Gossen Metrawatt GmbH
MAVOWATT 210
38
Attention!
!
Use only probes that are rated 600 V CAT III or higher.
Note!
Do not locate the probe coupling close to other conductors carrying high
current.
Note!
Be sure to connect the current probes with the arrow pointing towards
the load or an erroneous power reading will result.
The instrument is powered off.
1. Open the probe coupling and slip the measuring head over the conductor
carrying the current to be measured.
2. Position the probe in such a way that
– the arrow marking on the current probe points in the direction of current
flow and towards the load,
– the conductor is centered within the measuring head,
– the measuring head forms a perfect circle.
3. Close the probe coupling such that it visibly and audibly snaps into place.
4. Select the applicable current probe settings in the
Survey Setup
of the
instrument’s web server
22.
8.3
Measurement
MAVOWATT 210 can monitor the following power configurations:
– Single Phase
– Split Phase
– 3 Phase, Four Wire Wye
– 3 Phase, Three Wire Delta (2 or 3 probe)