background image

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

3.4 Wiring Requirements 

Power Cord Size and Air Switch Capacity 

Model 

Power Supply 

MCA(A) 

MOP(A) 

GMV-ND07TD/A-T(U) 

208/230V-1ph-60Hz 

0.375 

15 

GMV-ND09TD/A-T(U) 

0.375 

15 

GMV-ND12TD/A-T(U) 

0.375 

15 

 

 

(1)  An all-pole disconnection switch having a contact separation of at least 3mm(1/8 inch) in all 

poles should be connected in fixed wiring. 

(2)  The circuit breaker and power cord specification in above sheet is based on max 

power(max current) of the unit. 

(3)  The power cord specification in above sheet is based on ambient temperature of 40

(104

). 

(4)  The circuit breaker specification in above sheet is based on ambient temperature of 40

(104

). If the working condition is different, please adjust it according to the specification 

sheet of circuit breaker. 

4 Installation Instructions 

4.1 Installation of Indoor Unit 

4.1.1 Ceiling Opening Dimension and Suspension Bolt Position. 

Unit: mm(inch) 

 

Fig.4.1.1 

4.1.2 Suspend the Indoor Unit 

(1)  Drill bolt holes and install bolts 

1)  Stick the reference cardboard on the installation position; drill 4 holes according to 

the hole  site on the  cardboard as shown in Fig.4.1.2;  diameter of drilling hole is 

according to the diameter of expansion bolt and the depth is 60-70mm (2-3/8~2-3/4 

inch), as shown in Fig.4.1.3. 

 

 

Summary of Contents for GMV-ND07TD/A-T

Page 1: ...Owner s Manual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners One way Cassette Type Indoor Unit Models GMV ND07TD A T U GMV ND09TD A T U GMV ND12TD A T U...

Page 2: ...ld well keep this manual 6 If this unit fails to operate normally please contact our service center as soon as possible and provide the following information 1 Content on the nameplate model number co...

Page 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 4: ...Drainage System Testing 9 4 4 Panel Installation 12 4 5 Installation of Wired Controller 13 5 Wiring Work 14 5 1 Connection of Wire and Patch Board Terminal 14 5 2 Power Cord Connection 15 5 3 Connec...

Page 5: ...en charging welding process Do charge nitrogen when welding the pipes 11 Never short circuit or cancel the pressure switch to prevent unit damage 12 As for the unit controlled by the wired controller...

Page 6: ...er for help Any personal injury or property loss caused by improper installation improper debug unnecessary repair or not following the instructions of this manual should not be the responsibility of...

Page 7: ...e remote controller 14 Tapping screw 2 Used for fixing the remote controller holder 3 2 Installation Position Selection 1 The appliance shall not be installed in the laundry 2 The location should be a...

Page 8: ...gulations 2 Only qualified personnel can carry out installation work please contact with local dealer before installation 3 Make sure all the installation work completed before energizing 3 3 Requirem...

Page 9: ...eld or strong interference it is necessary to use shielded wire 3 3 2 Selection of Communication Wire between Indoor Unit and Indoor Unit or Outdoor Unit Fig 3 3 2 Material Type Total Length L m ft of...

Page 10: ...ove sheet is based on ambient temperature of 40 104 4 The circuit breaker specification in above sheet is based on ambient temperature of 40 104 If the working condition is different please adjust it...

Page 11: ...er and lower sides of the hanger bracket The washer fixing plate will prevent the washer from falling 3 The usage of paper pattern Refer to paper pattern of installation for ceiling opening dimension...

Page 12: ...nd then tighten the flaring nut with hand as shown in Fig 4 2 1 2 Tighten the flaring nut with torque wrench Fig 4 2 1 Pipe diameter mm inch Torque N m 6 35 1 4 15 30 9 52 3 8 35 40 12 7 1 2 45 50 15...

Page 13: ...to the drainage pipe Improper installation may lead to water leakage and damp the furniture and other things in the room 7 You can buy normal hard PVC pipe used as the drainage pipe During connection...

Page 14: ...ation height of raising pipe for drainage should be lower than B The gradient from raising pipe towards drainage direction should be at least 1 2 If the raising pipe is vetical with the unit the raisi...

Page 15: ...e g water pump etc 2 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check the draining through the drain socket...

Page 16: ...roper decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the...

Page 17: ...les and then install the corresponding screw cover 4 Close the horizon lover connect the butt terminal and arrange the wires 5 After tightening screws reinstall the air inlet grille Fig 4 4 4 4 5 Inst...

Page 18: ...e communication wires should be separated from power cord and connection wire between indoor unit 8 Adjust the static pressure via wired controller according to site circumstance 5 1 Connection of Wir...

Page 19: ...it can t operate normally Fig 5 2 1 1 Detach the electric box lid 2 Let the power cord pass through the wiring through holes 3 Connect wires according to Fig 5 2 1 4 Fix the power cord with wiring cla...

Page 20: ...1 Open electric box cover of indoor unit 2 Let the communication wire go through the rubber ring 3 Connect the communication wire to terminal H1 and H2 of indoor 4 bit wiring board 4 Fix the communica...

Page 21: ...s that must be set as master one and slave one 4 One wired controller can control 16 indoor unitS in maximum at the same time as shown in Fig 5 5 1 1 The type of indoor units must be the same if they...

Page 22: ...Multi Variable Air Conditioners One way Cassette Type Indoor Unit 18 Fig 5 5 1...

Page 23: ...outlet of indoor and outdoor unit are blocked 2 Check if securely grounded 3 Check if all the power cord and communication cable are securely connected 4 Check if any error code displayed after energ...

Page 24: ...y leakage of electricity Input voltage is too low Defect of main PC board The unit stops after running for a while The inlet or outlet of ODU or IDU are blocked by obstacle Poor cooling effect The fil...

Page 25: ......

Reviews: