre l aide d un appareil de nettoyage lectrique Si le filtre pr sente trop de poussi re le nettoyer avec un peu de d tergent neutre ou de l eau chaude Ensuit...

Page 55: ...yage de filtre db Code sp cial Code d bogage projet dL Erreur capteur temp rature air sortie 10 Analyse des dysfonctionnements Avertissement Ne r parez pas le climatiseur vous m me car une r paration...

Page 56: ...mment alors la t l commande ne travaille pas cor rectement Il est alors possible de r tablir le fonctionnement normal en coupant l alimentation et en remettant sous tension la t l commande La commande...

Reviews: