64
6.13.1 Floor Curing
Default setting is disabled.
Enabled
– Floor curing function is ON.
Disabled
– Normal operation of the Heat pump.
It is a fully automatic function. During the duration of this function DHW mode will be
automatically disabled.
The duration of the function depends on the ambient temperatures and moisture in the
screed. Minimum duration is 30 days.
There are to main cycles of the function, which are divided in 24 steps
– see graph below.
After the function is finished, the Heat pump returns to normal operation.
6.13.2 Floor Curing Current Stage
No setting, only display
Shows the correct working stage of the Floor curing function.
6.13.3 Floor Curing Current Stage Running Duration
No setting, only display
Shows the running duration of the correct working stage, meaning how long is the total
running time of this stage.
6.13.4 Floor Curing Current Stage Set Temperature
No setting, only display.
Shows the set temperature of the correct working stage.
6.13.5 Floor Curing Current Stage Valid Running Duration
No setting, only display.
Shows the correct working stage running time in the desired water temperature.
6.13.6 Floor Current Total Running Duration
No setting, only display.
Total running time of the Function.
6.13.7 Highest Water Temp. in Floor Curing Operation
No setting, only display
Highest reached water temperature during Floor curing operation.
<
DAY
>
W
at
er
T
em
pe
ra
tu
re
°C
Summary of Contents for Aerogor ECO COMPACT INVERTER 10A
Page 2: ......
Page 88: ...81 10 WIRING 10 1INDOOR UNIT ALL INVERTERS REFERS TO AS LINE OF HEAT PUMPS...
Page 89: ...82 INDOOR UNIT ALL INVERTERS...
Page 91: ...84 10 3OUTDOOR PCB ECO INVERTER...
Page 92: ...85 OUTDOOR PCB ECO INVERTER...
Page 93: ...86 10 4DRIVE FOR EEV ECO INVERTER 13A and ECO COMPACT INVERTER 13A...
Page 94: ...87 10 5OUTDOOR UNIT POWER EVI INVERTER 15A 18A...
Page 95: ...88 OUTDOOR UNIT POWER EVI INVERTER 15A 18A...
Page 96: ...89 10 6OUTDOOR UNIT DRIVE AEROGOR POWER EVI 15A 18A...