SYSTEM OPERATION

11

temporary heat pump lockout and run the heat pump 

again.

There are four adjustable items associated with Dual Fuel 

control. In the same way as the System Target Time, each 

of these items have defaulted values for Comfort Settings 

1 – 5.  Only when Comfort Setting 6 is selected will each 

item be available for full adjustment.

1)  Stage Up Percent (7 segment menu SUP):  This 

is a value that determines how far past the target 

runtime the system should continue running the 

heat pump before transitioning to the furnace. For 

example, assume this menu was set to 20% with 

a target runtime of 20 minutes.  If the thermostat 

did not remove the heating call after 20 minutes, 

the  system  would  allow  for  an  additional  20% 

heat pump run (20% of the 20 minute target is an 

additional 4 minutes).  In this case, the system 

would transition to gas heat after 24 minutes if 

the thermostat call was still present.  Each time 

this occurs, the system records this as a strike 

against the heat pump (the strike is important 

when looking at the Over Target Threshold)

2)  Over Target Threshold (7 segment menu Ott): If 

the heat pump has consecutively transitioned to 

gas heat for the selected Over Target Threshold 

amount  of  times,  meaning  for  this  many 

consecutive cycles it has been unable to satisfy 

the target time by itself,  then the heat pump will 

be temporarily locked out and the furnace will 

become the primary heat source.

3)  Stage Down Percent (7 segment menu SdP): This 

only applies when the heat pump is in a temporary 

lockout condition.  In this case, the system will 

be trying to determine when the best time is to 

remove the lockout and run the heat pump again.  

To determine the best time to remove the heat 

pump lockout the system looks at how easily the 

furnace is able to satisfy the thermostat using 

Low Stage Gas Heat Only.  Assume this setting 

is 15% and the target time is 20 minutes.  If Low 

Stage Gas Heat can satisfy the thermostat in less 

than 17 minutes (20 minutes - 15% = 17 minutes) 

then the algorithm records a strike against the 

gas furnace. (this strike is important when looking 

at the Under Target Threshold).

4)  Under Target Threshold (7 segment menu Utt):  

If the furnace is able to satisfy the thermostat 

using Low Stage Gas Heat Only for the selected 

number  of  consecutive  cycles  the  heat  pump 

lockout will be temporarily removed.  The heat 

pump will then be used 

during the next cycle. If 

the heat pump can satisfy the thermostat in less 

than the System Target Runtime the temporary 

heat pump hold will be completely removed and 

the heat pump will become the primary heat 

source again. if it fails to do so, the strike count 

against the furnace will be reset and the furnace 

will remain the temporary primary heat source 

until the Under Target Threshold is reached again.

The system will automatically make adjustments in an attempt 

to satisfy the thermostat as close to this target runtime as 

possible.  After a power cycle or mode change (cooling to 

heating or heating to cooling) the system will run full capacity 

for the selected mode during the first thermostat call.  Based 

on the selected target runtime and how long the initial cycle 

takes to satisfy the thermostat, the control algorithm will adjust 

the system stage times for a 2 stage unit or the capacity 

demand percentage for an inverter / modulating unit for the 

next cycle.  Note: actual runtimes may change depending on 
variations of load throughout the day.

The following table shows the default values for all 

Comfort Setting Options (1 – 5)

Comfort

Setting

Option

Target

Time

(Minutes)

Stage Up

Percentage

(%)

Stage Down

Percentage

(%)

Over Target

Threshhold

(Strike Count)

Under Target

Threshhold

(Strike Count)

1

10

20

20

2

10

2

15

20

20

4

8

3

20

20

20

6

6

4

25

20

20

8

4

5

30

20

20

10

2

The following table shows the ranges for each of item 

when the adjustable Comfort Setting Option 6 is selected.  

The table shows the minimum value, the maximum value 

and the defaulted value.  All items can be adjusted up or 

down by increments of 1 which provides full flexibility 

for all items.  Note: it is critical that these numbers be 

set properly.  If Comfort Setting option 3 is desired but 

a target time of 60 is preferred, select Comfort Setting 

Option 6 to enable all the adjustable menus, set the Target 

Time to 60 and make sure the other menus are set to 

match that of Comfort Setting Option 3.

Menu

Minimum Value Maximum Value Default Value

Target Time (t9t)

1 minute

240 minutes

60 minutes

Stage Up Percent (SUP)

0%

100%

20%

Stage Down Percent (SdP)

0%

100%

20%

Over Target Threshold (Ott)

1 strike

254 strikes

20 strikes

Under Target Threshold (Utt)

1 strike

254 strikes

20 strikes

Circulator Blower Speed

The Airflow quantity is displayed as a number on the three 

7 segment displays, rounded to the nearest 100 CFM.  

The display alternates airflow amount and the system 

operating status.

Each  furnace  has  a  “Maximum  CFM”  it  is  capable  of 

providing.  All fan operations (Constant CFM, Cooling 

Airflow Profiles, Low and High Stage gas heat airflow, 

outdoor Air Conditioner / Heat Pump Airflow, etc.) are 

based off of multipliers which are percentages of this 

maximum CFM. Max CFM is as follows:

Summary of Contents for AMVS960603BU AA

Page 1: ...serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools parts testing instruments and the appropriat...

Page 2: ...arts testing in struments and the appropriate service manual REVIEWALL SERVICEINFORMATIONINTHEAPPROPRIATESERVICE MANUAL BEFORE BEGINNING REPAIRS OUTSIDE THE U S call 1 713 861 2500 Not a technical ass...

Page 3: ...El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cualquier mo...

Page 4: ...ENTIFICATION 4 NOMENCLATURE The model and manufacturing number are used for positive identification of component parts used in manufacturing Please use these numbers when requesting service or parts i...

Page 5: ...s Steel tubular heat exchanger 115 volt silicon nitride igniter Left or right gas entry Line voltage EAC terminal GMVS96 U GMVS960603BU AA GMVS960805CU AA Goodman Brand 96 Ultra Low NOx Gas Furnace 1...

Page 6: ...the U S A this furnace can be used in the following non industrial commercial applications Schools Office buildings Churches Retail stores Nursing homes Hotels motels Common or office areas In all app...

Page 7: ...T IN PROPERTY DAMAGE EQUIPMENT DAMAGE PERSONAL INJURY OR DEATH Condensate Drain Lines and Drain Trap Acondensing gas furnace achieves its high level of efficiency by extracting almost all of the heat...

Page 8: ...ply pressures must be maintained within the ranges specified below The supply pressure must be constant and available with all other household gas fired appliances operating The minimum gas supply pre...

Page 9: ...l altitudes the air temperature rise must be within the range listed on the the Specification Sheet applicable to your model for the fuel used Manifold pressure adjustments and combustion analysis are...

Page 10: ...all after the power is turned on will run the outdoor unit at full capacity until the call is removed Use this mode for charging If system is running low stage cooling just cycle power and provide a c...

Page 11: ...arget Runtime the temporary heat pump hold will be completely removed and the heat pump will become the primary heat source again if it fails to do so the strike count against the furnace will be rese...

Page 12: ...mps up to full cooling demand airflow by first stepping up to 50 of the full demand for 30 seconds The motor then ramps to 100 of the required airflow A one 1 minute OFF delay at 100 of the cooling ai...

Page 13: ...D ehum Optional Optional Optional if feature supported by thermostat L1 L2 INDOOR BOARD TERMINAL CONNECTIONS OUTDOOR BOARD TERMINAL CONNECTIONS OUTDOOR TRANSFORMER 24V AC 240V GROUNDRECOMMENDED FIELDP...

Page 14: ...Refer to the low voltage wiring diagrams for additional wiring details Dehumidistat close on humidity rise R C G Y D ehum Dehumidistat close on humidity rise Figure 41 Fossil Fuel Applications This f...

Page 15: ...105 C All line voltage wire splices must be made inside the furnace junction box Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install desig...

Page 16: ...sfully been completed the user will have access to system information once in range Option 2 Remove the furnace door ensure the control has power and then read the 3 digits The code will temporarily r...

Page 17: ...scroll through Menus L6F Lm Cr Sr and rFd 4 Press and release the Center Button The center button is used to enter menus and make selections within menus 5 What will be displayed is the currently sele...

Page 18: ...d increments Gas Heat Trim Factor Option Menu Gas Heat airflow may be trimmed from 10 to 10 in 2 increments Gas Heat Stage Multiplier Menu CFM This menu allows adjustment of the low fire CFM multiplie...

Page 19: ...or otherwise trap condensate Use longest radius fittings possible If using 3 venting make the transition from 2 to 3 as close as practically possible Make sure there is no flue gas recirculation into...

Page 20: ...are for vertical or horizontal termination of the combustion air inlet and the exhaust vent pipes on Category IV gas fired condensing furnaces The DCVK 30 kit can be used for 3 diameter pipe systems...

Page 21: ...DRAFT AND CIRCULATION BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check motor windin...

Page 22: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Page 23: ...t As the external static pressure goes up the temperature rise will also increase Consult the proper tables for tempera ture rise limitation BTU HR Calculation Example The unit being tested takes 40 s...

Page 24: ...SERVICING 24 GAS VALVE BURNER ASSEMBLY PRESSURE TRANSDUCER INTEGRATED CONTROL BOARD CONTROL TRANSFORMER PRESSURE SWITCHES VENT PIPE CONNECTION COMBUSTION AIR CONNECTION DRAFT INDUCER Component I D...

Page 25: ...wires must be replaced replace with AWM 105 C 2 64 thick insulation of the same gauge or its equivalent CHECKING THERMOSTAT WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower co...

Page 26: ...motor reinstall blower compartment door 6 Turn on electrical power and verify proper unit operation DISCONNECT ALL POWER BEFORE SERVICING WARNING CHECKING DUCT STATIC The maximum and minimum allowabl...

Page 27: ...erature rise Decrease blower speed to increase temperature rise Refer to Circulator Blower Speed section in the Product Design section of this manual for speed changing details Temperature rise is rel...

Page 28: ...uced draft blower This voltage to the IBD will vary between furnace models and is dependent on what percentage of maximum fire is being called for The power wires are colored red white and black A gre...

Page 29: ...e etc and or consult with local gas utility WARNING HIGH VOLTAGE DISCONNECT ALL ELECTRICAL POWER AND SHUT OFF GAS SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT...

Page 30: ...E PERSONAL INJURY OR DEATH 6 Turn on gas to furnace and check for leaks If leaks are found repair and then reinstall burner compartment door 7 Turn on electrical power and verify proper unit operation...

Page 31: ...ition control No voltage Check transformer room thermostat and wiring If you have 24 volts coming off the transformer but receive approximately 13 volts on the terminal board between C and R check for...

Page 32: ...utively satisfy the thermostat under the set target time for this number of cycles the system will transition to the heat pump for primary heating dP Menu is enabled if the CF menu is set to 6 this pe...

Page 33: ...ge non communicating units AC Compressor Cooling Single Stage single stage non comm units AC1 Compressor Cooling Low Stage communicating units AC2 Compressor Cooling High Stage communicating units dHU...

Page 34: ...a set is correct for the specific model re populate data using correct memory card if required Furnace operates at reduced performance Airflow delivered is less than expected Circulator blower motor i...

Page 35: ...r Furnace fails to operate 1 Analog Pressure Error Blocked Vent Error Need to check the APS Sensor or its connection if this error is occurred The failure conditions occur as per the following for 5 s...

Page 36: ...essure switch circuit is closed at start of heating cycle Low stage pressure switch contacts sticking Short in pressure switch circuit wiring Replace low stage pressure switch Repair short in wiring I...

Page 37: ...erify and correct unit ground wiring if needed Check igniter output from control replace if necessary Furnace fails to operate on high stage furnace operates normally on low stage Induced draft blower...

Page 38: ...ch condensate switch open Check evaporator drain pan trap piping Fault Code Recall Accessing the furnace s diagnostic menu provides access to the last six faults detected by the furnace Faults are sto...

Page 39: ...ED CONTROL PK C USE COPPER CONDUCTORS ONLY AT LEAST 105 IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLA...

Page 40: ...contact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN B...

Reviews: