GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
23
III. Cooperation Between Different
Professions
A quality installation of air conditioning engineering depends on careful organization and close
cooperation between different professions such as architecture, structure, electric, water supply and
drainage, fire-fighting, and decoration. Pipes must be laid in places away from any automatic spray head
for fire-fighting, and must be reasonably arranged to ensure that the pipes fit the electric, luminaries, and
decoration.
1. Requirements for cooperation with civil engineering:
The riser should be installed in the air conditioning tube well, and the horizontal pipe should be
placed in the ceiling, if possible.
A place should be reserved for the ODU base to prevent the waterproof layer or insulating layer on
the roof from being damaged in later phase of installation.
At places on walls or floors where pipes need to go through, holes or casing should be preserved. If
the pipe needs to go through a bearing beam, a steel casing must be prepared.
2. Requirements for cooperation with decoration engineering:
The air conditioning installation should not damage the bearing structure or the decorative style. Air
conditioning pipes should be laid out along the bottom of the beam as possible. If pipes meet one
another at the same elevation, process based on the following principles:
Drain pipes enjoy the highest priority. Air ducts and pressure pipes should leave places for gravity
pipes.
Air ducts and small pipes should leave places for major pipes.
3. Requirements for cooperation with electric:
After the capacity of air conditioning unit is determined, check the following aspects with relevant
electric design personnel:
Whether the electrical load is designed based on the requirement of the air conditioning unit;
Whether the power cable and circuit breaker meet the unit requirement and abide by relevant
national safety regulations;
Whether the regional power supply quality (including voltage fluctuation and interference noise)
meet the international requirement.
Any nonconformity must be resolved through coordination.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...