background image

8

3” FLAT INSULATION
RETAINER
(BOTH SIDES)

Figure 4

To complete the conversion, slide the evaporator coil into
the chassis and attach the three (3) access panels. 

(Figure

5).

WRAPPER

INSULATION
JACKET

ZEE COIL
SUPPORT

WRAPPER
STIFFENER

DRAIN PAN
INSULATION KIT

BLOWER
ASSEMBLY

Figure 5

NOTE: 

When converted to downflow position, the coil may

protrude above the cabinet on some models.

Horizontal Conversion

Dedicated Downflow models are not suitable for horizontal
application and must not be used for this type of installation.
The only field modification required for conversion to “Hori-
zontal Right-Hand” is the removal of the plastic knockouts in
the horizontal panel drain connections.  To prevent the hori-
zontal drain pan from sweating in high humidity applications,
it is recommended that a DPIH insulation accessory kit be
used. NOTE: The DPIH insulation kit is not supplied with this
product and should be purchased separately. See 

Table 8

for the correct DPIH kit.

ARUF, ATUF

 or  ARPF Model

Insulation Kit

1729 / 1824

DPIH18-32

3030 / 1931 /  3636

DPIH36-42

3642 / 3743  / 4860 / 4961

DPH48-61

Table 8

The following describes converting to “Horizontal Left-Hand”.

Conversion to downflow MUST be performed in an area that
allows access to all sides prior to placing the air handler in its

final location (

See Figure 6

).

 

PRIMARY
DRAIN

SECONDARY
DRAIN

DPIH KIT

Figure 6

1. Remove the (3) air handler access panels.

2. Remove the “J” shaped bracket that retains the evapo-

rator coil.

3. Remove the flowrator from the lower left side access

panel and slide out the evaporator coil and horizontal
drain pan.

4. Remove the gasket from the horizontal pan drain con-

nections.

5. Remove the oval shaped plastic plug from the left side

access panel.  Remove the oval shaped rubber gasket
seal from the lower right side access panel.

6. The drain connections for the horizontal pan are sealed

with a thin coating of plastic.  Carefully knock out this
plastic seal with a screwdriver and hammer.  

Note:  The

upper drain will become the secondary drain which
is mandatory in many municipalities .

7. Install the plastic plug removed in step 5 to the right

side lower access panel and the oval shaped rubber
gasket to the lower left access panel.

8. Reinstall the evaporator coil with the horizontal panel

on the left side.  Note: Push the assembly completely to
the rear to ensure the engagement of the upflow pan
with the rear channel bracket.

9. Install the “J” bracket (removed in step 2) to support the

upflow pan to the tie channel.

10. Attach all panels and the metering device.

Condensate Removal

The coil drain pan has a primary and an optional secondary
drain with 3/4" NPT female connections. The connectors re-
quired can be 3/4" NPT male either PVC, CPVC or metal
pipe and should be hand tightened to a torque of approxi-
mately 37 in-lbs. to prevent damage to the drain pan connec-
tion. An insertion depth between .355 to .485 inches (3-5
turns) should be expected at this torque. Use the female (3/4
fpt) threaded fitting that protrudes outside of the enclosure
for external connections.

1. Ensure drain pan hole is NOT obstructed.

2. To prevent potential sweating and dripping on to finished

space, it may be necessary to insulate the condensate

Summary of Contents for ADPF

Page 1: ...LING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your respon...

Page 2: ...Canadian Electric Code CSA C22 1 uninterrupted unbroken When installing or servicing this equipment safety clothing including hand and eye protection is strongly recommended If installing in an area t...

Page 3: ...he Prod uct Registration page Product limited warranty certificates for models currently in production can be viewed at www goodmanmfg com or www amana hac com If your model is not currently in pro du...

Page 4: ...e con structed in a manner that limits restrictions and maintains suitable air velocity Ductwork is to be sealed to the unit in a manner that will prevent leakage Return Ductwork DO NOT TERMINATE THE...

Page 5: ...g the ground lug in the unit control box to the building electrical service panel Other methods of grounding are permitted if performed in accordance with the National Electric Code NEC American Natio...

Page 6: ...n denser or heat pump The 24V control voltage connects the air handler to the room thermostat and condenser Low volt age wiring is to be copper conductors A minimum of 18AWG must be used for installat...

Page 7: ...r handler in its final location To prevent the evaporator coil pan from sweat ing the DPI accessory insulation kit is to be used when per forming this conversion NOTE The DPI kit is not supplied with...

Page 8: ...left side access panel and slide out the evaporator coil and horizontal drain pan 4 Remove the gasket from the horizontal pan drain con nections 5 Remove the oval shaped plastic plug from the left sid...

Page 9: ...EQUIRED AT TRAP Drain Connection 2 MIN Figure 7 Use of a condensate removal pump is permitted when nec essary This condensate pump should have provisions for shutting off the control voltage should a...

Page 10: ...Assumes dry coil with filter in place SCFM correction for wet coil 4 208V 240V 0 1 0 2 0 3 0 4 0 5 High 1 155 1 090 1 025 950 895 ADPF18241 16 Med 940 890 860 815 755 Low 695 665 650 610 550 High 1 7...

Page 11: ...ge Return air is not obtained from any areas where there may be objectionable odors flammable vapors or prod ucts of combustion such as carbon monoxide CO which may cause serious personal injury or de...

Page 12: ...STAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2 WIRES BLUE WHITE GREEN RED CONTACTOR COIL AT AR UNIT Figure 8 Low Voltage Wiring Diagram for...

Page 13: ...STAT CLOSE ON TEMPERATURE FALL RED GREEN WHITE BLUE AT AR UNIT R Y O W BL 18 GA 5 WIRE 18 GA 7 WIRE NOTE R G BR W BL R R I B 18 GA 6 WIRE NEEDED WHEN OT IS USED R 18 GA 7 WIRE NEEDED WHEN TWO OT S ARE...

Page 14: ...HEN MATCHING THE ASPF AIR HANDLERS TO A SINGLE SPEED COOL ING OR HEAT PUMP UNIT REMEMBER TO CONNECT Y FROM THE THERMOSTAT TO THE Y2 ON THE LOW VOLTAGE TERMINAL BOARD An equivalent thermostat can be us...

Page 15: ...B YL BL CONDENSING UNIT 24V CONNECTION BL YL GR RD 18 GA 5 WIRES WITH COOLING 4 WIRES WITHOUT WH YL BR BR BR YL G C R HEAT PUMP UNIT WITH OPTIONAL HEAT KITS OF 10 kW AND BELOW C W1 W2 Y2 Y1 O G R TB 1...

Page 16: ...IT WITH OPTIONAL HEAT KITS OF 15 kW AND ABOVE C W1 W2 Y2 Y1 O G R TB 18 GA 7 WIRE O Y C W2 R Y O W2 E RD GR BL OR YL YL BL OR WH BR WH BL WH WH RD BR RD WH GR YL OR OR RD OR NOTES 1 OUTDOOR THERMOSTAT...

Page 17: ...R A L G H E A T K I T M O T O R The Electronic Blower Time Delay Relay provides power to the blower motor with a delay of 7 seconds after 24VAC is applied to G After 24VAC is removed from G the blower...

Page 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 20: ...20 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2004 2010 Goodman Manufacturing Company L P...

Reviews: