GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
62
Stop valve equipped
to the outdoor unit
for the gas pipe
Stop valve equipped
to the outdoor unit for
the liquid pipe
Gas pipe filter
Added stop valve
for the gas pipe
Drier filter for the liquid pipe
Added stop valve
for the liquid pipe
II. Pipe Installation for the Condensate Water
System
1. Pipes
Generally, U-PVC water supply pipes bonded with special glue are adopted as condensate water
pipes. PP-R, PP-C, and hot galvanized steel pipes can also be adopted. Aluminium plastic compound
pipes cannot be used.
2. Requirements on Installation
2.1 Determine the direction and elevation of a condensate water pipe before installing it. Avoid
overlapping it with other pipes to ensure straight inclination. The clamp of the pipe hanger is fixed
outside the insulation layer. The height of the clamp can be adjusted.
2.2 Distance between Hangers
External Diameter of
the Pipe (mm)
Φ≤25
32>Φ≥25
Φ≥32
Distance between
Horizontal Pipes (mm)
800
1000
1500
Distance between
Vertical Pipes (mm)
1500
2000
There are at least two hangers for each vertical pipe.
2.3 The inclination degree of the condensate water pipe must be above 1% and that of the main pipe
cannot be lower than 0.3%. Adverse slopes are not allowed.
2.4 When connecting three-way pipes, the two-way straight pipes must be laid on the same slope, as
shown in the following figures.
2.5 The condensate water pipe cannot be tied with the refrigerant pipe.
2.6 A ventilation hole must be provided on the top of the drain pipe to ensure smoother discharge of
condensate water.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...