SPLIT TYPE
10. Thermostat
Installation of the thermostat is very similar to that of the remote air temperature sensor.
17
18
19
20
21
22
Thermostat
XT5
XT5
XT6
HEAT
N
COOL
COOL
24V GN
D
L(220V AC)
24V AC
OF
F
HEAT
OF
F
23
24
33
34
Thermostat
How to Wire Thermostat
(1)
Uncover the front cover of indoor unit and open the control box;
(2)
Identify the power specification of the thermostat, if it is 230V, find terminal block XT5 as NO.22~24 and
block XT6 as NO.33~34;Otherwise, if it is 24V, find terminal block XT5 as NO.17~21;
(3)
If it is the heating/cooling thermostat, please connect wire as per the figure above.
Installation Examples
Setpoint range
10~30
℃
, By means of a large
setpoint dial
Mounting
Directly onto the wall or wall-box (mounting screws
supplied)
Supply voltage
230V, 50/60Hz
Wiring
Up to 9 screw-in terminals per unit, capable of
accepting wires up to 1.5mm
2
.
Thermostat switch
S.P. D.T.
Enclosure
Plastic 2-piece housing
Performance
Typical differential 1
℃ (
heating
& cooling) at 20 at 50% load with
anticipator connected
Dimensions
Protection class
85*130*40mm(W*H*D)
IP30
Electric ratings
4(2)A, 230V, Typical loads
are fans, zone valves, relays,
compressors. Compressors of
greater than 0.5kW capacity
should be switched via a
contactor.
Environmental
requirements
Operating temperature range 0 to 40
℃
. S
Operational life
Greater than 100000 cycles (all
loads) for thermostat contacts
at 230V; greater than 6000
operations for all manually
operated swtiches
Approvals
The XE70 range is CE, RoHs and WEEE
compliant. For regulatory information, DoC/CoC
D0045 is available on request. Product must be
wired as shown for CE compliance.