32
GMC-I Messtechnik GmbH
tdEF – Dwell Time Independent of Memory Location
Functions
•
Default dwell time:
– For all voltage-current value pairs included in a sequence to
whose memory locations
no special dwell time has been assigned
(tSEt = 00.00)
– For all status signals generated for these memory locations
•
tdEF
is used primarily to speed up programming if the value for
a certain dwell time is used repeatedly within a given
SEQUENCE
.
Setting Range
0.01 s to 99.99 s, maximum resolution: 0.01 s
Settings
(see sequence settings and execution on page 35)
☞
Do not enter
tdEF
until all
Uset
,
Iset
and
tset
values have been
assigned to all necessary memory locations!
☞
Procedure
for selecting
tdEF (
see also chapter 4.7, “Settings”
):
!
The
tdEF
display appears in the window for the
SEq
function,
along with a related numeric parameter [s].
Figure 4.7.3 e
Path to tdEF Settings
☞
Set resolution, i.e. the decimal place (cursor position) of the
numeric parameter by repeatedly pressing the
<SELECT>
key.
☞
Enter dwell time based on the previously entered resolution
value using the <
> key or the <
> key.
☞
After selecting the value, jump to the next or the previous
sequence function by pressing the
<FUNCTION>
key, or by
simultaneously pressing the
<FUNCTION>
key and the
<
> key
or the <
> key.
!
The last selected and displayed value for the numeric dwell
time parameter is used as a default setting.
Strt – Sequence Start Address
Functions
•
The beginning of a range within which memory locations or
content will be deleted or added
•
The
SEQUENCE
is always
defined by means of a start address and a
stop address.
•
The address of the memory location from which the
SEQUENCE
will start
•
The start address
can correspond to
any memory location from 11
to 255
.
•
The
start address
is selected immediately
before initially starting
a new
SEQUENCE
.
•
The
last selected start
address is always valid for any given
sequence
, regardless of the point in time at which the
sequence
is started.
•
The start address for a
sequence change
can be selected
independent of the stop address.
!
The contents of the memory location with the
Strt
address are
executed as the first function.
Setting Parameter
11
Lowest possible memory location
Strt
address
255
Highest possible memory location
Strt
address
Settings
(see sequence settings and execution on page 35)
☞
Procedure
for selecting
Strt, (
“Settings”
):
!
The
Strt
display appears in the window for the
SEq
function,
along with a related numeric parameter.
Figure 4.7.3 f
Path to Start Address Selection
☞
Select the desired memory location with the <
> or the <
>
key.
☞
After selecting the value, jump to the next or the previous
sequence function by pressing the
<FUNCTION>
key, or by
simultaneously pressing the
<FUNCTION>
key and the
<
> key
or the <
> key.
!
The last selected and displayed value for the
Strt
address is
used as a default setting.
Select the text parameter
from an options loop
From the SEq function group
*
ENTER
CE/LOCAL
FUNCTION
SELECT
Cursor position
Resolution of
numeric parameter
Possible selections for the
memory location start address
From the SEq function group
Select the
start address
FUNCTION
+
Summary of Contents for SSP 120 Series