Appendix: Practical Information on Testing Charging Points
Type II Plug for Mode 3 Charging
Source: Mennekes
Resistance Coding for Charging Cables
Table B.101
–
Resistor Codings for Plugs
Current capacity of the cable assembly
Nominal resistance of Rc
Tolerance
±
3%
3
Recommended
interpretation range
by the EVSE
13 A
1.5 k
Ω
0.5 W
1, 2
> 1 k
Ω
- 2.7 k
Ω
20 A
680
Ω
0.5 W
1, 2
330
Ω
-1 k
Ω
32 A
220
Ω
0.5 W
1, 2
150
Ω
-330
Ω
63 A (3-phase) /
70 A (1-phase)
100
Ω
0.5 W
1, 2
75
Ω
-150
Ω
Interrupt power supply
< 75
Ω
1
The power dissipation of the resistor caused by the detection circuit shall not exceed the value given above.
The value of the pull-up resistor shall be chosen accordingly.
2
Upon circuit failure mode, resistors used should preferably fail such that the resistance value rises.
Metal film resistors commonly show acceptable properties for this application
3
Tolerances to be maintained over the full useful life and under environmental conditions as specified by the
manufacturer.
Source: IEC 61851