background image

Menu Options

LED Display

Menu Description

gtF

Gas Heat Airflow Trim (default = 0%)

HdI

Maximum Compressor Run Time Between Defrost Cycles (default 

= 120 minutes)

HFd

Heat Pump Heating Airflow Off Delay Time (default = 60 seconds)

Hnd

Heat Pump Heating Airflow On Delay Time (default = 5 seconds)

HP

Select the range that includes the desired compressor RPS for 

inverter heating operation. See inverter manual for menu options

H

Maximum Compressor RPS for Heating Mode (inverter only)

Ht

Reset all heat pump heating settings to factory default. 

Ht

Percentage of high stage heat pump heating airflow to run during 

low stage operation. (default = 70%)

HtF

Heat Pump Indoor Airflow Trim (default = 0%)

HtH

High Heating Airflow Trim for Inverter Units. See inverter manual for 

menu options and defaults

HtI

Intermediate Heating Airflow Trim for Inverter Units. See inverter 

manual for menu options and defaults

HtL

Low Heating Airflow Trim for Inverter Units. See inverter manual for 

menu options and defaults

LF

View 6 most recent fault codes and clear all fault codes if desired. 

(furnace)

Ln

Restart communications between the indoor and outdoor unit.

D

Select the number of stages for the non-communicating outdoor 

unit. Default = OFF meaning no outdoor unit.

PPd

Enable Pump Down Mode

Fd

Resets furnace settings to factory defaults.

Ct

Maximum Current Option (system will limit capacity to percentage 

of maximum current) (default = 100%)



Control Shared Data Revision Number

t

Resets all outdoor unit settings to factory defaults.

t

System Verification Test (inverters only)

tn

Indoor Airflow for non-communicating outdoor units. (values based 

on 400CFM per ton) (default = 3.0 Ton)

t

Select Outdoor Unit Elevation (SL=same level, OL = outdoor lower, 

IL = indoor lower) Default = Outdoor Lower

CF

1 = system will try to satisfy the thermostat quickly.  

5 (default) = system will try to satisfy the thermostat more slowly.

tgt

Menu is enabled if the 

CF

 menu is set to 6. Select the target time 

the system will attempt to satisfy the thermostat.

UP

Menu is enabled if the 

CF

 menu is set to 6. Select the percentage 

past the target time when the system will transition to gas furnace 

operation during heat mode.  

tt

Menu is enabled if the 

CF

 is set to 6. (the gas furnace will run 

during the next heat call if the heat pump fails to satisfy the 

custom target time for this number of consecutive cycles) (default 

= 20 cycles)

Utt

Menu is enabled if the 

CF

 menu is set to 6. (if low stage gas heat 

is able to consecutively satisfy the thermostat under the set target 

time for this number of cycles, the system will transition to the 

heat pump for primary heating)

dP

Menu is enabled if the 

CF

 menu is set to 6. (this percentage will 

help determine when switching back to heat pump operation is 

appropriate. Default = 20%. If target time = 20 minutes, low stage 

furnace operation must satisfy the thermostat by less than 16 

minutes. (target time - 20% default = 16 minutes).

LED 

Display

Menu Description 

A

Aux (condensate switch enabled) 

t

Enable or disable inverter boost operation. (compressor speed may 

increase when this feature is on) (inverter only) 

tt

Boost mode will operate above this selected temperature. On = boost 

mode always on (default = 105°F) (inverter only) 

CAP

Cooling Airflow Profile setting (default = profile D shown as 4) 

CP

Heat Pump compressor lockout temperature. Furnace will act as 

primary heat source below this temperature. (Default = 45°F) 

CdL

Compressor off delay at the beginning and end of a defrost cycle. 

(default = 30 seconds) 

CFd

Cooling Airflow Off Delay Time. (default = 60 seconds) 

CL

Resets all cooling settings to a factory default 

Cnd

Cooling Airflow On Delay Time (default = 5 seconds) 

C

Control Firmware Revision Number 

C

Enable or disable inverter charge mode

CP

Select the range that includes the desired compressor RPS for inverter 

cooling operation. See inverter manual for menu options

C

Maximum Compressor RPS for cooling mode (inverter only) 

Ct

Percentage of high stage cooling airflow to run during low stage 

operation (default = 70%) 

CtF

Cooling Airflow Trim (default 0%) 

CtH

High Cooling Airflow Trim for inverter units. See inverter manual for menu 

options and defaults 

Ct1

Intermediate Cooling Airflow Trim for inverter units. See inverter manual 

for menu options and defaults 

CtL

Low Cooling Airflow Trim for inverter units. See inverter manual for menu 

options and defaults 

dF

Compressor run time between defrost cycles. (default = 30 minutes) (2 

stage units) 

dH

Enables or disables dehumidification feature in the outdoor unit (default 

= Enabled) 

dHL

Select "1" to enable dehumidification when the thermostat DH terminal 

is energized. Select "0" to enable dehumidification when the thermostat 

DH terminal is de-energized (default = 1) 

FCL

View 6 most recent fault codes and Clear Fault Codes if desired (outdoor 

communicating units) 

FdF

Force system into a defrost cycle (inverter units) 

Fd

Constant Fan Speed as percent of maximum airflow (Default = 25%) 

Fd

Gas Heat Fan Off Delay (default = 90 seconds) 

nd

Gas Heat Fan On Delay (default = 30 seconds) 

t

Percentage of high stage gas heating airflow to run during low stage gas 

heat operation (default = 70%) 

gH

Gas Heat

TROUBLESHOOTING

32

Summary of Contents for AMVS960603BU AA

Page 1: ...serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools parts testing instruments and the appropriat...

Page 2: ...arts testing in struments and the appropriate service manual REVIEWALL SERVICEINFORMATIONINTHEAPPROPRIATESERVICE MANUAL BEFORE BEGINNING REPAIRS OUTSIDE THE U S call 1 713 861 2500 Not a technical ass...

Page 3: ...El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cualquier mo...

Page 4: ...ENTIFICATION 4 NOMENCLATURE The model and manufacturing number are used for positive identification of component parts used in manufacturing Please use these numbers when requesting service or parts i...

Page 5: ...s Steel tubular heat exchanger 115 volt silicon nitride igniter Left or right gas entry Line voltage EAC terminal GMVS96 U GMVS960603BU AA GMVS960805CU AA Goodman Brand 96 Ultra Low NOx Gas Furnace 1...

Page 6: ...the U S A this furnace can be used in the following non industrial commercial applications Schools Office buildings Churches Retail stores Nursing homes Hotels motels Common or office areas In all app...

Page 7: ...T IN PROPERTY DAMAGE EQUIPMENT DAMAGE PERSONAL INJURY OR DEATH Condensate Drain Lines and Drain Trap Acondensing gas furnace achieves its high level of efficiency by extracting almost all of the heat...

Page 8: ...ply pressures must be maintained within the ranges specified below The supply pressure must be constant and available with all other household gas fired appliances operating The minimum gas supply pre...

Page 9: ...l altitudes the air temperature rise must be within the range listed on the the Specification Sheet applicable to your model for the fuel used Manifold pressure adjustments and combustion analysis are...

Page 10: ...all after the power is turned on will run the outdoor unit at full capacity until the call is removed Use this mode for charging If system is running low stage cooling just cycle power and provide a c...

Page 11: ...arget Runtime the temporary heat pump hold will be completely removed and the heat pump will become the primary heat source again if it fails to do so the strike count against the furnace will be rese...

Page 12: ...mps up to full cooling demand airflow by first stepping up to 50 of the full demand for 30 seconds The motor then ramps to 100 of the required airflow A one 1 minute OFF delay at 100 of the cooling ai...

Page 13: ...D ehum Optional Optional Optional if feature supported by thermostat L1 L2 INDOOR BOARD TERMINAL CONNECTIONS OUTDOOR BOARD TERMINAL CONNECTIONS OUTDOOR TRANSFORMER 24V AC 240V GROUNDRECOMMENDED FIELDP...

Page 14: ...Refer to the low voltage wiring diagrams for additional wiring details Dehumidistat close on humidity rise R C G Y D ehum Dehumidistat close on humidity rise Figure 41 Fossil Fuel Applications This f...

Page 15: ...105 C All line voltage wire splices must be made inside the furnace junction box Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install desig...

Page 16: ...sfully been completed the user will have access to system information once in range Option 2 Remove the furnace door ensure the control has power and then read the 3 digits The code will temporarily r...

Page 17: ...scroll through Menus L6F Lm Cr Sr and rFd 4 Press and release the Center Button The center button is used to enter menus and make selections within menus 5 What will be displayed is the currently sele...

Page 18: ...d increments Gas Heat Trim Factor Option Menu Gas Heat airflow may be trimmed from 10 to 10 in 2 increments Gas Heat Stage Multiplier Menu CFM This menu allows adjustment of the low fire CFM multiplie...

Page 19: ...or otherwise trap condensate Use longest radius fittings possible If using 3 venting make the transition from 2 to 3 as close as practically possible Make sure there is no flue gas recirculation into...

Page 20: ...are for vertical or horizontal termination of the combustion air inlet and the exhaust vent pipes on Category IV gas fired condensing furnaces The DCVK 30 kit can be used for 3 diameter pipe systems...

Page 21: ...DRAFT AND CIRCULATION BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check motor windin...

Page 22: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Page 23: ...t As the external static pressure goes up the temperature rise will also increase Consult the proper tables for tempera ture rise limitation BTU HR Calculation Example The unit being tested takes 40 s...

Page 24: ...SERVICING 24 GAS VALVE BURNER ASSEMBLY PRESSURE TRANSDUCER INTEGRATED CONTROL BOARD CONTROL TRANSFORMER PRESSURE SWITCHES VENT PIPE CONNECTION COMBUSTION AIR CONNECTION DRAFT INDUCER Component I D...

Page 25: ...wires must be replaced replace with AWM 105 C 2 64 thick insulation of the same gauge or its equivalent CHECKING THERMOSTAT WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower co...

Page 26: ...motor reinstall blower compartment door 6 Turn on electrical power and verify proper unit operation DISCONNECT ALL POWER BEFORE SERVICING WARNING CHECKING DUCT STATIC The maximum and minimum allowabl...

Page 27: ...erature rise Decrease blower speed to increase temperature rise Refer to Circulator Blower Speed section in the Product Design section of this manual for speed changing details Temperature rise is rel...

Page 28: ...uced draft blower This voltage to the IBD will vary between furnace models and is dependent on what percentage of maximum fire is being called for The power wires are colored red white and black A gre...

Page 29: ...e etc and or consult with local gas utility WARNING HIGH VOLTAGE DISCONNECT ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT...

Page 30: ...E PERSONAL INJURY OR DEATH 6 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 7 Turn on electrical power and verify proper unit operation...

Page 31: ...ition control No voltage Check transformer room thermostat and wiring If you have 24 volts coming off the transformer but receive approximately 13 volts on the terminal board between C and R check for...

Page 32: ...utively satisfy the thermostat under the set target time for this number of cycles the system will transition to the heat pump for primary heating dP Menu is enabled if the CF menu is set to 6 this pe...

Page 33: ...ge non communicating units AC Compressor Cooling Single Stage single stage non comm units AC1 Compressor Cooling Low Stage communicating units AC2 Compressor Cooling High Stage communicating units dHU...

Page 34: ...a set is correct for the specific model re populate data using correct memory card if required Furnace operates at reduced performance Airflow delivered is less than expected Circulator blower motor i...

Page 35: ...r Furnace fails to operate 1 Analog Pressure Error Blocked Vent Error Need to check the APS Sensor or its connection if this error is occurred The failure conditions occur as per the following for 5 s...

Page 36: ...essure switch circuit is closed at start of heating cycle Low stage pressure switch contacts sticking Short in pressure switch circuit wiring Replace low stage pressure switch Repair short in wiring I...

Page 37: ...erify and correct unit ground wiring if needed Check igniter output from control replace if necessary Furnace fails to operate on high stage furnace operates normally on low stage Induced draft blower...

Page 38: ...ch condensate switch open Check evaporator drain pan trap piping Fault Code Recall Accessing the furnace s diagnostic menu provides access to the last six faults detected by the furnace Faults are sto...

Page 39: ...ED CONTROL PK C USE COPPER CONDUCTORS ONLY AT LEAST 105 IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLA...

Page 40: ...contact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN B...